E(pn "Ec (o,
UNITED STATES
$. k.hj\\. oI',E NUCLE AR REGULATORY COMMISSION
<!u
^
REGION V
/
o $id 1990 N. CALIFORNIA BOUL2VARD g
o SUITE 202, WALNUT CR E EK PLAZA WALNUT CRE E K, CALIFORNI A 94596 August 7, 1979 Docket l'os. 50-528 50-529 50-530 Arizona Public Service Company P. O. Box 21666 Phoenix, Arizona 83036 Attention: Mr. E. E. Van Brunt, Jr.
Vice President, Construction Projects Gentlemen:
The enclosed Bulletin 79-18 is forwarded to you for information.
fio written response is required.
If you desire additional information regarding this matter, please contact this office.
Sincerely, n
{llD d L.
m R. H. Engelken Director
Enclosure:
IE Bulletin No. 79-18 cc w/ enclosure:
F. W. Hartley, APS 761345 to08210f6@
ggasuar
Accessions "o: 7908030403 SSINS No:
6820 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 August 7, 1979 IE Bulletin No. 79-18 AUDIBILITY PROBLEMS ENCOUNTERED ON EVACUATION OF PERSONNEL FROM HIGH-NOISE AREAS Description of Circumstances:
In January 1979, a number of licensee personnel were engaged in routine activities in the auxiliary building at the Florida Power Corporation, Crystal River Unit 3 nuclear plant.
While these indi'.icuals were working in the auxiliary building, in a high-noise (fan) area, an unplanned release of radio-active noble gases was detected by building monitors within the auxiliary building at concentrations which caused the licensee to initiate the facility emergency plan auxiliary building evacuation procedure.
The facility Emer-gency Officer (Shift Supervisor) assessed the monitor readings and initiated ar auxiliary building evacuation. The evacuation announcement, made over the 1 :ensee's PA system, was not heard by the personnel working in the high-noise area.
Licensee personnel did evacuate the auxiliary building upon observing that other parsonnel had lef t, and af ter calling the control room to inquire if an evacuation had been initiated During these occurrences, licensee personnel were not exposed to quantities of radionuclides above regulatory guidance.
However, the potential existed for inadvertent unnecessary exposure of individuals to radioactive materials.
Subsequent to the NRC followup inspection of this occurrence. Florida Power Corporation initiated an assessment of this situation and performed an engineering evaluation and identified several plant areas where the annun-ciator system needed audibility improvement. The licensee has installed a new auxiliary building evacuation tone signal and may add visual alarm indi-cators in areas of very high-noise.
Action to be Taken by the Licensees:
For all power reactor facilities with an operating license:
1.
Determine whether current alarm systems and evacuation announcement systems are clearly audible or visible throughout all plant areas with emphasis on high-noise areas.
Determination in high noise areas must be made with the maximum anticipated noise level.
761346
IE Bulletin fio. 79-18 August 7, 1979 Page 2 of 2 2.
Determine what corrective action is necessary to assure that areas identified as inaudible areas in (1) above, will receive adequate audible /
visual evacuation signals.
In areas where adequate audible / visual evacua-tion signals cannot be assured by hardware changes, determine what addi-tional administrative P.easures are necessary to assure personnel evacuation.
3.
Submit within 45 days of the date of issuance of this Bulletin, a written report of the findings on iten (1), and delineate completed or proposed corrective actions per item (2).
For operating facilities in a refueling or extended outage, the written report must be subnitted within 30 days after plant startup following the outage.
4.
For accessible areas, all corrective actions determined per item (2) must be completed within 120 days of the date of issuance of this Bulletin.
For inaccessible areas, the written report must include a tire schedule for completion of corrective actions in this area.
Reports should be submitte;' to the Director of the appropriate ?!RC Regional Office and a copy should be forwarded to the fBC Office of Inspection and Enforcement, Division of Reactor Operations Inspection, Washington, D.C. 20555.
For all power reactor facilities with a construction pemit, this Bulletin is for information only and no written response is required.
Approved by GAO, B180225 (R0072); clearance expires 7/31/80.
Approval was given under a blanket clearance specifically for identified generic problems.
Enclosure:
LIST OF IE Bulletins Issued in Last 6 flonths 7furI C W
IE Bulletin No. 79-18 Enclosure August 7, 1979 Page 1 of 3 LISTING OF IE BULLETINS ISSUED IN LAST SIX MONTHS Bulletin Subject Date Issued Issued To No.
79-17 Pipe Cracks in Stagnant 7/26/79 All PWR's with Borated Water Systems at operating license PWR Plants 79-16 Vital Area Access Controls 7/26/79 All Holders of and applicants for Power Reactor Operating Licenses who anticipate loading fuel prior to 1981 79-15 Deep Draft Pump 7/11/79 All Pcwer Reactor Deficiencies Licensees with a CP and/or OL 79-14 Seismic Analyses for 6/2/79 All Power Reactor As-Built Safety-Related facilities with an Piping System OL or a CP 79-13 Cracking in Feedwater 6/25/79 All PWRs with an System Piping OL for action. All BWRs with a CP for information.
79-02 Pipe Support Base Plate 6/21/79 All Power Reactor (Rev. 1)
Designs Using Concrete Facilities with an Expansion Anchor Bolts OL or a CP 79-12 Short Period Scrams at 5/31/79 All GE BWR Facilities BWR Facilities with an OL 79-11 Faulty Overcurrent Trip 5/22/79 All Power Reactor Device in Circuit Breakers Facilities with an for Engineered Safety OL or a CP Systems 79-10 Requalification Training 5/11/79 All Power Reactor Program Statistics Facilities with an OL 761348
IE Bulletin No. 79-18 Enclosure August 7, 1979 Page 2 of 3 LISTING OF IF BULLETINS ISSUED IN LAS.
IX MONTHS Bulletin Subject Date Issued Issued To No.
79-09 Failures of GE Type AK-2 4/17/79 All Power Reactor Circuit Breaker in Safety Facilities with an Related Systems OL or CP 79-03 Events Relevant to BWR 4/14/79 All BWR Power Reactor Reactors Identified During Facilities with an OL Three Mile Island Incident 79-07 Seismic Stress Analysis 4/14/79 All Power Reactor of Safety-Relatea Piping Facilities with an OL or CP 79-05C&O6C Nuclear Incident at Three 7/26/79 To all PUR Power Mile Island - Supplement Reactor Facilities with an OL 79-06B Review of Operational 4/14/79 All Combustion Engineer-Errors and Systen Mis-ing Designed Pressurized alignments Identified Water Power Reactor During the Three Mile Facilities with an Island Incident Operating License 79-06A Review of Operational 4/18/79 All Pi ess'irized Water (Rev1)
Errors and System Mis-Power Reactor Facilities alignments Identified of Westinghouse Design During the Three Mile with an OL Island Incident 79-06A Review of Operational 4/14/79 All Pressurized Water Errors and System Mis-Power Reactor Facilities alignments Identified of Westinghouse Design During the Three Mile with an OL Island Incident 79-06 Review of Operational 4/11/79 Al' Pressurized Water Errors and Systen M:s-Pt -- Reactors with an alignments Identiiled OL except B&W facilities During the Three Mile Island Incident
% 1349
i IE Bulletin fo. 79-18 Enclosure August 7, 1979 Page 3 of 3 LISTI!!G OF IE BULLETIllS ISSUED II: LAST SIX MONTHS Bulletin Subject Date Issued Issued To flo.79-05B Nuclear Incident at 5/21/79 All b&W Power Reactor Three Mile Island Facilities with an OL 79-05A Nuclear Incident at 4/5/79 All B&W Power Reactor Three flile Island Facilities with an OL 79-05 fluclear Incident at 4/2/79 All Power Reactor Three Mile Island Facilities with an OL and CP 79-04 Incorrect Ueights for 3/30/79 All Pcwar Reactor Swing Check Valves Facilities with an Manufactured by Velan OL or CP Engineering Corporation 78-12B Atyoical Weld Material 3/19/79 Al', Power Reactor in Reactor Pressure Facilities v:ith an Vessel Welds OL or CP 79-03 Longitudinal Welds Defects 3/12/79 All Power Reactor In ASi1E SA-312 Type 304 Facilities with an Stainless Steel Pipe Spcols OL or CP Manufactured by Youngstown Welding and Engineering Co.79-01A Environnental Oualification 6/6/79 All Power Reactor of Class 1E Equipment Facilities with an (Deficiencies in the Envi-OL or CP ronnental Dualification of ASCO Solenoid Valves)