ML19210B093
| ML19210B093 | |
| Person / Time | |
|---|---|
| Site: | Crane |
| Issue date: | 11/30/1977 |
| From: | Reid R Office of Nuclear Reactor Regulation |
| To: | |
| Shared Package | |
| ML19210B088 | List: |
| References | |
| NUDOCS 7911040036 | |
| Download: ML19210B093 (25) | |
Text
-.-
~
j'#
\\
UNITED STATES NUCLEAR REGULATORY COMMISSION y
a 1g -.h WASHINGTON, D. C. 20555 g
%,,*9. y- --[
METROPOLITAN EDISON COMPANY JERSEY CENTRAL POWER AND LIGHT COMPANY PENNSYLVANIA ELECTRIC COMPANY DOCKET NO. 50 289 THREE MILE ISLAND NUCLEAR STATION UNIT NO. 1 AMENDMENT TO FACILITY OPEPATING LICENSE Armndment No. 32 License.No. OPR-50 1.
The Nuclear Regulatory Ccmission (the Comissien) has found that:
.A.. The application for amendment by Metropolf'an Edison Company, Jersey Central Power and Light Company, and Pennsylvania Electric Company (the licensees) dated February 10, 1977, as revised August 12, 1977, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth'in 10 CFR Chapter I; B.
The facility will operate in confomity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.
There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health
. and safety of the public, and (11) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this amendment will not be inimical to the ccmon defense and security or to the health and safety of the public; and
,E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the-Comission's regulations and all applicable requirements have been satisfied.
.a e
e
/c 1 r, r e) 1I9d 1 Jus 9
J 911040 0 3 6
- = - -
9
.A e
j n
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-50 is hereby amended to read as follows:
(2) Technical Soecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 32, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment becomes effective 30 days after the date of its issuance.
FOR THE NUC1. EAR REGULATORY C0FF.ISSION
~
~ ~
~
Robert W. Reid, Chief
~
Operating Reactors Branch #4 Division of Operating Reactors Atta'chment:
Changes to the Technical Specifications Date of Issuance: November 30, 1977 g
s b
g 3_
1-
/
- M d'
e m
,m b
"~ '
~'
=
4 ATTACHMEtiT TO LICEflSE AMEflDMEftT f0. 32 FACILITY OPERATItiG LICEilSE l'0. DPR-50 DOCKET f:0. 50-289 Revise Appendix A as follows:
,- Insert Pages Remove Pages 1-5 1-5 3-86 thru 3-93 4-72 thru 4-73c 4-74 thru 4-76 6-2 6-2 6-3 6-3 6-6a 6-6a 6-11 6-11 6-26 Changes on the revised pages are shown by marginal lines.
R O f
1500 130 4
e
l.
n 1.6 PCUER DIS'RI2U'"ICN 1.6.1 QUADRA'T:' PC'4IR TILT Quadrant power tilt is defined by the following equatien and is expiessed in percent.
100 Fever in any cere cuad snt
-1 Average pover of all quadrants The quadrant tilt li=its are stated in Specifica:1cn 3.5 2.k.
1.6.2 REACTCR ?C'4ER D:3ALA3CZ Reactor ;cver i= balance is the ;cver in the tcp half of the ec e =inus the power in the bette= half cf the core expressed as a percentage of rated ;cver.
Imbalance is =cnitored centinuously by the RFS using input frc= the power range channels.
!= balance " *ts are defined in Specifica ics 2.1 and i= balance set;oints are defined in Specification 2.3 1.7 CON"'ADEN"' 2... mR I""'
Centai==ent integrity exists when the folleving cenditicus are satisfied:
The equi;=ent hatch is closed and sealed and both decrs of the persennel a.
hatch and e=ergency hatch are closed and sealed except as in "b" below.
b.
At least c e door en each of the persen=e1 hatch and e=ergency hatch is closed and sealed during refueling or persennel passage through these hatches.
c.
All nonautc=atic centa#- est isclatica valves and blin:1 flanges are closed as required by the "Ccatai =ent !=te pity Check List" attached to the operating precedure "Ccatai==ent Integrity and Access Li=its."
d.
All autcmatic centa4-ent isolation valves are c;erable er lected closed.
The contain=ent leakage deter =ised at the last testing interval e.
satisfies Specificatien h.h.1.
1.8 FIRE SUFFRESSICU '4ATER SYS"'Et A FIRE SUFFRISSICU '4ATIR SYS m shall ec sist of: a vater scurce, pavity tank or pu=p and distributien piping with asscelated sectic alizing ec rcl or isolatien valves. Such valves include yard hydrant curb valves, and the first valve upstres= of the water flew alar = device en each sprinkler, hose standpipe or spray syste: riser.
Amendment No.
32 1-5
9?
3.18 FIRE FECTICTICN 3.18.1 FIRI DCICTICN INSTRCCATICU Aeolicabilit-r: At all ti=es when equip =ent in that fire detection :cce is required to be operable.
objective: To insure adequate fire detectica capability.
Steeificatien:
3 18.1.1 The =ini=u= fire detectica i=str=entation for each fire detectice
~
zone shewn in Table 3.18-1 shall be operable.
3 18.1.2 With the nunber of CFIRA3L2 fire detection instr =.ents less than required by Table 3.18-1.
a.
Within 1 heur, establish a fire vatch patr:1 to inspect the zcue with the incperable instr =ent(s) at least cuce per hour, and b
Restore the inoperable instrument (s) to OPERA 3LE status within 14 days or prepare and submit a special report to the Con: mission within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the in-strument(s) to OPERABLE status.
Bases OFIRA3ILITY of the fire detection instr =entatien ensures that adequate warning capabilit/ is available fer the prenpt detectics of fires. S.is capability is required in order to detect and locate fires ' + % " early stages. Frc=pt detection of fires vill reduce the potential for da= age to safety related equip =ent and is an integral ele =ent in the overall facility fire protectica Prc5:a=.
In the event that a pertien of the fire detection instr =entation is ineperable, the establish =ent of frequent ' fire patrols in the affected areas is required to provide detection capability until the inoperable instrumentation is restored to operability.
7 0 ' N%(Te D
1 '9 D 1
OL Q]bd U
ug
} r O. ic2
- JJ
~
Amendment No.
32 3-86
9?
e TABIJ. 3 15-1 FIRE D1"ECTICH INS *TJ:CITS Total Nu=ber Instru=ent Iccation of Detectors Mini =us Instru=ents Operable Heat S=cke Heat S=cke 1.
Centrcl Building nev. 355' Centrol Recs 0
h NA 2
Cc=puter Rocs 0
h NA 2
2.
Centrol Suilding Eev. 338' 1D h160 7 SWCR 0
1 NA 1
13 h160 V SWGR 0
1 NA 1
ESAS Cabinets 0
1 NA 1
Cable Spreading h
1 2
1 3
Centrol Su11di=g nev. 322' 1P h80 7 S*aT,R 0
1 NA 1
1S h80 V SWGR 0
1 NA 1
Battery Recm A 0
1 NA 1
r.
Batter / Recs 3 0
1 NA,
,1 Inverter Recs A 0
1 NA 1
Inverter Recs 3 0
1 nA 1
Re=cte Shutdevn Panel 0
1 NA 1
h.
Diesel Generators Diesel A 1
0 1
NA Diesel 3 1
0 1
NA NA 5
Screen Ecuse 2
0 1
6.
Aux. and Fuel W"d'*ng 1
1 1
1 Building
~~
O
~O I 7 3-87
)byJ lD)
Amendment No.
32
3.18.2 FIRE SUPPRESSION WATER SYSTIM Aeoliestility: All operating conditicas Objective: To insure adequate fire suppression capability Steeifiestien:
3 18.2.1 The Fire Suppression 'later Systes shall be operable with:
Two (2) high pressure pu=ps of the fellovi=g fcur (h), sN' be a.
operable with their discharge aligned to the fire suppressics headei and autc=atic initiation icgic cperable.
A=y two of the pu=ps provide ecsbined capacity greater than 3575 gal /=in:
1.
Circulating Water Flu =e Diesel Tire Pu=p 2.
River Water Diesel Fire Pu=p, Unit 1 3.
River Water Diesel Fire Pu=p, Unit 2 h.
River Water Meter Fire Pu=p, Unit 1 b.
Q (2) separate vater supplies of the fc11cwing fcur (k) ec.ch containing a =ini=us of 90,0C0 galices:
1.
Altitude Tank 2.
Circulating 'Jater Flu =e 3.
Unit I River 'Jater Istake k.
Unit II River Water Intake c.
An operable flow path capable of taking suction from two of the operable sources listed in b, above, and transferring the water through distribution piping with operable sectionalizing control or isolation valves to the yard hydrant curb valves and the front valve ahead of the water flow alarm device on each sprinkler, hose standpipe or spray system riser.
3.18.2.2 a.
With less than the above required equipment OPERA 3LE restore the inoperable equipment to OPERA 3LE status within 7 days or. prepare and submit a Special Report to the Commission within the next 30 days outlining the plans and procedures to be used to provide for the loss of redundancy in this system.
b.
With the FIRE SUPPRESSION WATER SYSTEM INOPERABLE:
1.
Establish a backup FIRE SUPPRESSION WATER SYSTEM within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, and provide Prompt Notification with Written Follow-up pursuant to Specification 6.9.2.A outlining the actions taken, the cause of the inoperability, and the plans and schedule for restoring the system to OPERABLE status, or 2.
Be in hot shutdown within 1 hour-and cold shutdown within the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
1ro7 1r/
1JuJ lJO 3-88 Amendment No.
32
3.18.3 DE1UGI/SFR!.r23 SYS~'D'S Ateliesbility: At all times when equip =ent in the area is required to be operable.
Objective:
To assure adequate fire suppressien capability.
Steeifiestien:
3.18.3.1.The Deluge and/cr Sprh kler Syste=s located in the following areas shall be operable.
- Diesel Get. crater and Radiator Rec =s a.
b.
Diesel Generater Cc=bustien Air Intakes c.
Diesel Generater Cccling Air Intake d..
Centrol Building Filter (AE-73A, AH-733) Rec =s
- ~
e.
Air Intake ?c.=nel (3 :ones) f.
Charecal Filter (AE-Flo, AE-711) g.
Intake Screen P..p Ecuse h.
Diesel-driven fire pump areas 1.
Control Building at elevation 306'.
3.18.3.2 With any of the above deluge and/or sprinkler systems in any room or zone inoperable:
Establish a continuous fire watch with backup fire suppression a.
equipment for the unprotected area (s), within ene hcur except that no fire vatch is required in the e.ir intake tunnel.
b.
Restore the system to OPEF.t31E status within ik days er pr.epare and sub=it a Special Repert to the Cc _ issics within the rext 30 days outlining the action taken, the cause of inoperability and the plans and schedule for restoring the system to OPERABLE status.
II O
iFI l JuJ l - 3 Amendment No.
32 3-89
3.18.k CO2 ST3IIM Arp11eabilit-rt At all tir.es when the eq tip=ent in the area is required to be operabic.
Objective: To insure adequate fire suppression capability.
Steeification:
3 18.h.1 The CO2 systes for the Cable Spreading Rees shall be operable with a level correspending to 8500 it= and a -* pressure of mi n4 m 300 psig in the associated storage tank (s'.
3.18.h.2 With the CO2 systes for the Cable Spreading Rees ineperable:
a.
Establish a continuous fire watch with backup fire suppression equipment for the unprotected area within one hour.
b.
Restore the system to OPERABLE status within 14 days or prepare and submit a Special Report to the Coc=tission within the next 30 days outlining the action taken, the cause of inoperability and the plans and schedule for restoring the system to CPERABLE status.
.)
I s u u)
]a"0 i-3 Anendnent No. 32 3-90
3.18.5 EALCN SYS E!
Arelicability: At all times except when the Centrol 3 gild
- g ventilatica is en recirculation.
Objective:
To' assure adequate fire suppression for the Air Intake tunnel.
Sodeifiestion:
3.18.5.1 The Halon Systems for the air intake tunnel shall be operable except for testing or maintenance not to exceed 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> that requires the air tunnel to be occupied. The Halon storage tanks shall have at least 90% of full charge pressure and 95% full charge weight.
3.18.5.2 If the Halon system in any zone is inoperable:
The Air Intake Tunnel Deluge system shall be in service unless a.
the tunnel is occupied.
b.
Restore the system to OPERABLE status within 14 days or prepare and' submit a Special Report to the Commission within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to operable status.
e 1 r o 1"7 lsyJ ls/
Amendment No.
32
_g e
e e
I 3.18.6 FIRE ECSE STATICUS Anulicabilit r: At all ti=es when the equip =ent in the area is required to be operable.
Ob.i eetive r To insure adequate fire suppressica capability.
Seceificatien:
3.18.6.1 The fire hose statices listed in Table 318-2 shall te operable er an additional hose nust be routed to the unprotected area fres an operable hese statics vithin one (1) hour.
_ Bases:._,
The OPERABILITY of the fire suppression systems ensures that adecuate fire suppressicn cacability is available to confine and extinctish fires occurring in any portica of the facility where safety related ecui: ment is located. The fire suporession system consists of the water system, The collec-spray and/or serinklers, CO,, Halen and fire hose stations.
e tive capability of the fire'superession systems is adequate to minimize potential damage to safety related equipment and is a major element in the facility fire protection program.
In the event that portiens of the fire suppression systems are inopersble, alternate backup fire fignting equipment is required to be made available in the affected areas until the inoperable equipment is restored to. serv 1ce.
In the event the fire suppression water system becomes incperable, immediate corrective measures must be taken since this system rovides the major fire suppression capability of the plant.
The requirement for a twenty-four hcur report to the Ccamission provides for prem:t evalua-tion of the acceptability of the corrective measures to provide adequate fire suppression capability for the contfnued operation of the nuclear-plant.
1r'o 1-IsUJ sJ Amendment No. 32 3-92
n Table 3.13-2 HOSE STATIONS Intermediate Building 1.
Fire hose near northeast piping chamber staireay at elev. 309'. (2 stations)
Auxiliarf 3uiliin-1.
Fire hose near stairvay at northeast end of buildi=g sear valve rces at elev. 285'.
2.
Fire hose near vaste evaperater ec=densate tank and auxiliar/ steam condensate return unit elev. 285'.
3.
Fire hose near stairvay at certheast end of auxiliar/ building and engineered safeguards centrol center, elev. 309'.
k.
Fire hose near radicactive vaste centrol center, elev. 309'.
Turbine Building 1.
Fire hose along vest side of huildi=g near 12th stage extractica feed-vater heaters, elev. 226'.
I 2.
Fire hose along vest side of building near loth stase extractica feed-vater heaters, elev. 359'.
D IsvU IJ/
Amendment No. 32 3-13
h.17 FIRE FRCSC*!C:7 SYS*D'S k.17 1 FIRE FRCTIO*!O:t !!!S;?.CCI"'S Aerliesbilit/:
Instr =ents listed in Table 3 18-1 Cbjective: To insure operability of fire d.etectics instr =ents.
Srecification:
h.17 1.1 Each of the fire detection instr =ents listed in Table 3.18-1 shall be de=enstrated operable:
a.,, Cece each 6 =enths t/ a Channel Functional Test.
4.17.1.2 The non-supervised circuits between the local panels for the instruments in Table 3.18-1 and the control room shall be demonstrated OPEFJLBLE at least once per month.
Amendment No.
32 4-72
)
h V
.e
~
h.17.2 72.2 SU?FF.I.SSICN WATS SYSTE4 Atelicabilitf: Fire Suppressica Water Syste's as defined in Specificaticn 1.3.
Objectiret To inscre systen operability.
Steeificatien:
h.17 2.1 Thy system shall be de=enstrated operable:
Once per 7 days by veri.*/ ng 90,0C0 galices of vater in the i
a.
altitude tank, equivalent level in the circulating vater f1=e, and/or equivalent level in the river.
b.
Once per scnth on a staggered test basis by starting each A and operatics it for 15 minutes en recirculatica flev.
f* - O 4
gsVd IUI
~
Acendnent No.
32 4-73
c.
At least once per 31 days by verifying that each valve (manual, pcwer operated or autcmatic) in the ficw catn is in its enrrect position.
d.
At least once per : a.nnths by performance of a system flush.
e.
At least cnce per 12 months by cycling each testable valve in the fl.cw path through at least one cceplete cycle of full trevel.
f..
At least once per 18 months by performing a systa-functienal
. test which includes simulated autcmatic actuatic.. of the system throughout its cperating sequence, and:
1.
Verifying that each autcmatic valve in the flew cath actuates to its correct positien en a test signal,
_))
2.
Verifying that each pump develops at least 2500 gpm at a system head of 250 feet for FS-P-1 and 294 feet for FS-P-2 and FS-P-3, 3.
Cycling eech valve in the flow path that is not testable during plant operatien through a-least ene cceplete cycle of full travel, and
~ ~~ -'-~~~
~
4.
Verifying that each high pressure pumo starts to maintain t$e fire suppression water system prerfure.
1125. psi g.
g.
At least once per 3 years by ;erforming a flow test of the systam in accordance with Chac:cr 5, Section 11 of the Fire Protection Handbcok,14th Editicn, published by the !!ational Fire Protection Association.
1533 i<2 Amendment No. 32 4-73a
4.17.2.2 The fire pump diesel engines shall be demonstrated OPERABLE:
a.
At least once per 31 days by verifying; 1.
The fuel storage tanks contain at least 250 gallons of fuel, and 2.
The diesels start from ambient conditions and operate for at least 20 minutes.
b.
At least once per 92 days by verifying that a sample of diesel fuel from each fuel storage tank, obtained in accordance with ASTM-0270-65, is within the acceptable limits specified in Table 1 of ASTM-0975-74 with respect to viscosity, water content and sediment for the type of fuel specified for the diesels, c.
At least once per 18 months, during shutdown, by:
1.
Subjecting each diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for the class of service, and 2.
Verifying each diesel starts from ambient conditions on the auto-start signal and operates for 2,20 minutes while loaded with the fire pump.
4.17.2.3 Each fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:
a.
At least once per 7 days by verifying that:
1.
The electrolyte level of each battery is above the plates, and 2.
The overall battery voltage is 3,24 volts.
r'O I
JVV "J
Amendment No.'32 4-73b
b.
At least once per 92 days by verifying that the soecific gravity is appropriate for continued service of the battery, c.
At least once per 18 months by verifying that:
1.
The batteries, cell plates and battery racks show no visual indication of physical damage or abnormal deteriora-tion >and 2.
.The battery-to-battery and terminal cc.nnections are clean, tight, free of corrosion and coated with anti-corrosion r.4 erial.
1I^9 1
3 isva i
s.
r Amendment No.
32 4-73c
k.17.3 DEIUOE/S7?.
E SYSTEG Aeoliesbility:
Deluge and Sprinkler Systens.
Obieetive:
To insure system c;erability.
Steeifiestien:
h.17 3.1 The deluge and/cr sprinkler syste=s listed in Specification 318.3.1 shall be de=cestrated to be operable:
Once per =cuth by a flush through the dre.in/ test valves at the a.
inlet to each deluge valve.
b.
Once per =cnth by fleving water thrcush the inspectors test connecticn on each vet sprinkler header to verify absence of header bicekage.
At least once per 12 :onths by cycling each testable valve in c.
the flow path through at least one co=plete cycle of full travel.
d.
Once per 18 months by performing a system functional test which includes tripping detectors and:
(a) verifying actuation of trip devices on associated deluge valves, and (b) cycling each valve in the flow path that is not testable during plant operacion through at least one complete cycle of full travel. This functional test will not normally involve flowing water thrcugh the sprinkler / deluge header. Deluge sprinkler valves will be inspected internally to verify operability in all instances where header flooding during the test is undesirable.
Once per 16 =cnths by visual inspection of deluge headera to e.
verify their integrity.
f.
Once per 18 :onths by visual inspection (from ficer level) of each not:1e to verify absence of spray pattern bicekage.
Once per 3 years by a gas or vater flev test of any c;en type g.
deluge head to verify absence of bicekage.
k.17.h CO2 SYSTE4 Accliesbility:_
CO Systes for the Cable Spreading Rocs.
2 Objective:
To insure systes c;erability.
Seceifiestion:
k.17.k.1 The CO systen shall be de=enstrated operable:
2 At least once per week by verifying the CO2 storage tank a.
level and pressure.
b.
At least once per 18 months by verifying the system valves and associated ventilation dampers actuate manually and automatically in response to a simulated actuation signal. A brief flow test shall be made to verify flow from each nozzle.
("Fuff Test")
g
),
r Amendment No.
32 4-74 lavU i'3
k.17 5 Ealen Syste=s Acelicabilitv: Ealen Syste=s described in Specificatica 3 13.5 Objective: To insure system operability.
Steeificatien:
h.17.5 1 The Halen System shall te verified cperable:
At least once per 6 months by verifying each Halod storage' ~ ' ~[
a.
tank weight and pressure.
b.
At least once per 18 months by:
1.
Verifying that the system, including associated ventilatien da=pers, actuates autc=atically to a si= lated test signal.
2.
Functienal test of the ultraviolet detectors test of the pressure valve detecters, a:d replare ent of,the explosive actuators.
~
e
.a 1:33 166 Amendment No.
32 k-75
?
n h.17.6 ECSE STATIC *;S Arelienbility:
Ecse stations listed in Table 313-2.
Obieetiv el, To insure system operability.
Steeifiestien:
k.17.6.1 Each fire hose station shall be verified operable:
~
~
a! At least once pe'r month by visual inspection of the station to assure all equipment is at the station.
b.
At least once per 18 months by removing the hose for inspection and re-racking, and replacing all gaskets in the couplings that are degraded.
At least once per 3 years, partially open hose station valves c.
to verify valve operability and no blockage, d.
At least once per 3 years by conducting a hose hydrostatic test at a pressute at least 50 psi greater than the maximum pressure availabic at that hose station.
f:
1sVU 1
7 I O iU/
Amendment No.
32 h-76
b.
Proposed tests and experi=ents,
'.,.e) and to make an initial determinatien tha: "a" and "b" above do not constitute an unreviewed safety question.
NOTh The Unit Superintendent shall report direc:1y to the "anager-Genera:ica Operations-Nuclear and is respcnsible to his for the ad=inistration, operation and =aintainance of Ihree Mile Island Nuclear Station Uni: 1.
6.2 ORGANIZATION O'FFSITE 6.2.1 The organization of the Met-Ed Corporate Technical Support staff for Station manage:ent and technical support shall be functionally as shewn in Figure 6-1.
FACILITY STAFF
.6.2.2 The organi=ation wi:hin the sta:1on for operations, :echnical support, and maintenance shall be fune:1cna117 as shown in Figure 12-1 of the Final Safety Analysis P.eport.
Each on-duty shif t s$ tall,as a sini=um,be comp'osed of the following a.
shift crew:
Shif t Supervisor or Shif t Foreman (See Notes 1 & 3) 1 Control Room Operator (See Notes 2 & 3) 2 Auxiliary Operator (See Note 3) 2 Q
Additional Station Personnel Available to Serve on the Fire Brigade (See Note 4) 5 Men / Shift 10 b.
At least two licensed Reactor Operators shall be at the station, one of whos shall be in the Centrol Room at all ti=es when there is fuel in the reac:or vessel. One of these operators shall held a Senior Reactor Operator's License.
c.
At least two licensed ' Reactor Operators shall be present in the Control Roos during reactor start-up, scheduled reactor shutdot.n and during recovery from reac:or trips.
d.
At least one =ccher of each opera:ing shif: shall be qualified to implement necessary radiation protec:1on procedures.
A licensed Senior Rea':or Operator wi:h no other concurrent opera:1cnal c
e.
duties shall direc:1y supervise:
(a) irradiated fuel handling and transfer ac:ivities onsite, and (b) all unirradiated fuel f
handling and transfer ac:Lvities to and frem the. Reactor Vessel.
NOTES:
1.
The Shif t Supervisor, or the Shif t Foreman if a Shift Supervisor is not assigned, shall have an NRC Senior Reac:or Operator's License.
Amendment No.
32 6-2
,e,
- j. 8
,~
~
[I' 2.
Only one. _nsed Control Room Operacer sha.
.ae required per shif:
during cold shutdown or refueling operacions.
3.
Shift Supe: visor, Control Room Operator and Auxiliary Opera:or refer to functions that are to be perfo=ed and de not refer to the ti:le of the individual. These functions =ay be perfo=ed by any individual pcssessing :he necessary licenses and qualifications.
4.
The same 5 personnel on the fire brigade can satisfy the require-ments on Units 1 and 2.
l 6.3 STATION STAFF OUALIFICATIO:IS 6.3'.1 Co=prising the s:atien scaff shall be supervisory and professional personnel enec= passing the qualifications described in See: ion 4 of
, ANSI N18.1-1971, " Selection and Training of Nuclear Power Planc Personnel."
6.4 TRAINING 6.4.1 A retraining and replace =en: training progra:2 for the. facili:7 staff shall be naintained under :he direction of the Supervisor of
. Training and.shall zeet or ex,ceed the require =ents and reco==endations of Section 5.5 of ANSI N18.1-1971 and Appendix "A" of 10 CTR Part 55.
6.5 REVIEW kid AUDIT 6.5.1 PLANT OPERATIONS RE' LIEU CO:0!ITTEE (PORC)
FUNCTION 6.5.1.1 The Plant Operations Review Co==ittee shall function to advise the Unit Superintendent on all =a::ers rela:ed to nuclear safety.
COMPOSITION 6.5.1. 2 The Plant Operations Review Ccesittee shall be cocposed of:
a) - Unit Superintendent
~~
b)
Supervisor of Operations c)
Supervisor of Maintenance d)
Unic Elec:rical Engineer e)
Unit Mechanical Engineer
()
Unit-Nuclear Engineer g)
Unit las:ru=ent and Control Engineer h)
. Supervisor of Radiation Pro:ection and Chemistry
, 1);
PORC Chair =an
.g j)
Other planc engineers assigned by the Unit St.;,erintendent The Unit Superintendent shall designate the nest.crs, the Chairman, and the Vice Chair =an of the Plant Operations Review Cocmit tee.
ALTERNATES 6.5.1.3 Alternace sembers shall be appo' %d in wri:ing by :he Unit Superintendent to serve on a "rc; 'rarn basis. For purposes of this specifica:1on, a designace' g e.r*. ate shall be considered to have the Anendment No.
32 63
}u i r 9 suo
k.
Periodically audit the areas listed bel.ov to verify co=pliance with the Three Mile Island Operating Quality Assurance Plan,
/
internal rules and procedures, federal regulations, and operating license provisions:
1)
The 13 Critiera of 10CFPJ0, Appendix 3 2)
Nor=al S tation Operation 3)
Inservice Inspection 4)
Refdeling 5)
Radiological Controls 6)
Station Maintenance 7)
Technical Specifications 8)
Training and Qualifications of Station Staff 9)
E=ergency Plan 10)
Industrial Security Progras 11)
Fire Protection Progra= and Inple=enting Procedures l
In perfor=ing these audies, written procedures and/or checklists shall be used. As a nini um, each area shall be audiced at least once every two years.
e
~
/
3 p n 3>
l<q 4 --
U las Anendnent No. 11 6-6a
6.8 FRCCEUEES 6.8.1
'4ritten procedures and =A-'nistrative policies shall be established, i=plemented and =aintained that =eet er exceed the require =ents and reccc:=endaticus of Sections 31 and 5 3 of A::S! :ll3.7-1972 and Appendix "A" of US:iRC Regulatory Guide 1.33 :Tove=ter 1972 except as Provided in 6.8.2 and 6.8.3 telev.
I=plementation of the Fire Prctectica Progrs= shall be by =eans of vritten precedures.
6.8.2 7.ach nuclear safety related precedure a=d ad=inistrative policy of 6.8.1 above, and changes thereto, shall be reviewed by the Plant Operatiens Review Cc==ittee and apprcved bf the Unit Superintendent prior to i=ple=entation and periodiry as =sy be set ferth in each docu=ent.
6.8 3 Te=perary changes to procedures of 6.8.1 above =ay te =ade provided:
a.
The intent of the original precedure is not altered.
b.
The change is approved by two =e=bers of the plant =anage=ent staff, at least ene of -tc= holds a Se=icr Reacter Operator's License en the unit affected.
The change is docu=ented, reviewed by the ?lant Operatic:s c.
Review C-4ttee and approved by the Unit Superintendent " thin 7 days of i=plementatien.
I' 9 1~!}
avJ l
Amendment No.
32 6-11
n 6.14 FIRE F*C"'EC"'!C'i I?! SPEC" ION 1.
An independent fire protecticn and less preventien, inspection and 3
audit shall be perfor=ed annually utilizing either qualified off-site licensee persennel er an cutside fire protection firm.
2.
An inspection and audit by an cutside qualified fire censultant
'shall te' performed'at inte.-tals no greater than three years.
n I
2
.) O O Amendment No.
32 6 26