PNO-79-153:on 790612,reactor Tripped from 50% Power Due to Closure of Four Inboard Msivs.Caused by Blown Fuses in Ac & Dc Power Supplies to Air Control Solenoids for Four Inboard Valves
ML19256C993
Person / Time
Site: Brunswick 
Issue date: 06/13/1979
From: Bryan S, Klingler G, Nolan F
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-79-153, NUDOCS 7910150828
Download: ML19256C993 (1)


Text

i t>(

PRELIMINARY NOTIFICATION June 13, 1979 FRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE -- PNO-79-153 This oreliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance.

The information presented is as initially received without verification or evaluation and is basically all that is known by IE staff as of this date FACILITY:

Carolina Power and Light Ccmpany Brunswick, Unit No. 2 Docket No. 50-324 Southport, North Carolina S"BJECT:

MAIN STEAM ISOLATION VALVE CLOSURE AND REACTOR TRIP At 1:00 p.m. on June 12, Brunswick Unit 2 tripped from 50% power due to closure of the four inboard main steam isolation valves (MSIVs).

The trip was caused by blown fuses in the AC and DC power supplies to the air control solenoids for the four inboard valves.

The cause is attributed to a wiring error associated with an intermittent ground.

One of the power leads to the DC solenoid for valve "D" was found wired to a terminal of the AC solenoid.

During the period of opera-tion, only the AC solenoid was energized maintaining the valve open.

This wiring error occurred during the recent refueling outage when the MSIVs were removed for repair.

The other seven MSIVs were inspected and found to be wired correctly.

Media interest is not anticipated. A news release is not planned by the licensee nor the NRC.

The State of North Carolina has been informed.

Region II (Atlanta) received notification of this occurrence by telephone from the licensee at 3:00 p.m. on June 12.

This information is current as of 12:15 p.m.

on June 13.

Centact:

GKlingler, IE x28019 FNolan, IE x28019 SEBryan, IE x28019 D:stribution-Transmitted H St Q.I.

' lT Chairman Hendrie Commissioner Bradford S. J. Chilk, SECY Ccrcissioner Kennedy Commissioner Ahearne C. C. Kammerer, CA C:mcissioner Gilinsky ACRS (For Distribution)

Transmitted:

MSBB 4*fD P. Bldg 7.'f/C L/iy V,

Stello, IE L V Gossick, EDO H. R. Denton, NRR Region L

  • I H.

L. Ornstein, EDO R. C. DeYoung, NRR J. J. Fouchard, PA R. J. Mattson, NRR N. M. Haller, MPA R. S. Boyd, NRR (MAIL)

SS Bldg V ! L(L/ c /

J. J. Cummings, OIA R. G. Ryat, OSP W.J.Dircks,Nh[Se H. F. Shapar, ELD R. Minogue, SD S. Levine, RES PRELIMINARY NOTIFICATION 1450 194 4910 un D2&

J