ML19256B524

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-15, Deep Draft Pump Deficiencies. Action Required
ML19256B524
Person / Time
Site: Haddam Neck File:Connecticut Yankee Atomic Power Co icon.png
Issue date: 07/11/1979
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Counsil W
CONNECTICUT YANKEE ATOMIC POWER CO.
References
NUDOCS 7907270326
Download: ML19256B524 (1)


Text

[pe* "'%g),

pg UNITED STATES y y 3,, c f',g NUCLEAR REGULATORY COMMISSION

/

c REGION 1

~ ## o[

/#

631 PARK AVENUE 0,

D KING OF PRUSSIA, PENNSYLVANIA 19406 July 11, 1979

. Docket No. 50-213 Connecticut Yankee Atomic Power Company ATTN:

Mr. W. G. Counsil Vice President - Nuclear Engineering and Operations P. O. Box 270 Hartford, Connecticut 06101 Gentlemen:

The enclosed Bulletin No. 79-15 is forwarded to you for action.

A written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely,

/

wt

~

Boyce H.

rier d irector

Enclosures:

1.

IE Bulletin No. 79-15 w/ Attachments 2.

Listing of IE Bulletins Issued in Last Twelve Months cc w/encls:

R. Graves, Plant Superintendent D. G. Diedrick, Manager of Quality Assurance J. R. Himmelwright, Licensing Safeguards Engineer 1

7 9072703h jo q

ENCLOSURE 1 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Bulle'.in No. 79-15 9 ate-July 11, 1979 Page 1 of 3 D2EP DRAFT PUMP DEFICIENCIES Description of Circumstances:

On October 20, 1978, Commonwealth Edison Company reported that manufacturing deficiencies had been identified in new high pressure core spray, low pressure core spray, and residual heat removal pumps manufactured by Ingersoll-Rand (I-R)

Company, Cameron Pump Division.

Each of these pumps is a vertical turbine pump with impellers located in bowls in a sump or a self contained barrel.

The motor (prime mover) is located at the highest pump elevation to take into account maximum flooding at the site or space considerations.

The suction is at the lower end of the pump while the discharge head is just below the driver.

Bearings supporting the vertical shaft segments (usually 5 to 10 segments) are either self lubricated, force fed (lubricated by fluid being pumped), or oil lubricated and maintained within their own isolated system.

These pumps are designated as " Deep Draft".

Figures 1&2 show typical outlines of such pumps.

The internal deficiencies, identified through dimensional and visual inspections were as follows:

Low Pressure Core Spray Pumps (I-R Model No. 29APKD-5) (Date of Manufacture -

Feburary 1973)

Loose impeller bolts and bolts improperly staked Loose key - keyway fit Excessive runout on pump shaft Bearing showed wear Bearing clearance exceeded recommended tolerance Coupling thread galled Wear ring clearance out-of-specification Impeller-to-shaft clearance out of specification Cracks found in second-and-third-stage impellers Stuffing box bushings were severely galled High Pressure Core Spray Pumps (I-R Ma September 1972)

DUPLICATE DOCUMENT Bearing clearance exceeded recommen Wear ring clearance out-of specific Entire document previously Bearings showed wear entered into system under: