ML19257C470

From kanterella
Jump to navigation Jump to search
Forwards IE Circular 80-01, Svc Advice for GE Induction Disc Relays. No Response Required
ML19257C470
Person / Time
Site: Beaver Valley
Issue date: 01/17/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Dunn C
DUQUESNE LIGHT CO.
References
NUDOCS 8001290176
Download: ML19257C470 (1)


Text

fA

[

o 8%

~g UNITED STATES g

NUCLEAR REGULATORY COMMISSION 3.*-

E REGION I

          • ,$[

8, %,

631 PARK AVENUE U

KING OF PRUSSIA, PENNSYLVANIA 19406 Docket No. 50-334 Jay 17 ;ggg Duquesne Light Company ATTN:

Mr. C. N. Dunn Vice President Operations Division 435 Sixth Avenue Pittsburgh, Pennsylvania 15219 Gentlemen:

The enclosed IE Circular No. 80-01 is forwarded to you for information and, if applicable, necessary action in accordance to the attached General Electric Company Service Advice 721-162.2. No written response to this Circular is required. If you have any questions related to the subject, please contact this office.

Sincerely, k

n oyce H. Grier

" Director

Enclosures:

1.

IE Circular No. 80-01 2.

List of Recently Issued IE Circulars CONTACT:

S. D. Ebneter (215-337-5296) cc w/encls:

F. Bissert, Technical Assistant Nuclear R. Washabaugh, QA Manager J. Werling, Station Superintendent G. Moore, General Superintendent, Power Stations Department J. J. Carey, Nuclear Technical Assistant R. Martin, Nuclear Engineer 1839 514 8001290 p

iqc

ENCLOSURE 1 UNITED STATES SSINS No.:

6830 NUCLEAR REGULATORY COMMISSION Accessions No.:

0FFICE OF INSPECTION AND ENFORCEMENT 7912190644 WASHINGTON, D.C.

20555 IE Circular No. 80-01 Date:

January 17, 1980 Page 1 of 1 SERVICE ADVICE FOR GENERAL ELECTRIC INDUCTION DISC REL'YS Alabama Power Company reported to the NRC on October 16, 1979 a potential problem with certain General Electric Company induction disc type protective relays.

A higher than normal pick-up value was caused by petroleum jelly lubricant which under high temperature conditions can migrate to the backstop.

At room temperature the lubricant can become adhesive and cause pickup values to be higher than setpoint values.

General Electric (GE) laboratory confirmed some higher than normal pickup values and recommended that users determine whether relays meeting the following criteria are in use at their facilities:

(1) Relay type:

IAC, IAV, ICR, or IJCV, AND (2) The relay date code (which is printed on a 3/4" x 3/8" sticker affixed to the relay cradle) has a number less than 50, followed by any of the following two letter codes:

(a) Any first letter followed by H, J, K, L, or M; or (b) The letter combinations AN, BN, CN, DN, EN, DG, EG, FG, GG, HG, JG, KG, LG or MG.

For example, 31GK wuuld be considered, while 50 GK or 23HN would not be considered.

Experience has shown that the cleaning procedure recommended in GE Service Advice 721-162.1 may not in all cases remove all of the petroleum jelly which is lodged in place.

Based on the above, licensees are advised to apply G.E. Service Advice 721-162.2 (Attachment A) to all relays that fall within the above two criteria.

No written response to this Circular is required.