PNO-79-04:on 790108,instantaneous Gaseous Release Rate Specified by Tech Spec Was Exceeded by 270%.Seventy Ci of Noble Gas Activity Was Released for 1.5 Hours.Caused by Cooling Sys Not Operating During Reactor Shutdown
ML19256C741
Person / Time
Site: Peach Bottom 
Issue date: 01/09/1979
From: Liza Cunningham, Higginbotham L
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-79-004, PNO-79-4, NUDOCS 7910120394
Download: ML19256C741 (1)


Text

.

PRELIMINARY NOTIFICATION g

January 9, 1979 R

(

PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-79-04 V

This preliminary notification constitutes EARLY notice of event of POSSIBLE safety or public interest significance.

The information presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.

Facility:

Philadelphia Electric Company Peach. Bottom Atomic Power Station, Unit 3 (DN E')-278)

Lancaster, PA

Subject:

RELEASE OF GASE0US ACTIVITY IN EXCESS OF TECHNICAL SPECIFICATIONS On January 8,1979, at 5:00 a.m. the instantaneous gaseous release rate specified by Technical Specification 3.8.C.1 was exceeded by 270% for 1 1/2 hours releasing approximately 70 Curies of noble gas activity.

The reactor had been shutdown on January 5,1979 and was under-going maintenance on the Reactor Core Isolation Cooling (RCIC) system.

The shutdown cooling system was being used periodically to maintain coolant temperature low enough to prevent degassification.

Investigation by the licensee revealed that for the 1 1/2 hour period,

+he shutdown cooling system was not operated, resulting ir. coolant temperature exceeding 200 F and causing degassing.

During this time RCIC isostion valves were dismantled and provided a leak path from the Reactor Building via the Main Steam Isolation Valve (MSIV) Room to the Unit 3 vent stack.

Three personnel (two operators and one health physics technician) had entered the MSIV Room during this time and may have received exposure.

The licensee is currently evaluating their exposure.

An NRC inspector is currently onsite conducting a review of this occurrence.

Media interest is not expected.

The Commonwealth of Pennsylvania has been informed A press release is being considered by the NRC.

NRC, Region I, (Philadelphia) received notification of this occurrence by telephone from the licensee at 3:00 p.m., January 8,1979.

Contact:

LJCunningham, IE x28188 LBHigginbotham, IE x28454

/b Distribution:

Transmitted H St i

Cnairman Hendrie.

Commissioner Bradford S. J. Chilk, SECY Commissioner Kennedy Commissioner Ahearne C. C. Kammerer, CA (ForDistribution)

Commissioner Gilinsky.h I'/

P.Bldgd.b J. G. Davis, IE Transmitted:

MNBB L. V. Gossick, ED0 H. R. Denton, NRR Region 1 4.9/.1 J. J. Fouchard, PA R. C. DeYoung, NRR N. M. Haller, MPA R. J. Mattson, NRR R. G. Ryan, OSP V. Stello, NRR (MAIL)

~

H. K. Shapar, ELD R. S. Boyd, NRR J. J. Cummir.gs, 01A C

SS Bldg 4.9 0 R. Minogue, SD W. J. Dircks, NMSS PRELIMINARY NOTIFICATION

1448.157-