ML19253B653

From kanterella
Jump to navigation Jump to search
Discusses Need for Plant Designs to Consider Leaks Encountered During Recirculation of Sodium Hydroxide Tank. Corrective Backfit Operations May Be Necessary at Existing Plants
ML19253B653
Person / Time
Site: Crane 
Issue date: 06/21/1974
From: Brunner E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Thornburg H
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML19253B649 List:
References
NUDOCS 7910160740
Download: ML19253B653 (1)


Text

,,

7 UNITEo STATES t

ATOMIC ENERGY COMMISSION -

[4(% j ;,%

oanscTon ATE or HEcutAvony oPER ATroNS

/

[W- /[f' REoroN 1 631 P ARK AVENUE

~. /f KING oF PRUSSI A, pef 4NSYLVANI A 15406 4

kN 211gy H. D. Thornburg, Chief, Field Support and Enforcement Branch Directorate of Regulatory Operations, HQ RO INSPECTION REPORT No. 50-289/74-25 METROPOLITRI EDISON COMPANY LICENSE NO. DPR-50 The subject inspection report is forwarded for appropriate Headquarters action.

The action requested is discussed below:

Detail 7 of the inspection report discusses the dilution of the Sodium Thiosulfate Tank during recirculation of the Sodium Hydroxide Tank as a result of leakage thru a normally closed valve and the corrective actions taken and being considered by the licensee. We note that the licensee is acting responsibly to prevent a recurrence of'this situation.

Technical Specifications require that each tank be sampled quarterly and after makeup. The safety implications of this event are that it would be possible to operate unknowingly with a tank out of specs until the next sample period. We believe this occurrence has disclosed an apparent design deficiency which may be generic to B&W designed plants.

We recommend that Licensing review this matter for possible backfit considerations on currently licensed plants and for possible considera-tion during design review of plants not yet licensed.

The documentation letter and inspection report for this inspection have been sent to the licensee from this office.

E. J. Brunner, Chief Reactor Operations Branch

Enclosures:

1.

' Copy of Documentation Letter and Description of Violations 2.

RO Inspection Report No. 50-289/74-25

[44 t7910160 W O