t t
APPENDIX A NOTICE OF VIOLATION Mis.eissippi Power and Light Company License No. CPPR-119 Based on the results of the NRC inspection conducted on June 28-30, 1978, it appears that certain of your activities were not conducted in full compliance with NRC requirements as indicated below.
These items have been categorized as described in our correspondence to you dats :
December 31, 1974.
Criterion V of Appendix B to 10 CFR 50, as implement, ' by the PSAR, Paragraph 17.1.5, requires in part, " Activities af f ecting quality shall be prescribed by documented instructions, procedures,... and shall be accomplished in accordance with these instructions, procedures,.
In addition, Specification No. 9645-C-191.0, I
paragral.i 8.1.5.1.5 and referenced ASTM Standard, C-31-69, require that concrete test specimens made in the field be stored and cured during the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> under conditions that maintain the tem, rature in the range of 60 to 80 degrees Fahrenheit.
Contrary to the above requirements, on June 28, 1978, test cylinder sets 2650 A-D, 2651 A-D, 2652 A-D, 2653 A-D and 2654 A-D were being exposed to full sun at an ambient temperature of 99 degrees Fahrenheit.
This is an infraction.
(
1032
,_ 5 lSOCDO N