ML19225C410

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 790402-03 & 13-23
ML19225C410
Person / Time
Site: Comanche Peak  
Issue date: 05/14/1979
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML19225C405 List:
References
50-445-79-11, 50-446-79-11, NUDOCS 7907300250
Download: ML19225C410 (1)


Text

. _.

50-445/79-11 50-446/79-11 Appendix A NOTICE OF VIOLATION Based on the results of the NRC investigation conducted during the periods April 2-3 and April 13-23, 1979, it appears that certain of your activities were not conducted in full compliance with the conditions of your NRC Construction Permit No. CPPR-126 63 indicated below:

Failure to Implement the Quality Assurance Program For Civil Construction 10 CFR 50, Appendix B, Criterion II requires that a quality assurance program be established and implemented for the construction of the structures important to safety of the nuclear plant.

The Taxas Utilities Generating Company Comanche Peak Steam Electric Station Quality Assurance Plan affirms the intention to fulfill this require-ment. The CPSES " Civil Inspection Manual" provides a body of inspection and testing procedures required to implement the Quality Assurance Plan.

Contrary to the above:

On January 18, 1979, personnel of the civil construction labor force placed an undetermined amount of concrete of an unknown quality on the dome of the Unit 1 containment without the knowledge of your Quality Assurance organization and without benefit of required inspections and testing of the concrete.

This is an infraction.

Sl{

..qg0730 0