STN 5]-482/79-04 Appendix A NOTICE OF VIOLATION Based on the results of the NPC inspection conducted daring the period March 5-8,1979, it appears that certain of your activities were not conducted in full compliance with the conditions of your NRC Construction Permit No. CPPR-147 as indicated below:
10 CFR Part 50, Appendix B, Criterion V states in part, " Activities affecting quality shall be prescribed by documented instructions, procedures, or drawings, of a type appropriate to the circumstances and shall be accomplished in accordance with these instructions, procedures, or drawings."
Failure to Initiate Nonconformance or Deficiency Reports Daniel Procedure QCP-I-04, Rev. O, paragraph 3.5 states in pact,
" Discrepant conditions which cannot be corrected during in-process inspection shall be documented and controlled using a Noncon-formance or Deficiency Report...."
Contrary to the above:
Temperatures in the concrete lab curing room fell below the ASTM C-31 minimum tolerance of 70.4 F for three periods of time and the recorder failed to record temperature data for one period of time, as listed below, and Nonconformance or Deficiency reports were not initiated.
Concrete Lab Curing Room Temperature From To Lowest Temperatuge Date Time Time Date Recorded F
12/5/77 6 p.m.
6 a.m.
12/7/77 69.8 12/9/77 6 a.m.
6 a.m.
12/11/77 68.7 12/20/77 6 a.m.
6 p.m.
12/21/77 67.14 12/30/77 11 :30 p.m.
7 a.m.
1/3/78 no record This is an infraction.