ML19256E860

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-17,Revision 1, Pipe Cracks in Stagnant Borated Water Sys at PWR Plants. No Response Required
ML19256E860
Person / Time
Site: Summer 
Issue date: 10/29/1979
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Nichols T
SOUTH CAROLINA ELECTRIC & GAS CO.
References
NUDOCS 7911150429
Download: ML19256E860 (2)


Text

/

'o UNITED STATES NUCLEAR REGULATORY COMMISSION 5

g

. r REGION 11 o

101 MARIETTA ST., N.W., SUITE 3100 Y

i 4

o ATLANTA, GEORGIA 30303 OCT 2 31979 In Reply Refer To:

RII:JP0 50-395 South Carolina Electric and Gas Company Attn:

T. C. Nichols, Jr., Vice President Power Production and System Operations P. O. Box 764 Columbia, South Carolina 29218 Gentlemen:

The enclosed Bulletin No. 79-17, Revision 1 is forwarded to you for information.

No written response is required.

However, the potential corrosion behavior of safety-related systems as it regards your plant over the long-term should be taken into consideration.

If you desire additional information concerning this matter, please contact this office.

Sincerely, C---

N?,

James P. O'Reilly Director

Enclosure:

IE Bulletin No. 79-17, Revision I w/encls.

1336 303 7 91115 0 + z "I

UNITED STATES SSINS No.:

6820 NUCLEAR REGULATORY COMMISSION Accession No.:

OFFICE OF INSPECTION AND ENFORCEMENT 7908220157 WASHINGTON, D.C.

20555 23 October 29, 1979 IE Bulletin No. 79-17 Revision 1 PIPE CRACKS IN STAGNANT BORATED WATER SYSTEMS AT PWR PLANTS Description of Circumstances:

IE Bulletin No. 79-17, issued July 26, 1979, provided information on the cracking R1 experienced to date in safety-related stainless steel piping systems at PWR R1 plants.

Certain actions were required of all PWR facilities with an operating R1 license within a specified 90-day time frame.

R1 After several discussions with licensee owner group representatives and inspection R1 agencies, it has been determined that the requiremente of Item 2, particularly R1 the ultrasonic examination, may be impractical because of unavailability of R1 qualified personnel in certain cases to complete the inspections within the time R1 specified by the Bulletin. To alleviate this situation and allow licensees the F1 resources of improved ultrasonic inspection capabilities, a time extension and R1 clarifications to the bulletin have been made. These are referenced to the R1 affected items of the original bulletin.

R1 During the period of November 1974 to February 1977 a number of cracking incidents have been experienced in safety-related stainless steel piping systems and por-tions of systems which contain oxygenated, stagnant or essentially stagnant bor-ated water. Metallurgical investigations revealed these cracks occurred in the weld heat affected zone of 8-inch to 10-inch type 304 material (schedule 10 and 40), initiating on the piping I.D. surface and propagating in either an inter-granular or transgranular mode typical of Stress Corrosion Cracking. Analysis indicated the probable corrodents to be chloride and orygen contamination in the affected systems.

Plants affected up to this time were Arkansas Nuclear Unit 1, R. E. Ginna, H. B. Robinsta Unit 2, Crystal River Unit 3, San Onofre Unit 1, and Surry Units 1 and 2.

The NRC issued Circular No. 76-06 (copy enclosed) in view of the apparent generic nature of the problem.

During the refueling outage of Three Mile Island Unit I which began in February of this year, visual inspections disclosed five (5) through-wall cracks at welds in the spent fuel cooling system piping and one (1) at a weld in the decay heat removal system. These cracks were found as a result of local boric acid buildup and later confirmed by liquia penetrant tests. This initial identification of cracking was reported to the NRC in a Licensee Event Report (LER) dated May 16, 1979. A preliminary metallurgical analy section of cracked and leaking weld join DUPLICATE DOCUMENT R1 - Identifies those additions or revis Entire document previcisly entered into system ur ler:

bf j

ANO u gr ag; No. of pages:

If