OPERATING DATA REPORT DOCKET NO.

50-333 DATE Oct.1979 COMPLETED BY li. Zu felt TELEPIIONE (31aj a42-3840 OPERATING STATUS

1. Unit Name:

Fit: Patrick Notes

2. Reporting Period:

790901 - 790930

3. Licensed Thermal Power (SIWt):

2436

4. Nameplate Rating (Gross MWe):

883 821

5. Design Electrical Rating (Net MWe):

830

6. Maximum Dependable Capacity (Gross MWe):

800

7. Maximum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, Gise Reasons:

None Nonc

9. Power Lesel To Which Restricted,If Any (Net MWe):
10. Reasons For Restrictions,If Any:

This Month Yr..to.Date Cumulatise 720 6551 36624

11. Ilours in Reporting Period
12. Number Of flours Reactor Was Critical 655.1 2422.4

_ 24484.6

13. Reactor Reserve Shutdown flours 0

0 0

14. Ilours Generator On-Line 555.6 2322.9 23610
15. Unit Resene Shutdown llours 0

0 0

16. Gross Thermal Energy Generated (MWil) 792072 4418232 46652380
17. Gross Electrical Energy Generated (MWil) 256390 1492110 15786980 IS. Net Electrical Energy Generated (MWil) 24753C 1445965 15271950
19. Unit Senice Factor 77.2%

35.5%

64.5%

77.2a 35.5%

64.5%

20. Unit Asailability Factor
21. Unit Capacity Factor (Using MDC Net) 43.0*6 27.6%

58.0*6

22. Unit Capacity Factor (Using DER Net) 41.9o 26.9"a 50.8%
23. Unit Forced Outage Rate 22.8*4 64.5%

22.3%

24. Shutdowns Scheduled Oser Nest 6 Months (Type. Date.and Duration of Each t:

Snubber inspection and refueling outage scheduled for March, 1980.

25. If Shut Down At End Of Report Period. Estimated Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forecast Achieved INITIA L CRITICA LITY INITIA L ELECTRICITY COMMERCIA L OPER ATION 7910100 c) b ll26 l52 R

AVER AGE DAILY UNIT POWER LEVEL DOCKET NO. 50-333 UNIT JAFNPP DATE Oct. 1979 CO\\1PLETED BY E. Zufelt TELEPilONE (315)342-3840 MONT11 September, 1979 DAY AVERAGE DAILY POWER LEVEL DAY AVER AGE DAILY POW?iR LEVEL (51We-Net)

(5twe. Net )

1 0

37 470 2

0 gg 461 3

0 19 551 4

0 622 20 5

0 630 21 6

0 632 22 7

11 680 23 8

113 785 24 9

215 570 25 10 284 26 385 11 325 418 2,

356 12 28 413 13 396 414 29 14 393 30 563 15 249 33 16 378 Summary: Unit was returned to service on September 7, 1979 after a shutdown of 4228.1 hours1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> for Pipe Stress Re-Analysis.

Il-26 153

50-333 UNIT SilUTDOWNS AND POWER REDUCTIONS DOCKET NO.

UNIT N AME JAFhPP DATE Oct. 1979 REPORT MONTil Sept. 1979 COMPLETED BY E. Zufelt TELEPIIONE (315)342-3840 "i

L

!?

3

. Yi Licensee

,E r, b".

Cause & Correcti..

No.

Date i

5?

.s ~ 5 Event

y 8-3 Action to

$E j di g Report n (E C Prevent Recurrence 6

5 79 315 F

164.4 D

4 79-014 ZZ ZZZZZZ Re-evaluation of stress calculations and modifications as required.

(Cumulative hours-total 4228.1) 6 790925 S

0 11 4

N/A N/A N/A Reduced power to check for condenser tube leaks.

1 3

4 F: Forced k.ason:

Method:

Exhibit G - Instructions S: Scheduled A. Equipment Failure (Explain) 1-Manual for Preparation of Data B. Maintenance oi Test 2 Manual Scram.

Entry Sheets for Licensee C Refueling 3 Automatic Scram.

Event Report (LER) File (NUREG-N D Regulatory Restriction 4-Other (Explain) 0161)

E-Operator Training & License Examination F Administrative 5

G Operational Error (Explain)

Exhibit I-Same Source ty-Il Other ( Explain) b

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE SEPTEMBER, 1979 The unit was returned to service on September 7, 1979 after 4228 hours0.0489 days <br />1.174 hours <br />0.00699 weeks <br />0.00161 months <br /> of cold condition for re-evaluation of pipe stress.

On September 25, power was reduced to approximately 400 MWe to check for condenser tube leaks.

On September 30, the condenser tubes were plugged and the power was increased to the pre-conditioning threshold and continued at the pre-conditioning rate.

1126 155

JAFES A. FITZPATRICK NUCLEAR POWER PLANT Maintenance Summary I 6 C - Sept. 1979 W rk Request #

Cause of Results of Action taken to Repair Date System llow Detected Component #

Malfunction Malfunction Preclude Time Recurrence (llours) 3057 Water leak on Replaced unit 9-10-79 02 02-3-LIS-72A OPS Age /Use span / Adjustment Recalibrated 40.0 3056 Incorrect switch / Corrected wiring 9-10-79 02 02-3-LIS-72D OPS Incorrect wiring Relay position error /OR #79-129 7.0 3156 Calibrated DPI/DPT 4.0 9-19-79 02 02-3-DPI-93 OPS Drift Incorrect reading ;

12477 Incorrect 9-3-79 03 RIO1 OPS indicating bulbs No lights Replaced bulbs 2.0 Failed IC chip on 3018 sequence logic 9-3-79 03 RSCS OPS card Malfunction alarm Replaced DJ 4.0 3095 Failed to funct-9-10-79 03 RSCS OPS Relay K61 fTiled ion in Group III Replaced K61 6.0 2715 8-28-79 05 RPS-MG-1A/1B ISC N/A N/A IMP-5.2 10.0 2691 Bad pre-amp Indicator Resoldered 9-2-79 07 SRM "D" OPS connection downscale connector 6.0 3112 Replaced 4D-12-13 N

9-11-79 07 RBM "B" OPS Bad LPRM card Inop in APRM "A" 8.0 CN 3134 Loose switch Tightened 9-10-79 07 RBM "B" OPS connector Rod block connector 6.0 g

S 2718 Functional test 9-5-79 07 TIP Sys.

I6C N/A N/A after S/D 28.0 3115 Faulty multiplex Replaced card 9-14-79 07 RBM "A" OPS card Rod hinck T9P 74 19; O

JAMES A. FITZPATRICK NUCLEAR PONER PLANT Maintenance Summary I S C - Sept. 1979 r

p st #

Cause of Results of Action taken to Re) air Date System llow Detected Component #

Malfunction Malfunction Preclude Tu'e Recurrence (liot 's) 3169 Stuck contacts 9-14-79 07 RBM "B" OPS on relay Rod block Exercised relay 18.0 3103 9-14-79 07 APRM A-D-F OPS N/A Check trips Found ok 2.0 3184 Malfunctioning 9-17-79 07 RBM "B" OPS Relay cards Downscale Replaced card 1.0 2764 Alarm but no 9-25-79 07 APRM "F" OPS Unknown half scram See WR-3235 7.0 3235 Alarm but no 9-25-79 07 APRM "F" OPS Unknown half scram IMP 7.6 20.0 3014 Fastened 9-4-79 10 10-LS-103 OPS Loose detector Continuous alarm connector 4.0 2650 Tightened 9-10,-79 10 10-A0V-71B OPS Loose connections Air leaks fittings 4.0 3217 Replaced ca.J 6 9-21-79 10 LS-100 OPS Bad P.C. card Constant alarm repaired plug 20.0 2694 9-4-79 11 PI-53 OPS Unknown Found ok 2.0 EM 2613 Verified 9-21-79 11 LI-66 OPS tank levels 35.0 U'.

y 3092 Repaired connecti.in 9-24-79 14 LS-20B OPS Broken connection Alarm IMP G-30 10.0 2615 Dirty detector Difference in Cleaned chamber 8-30-79 17 RTS-431 OP9 ch,=bar

^ /p va~88---

'ca '"

  • ^ ^

JAMES A. FITZPATRICK NUCLEAR POWER PLANT Maintenance Summary I 5 C - Sept. 1979 Date System W rk Request #

Cause of Results of Action taken to Repair How Detected Component #

Malfunction Malfunction Preclude Time Recurrence (Hours) 2680 8-30-79 17 RR-152 OPS Drift Failed ST-11 Calibrated recorde 3.0 3008 Calibrated 9-3-79 17 RIS-452B OPS Drift Failed ST-12B recorder 4.0 3010 Repair / calibrate 9-3-79 17 RIS-458A OPS Failed transistor Failed ST-12D recorder 7.0 3004 Erroneous 9-4-79 20 FQ-527 OPS Drift flow indication Calibrated SQX 4.0 3113 Erroneous 9-11-79 20 FQ-530 OPS Drift flow indication Calibrated FT.

6.0 2711 Replaced ind.

8-26-79 27 PI-102B ISC OR-79-083 N/A 6 calibrated 6.0 2544 Out of tolerance 8-27-79 27 Various ISC test equipment N/A Recalibrated 16.0 2584 8-25-79 72 DPS-104B OPS Drift Rccalibrated 2.0 1060 Replaced /

_8-27-79

'93 93-Meters ISC Broken No indication Calibrated 40.0 ps) 1957 Replaced CJs8-30-79 99

  1. 3 Camera Sec.

Bad Vidicon tube Poor picture Vidicon tube 8.0 1962 (29-12-79 99 IAL #115 Sec.

Loose wire Constant alarm Tightened wire 5.0 291 Replaced 9-20-79 99 Spare Monitor Sec.

Bad transistors No picture Transistors 10.0

It j:

JAMES A.

FITZPATRICK NUCLEAR PONER PLANT

(

Maintenance Summary I 6 C - Sept. 1979 i

l W rk Reauest #

Cause of Results of Action taken to Repair i

Date System

!!ow Detected j

Component #

Malfunction Malfunction Preclude Time Recurrence

(!!ours) 1097 E

9-20-79 99

  1. 1/#2 Camera Sec Bad Vidicon No/ Poor Picture Re-aligned camera 10.0 1952 IIalf of picture Aligned auto-gain 9-20-79 99
  1. 2 Camera Sec.

Ckt. Drift blacks out ekt.

10.0 1991 Bad electronic Will not 9-20-79 99

  1. 4 Camera Sec.

drive pan or tilt Repaired ekt.

4.0 2727 Alarms in 9-20-79 99 IAL 115/118 Sec.

Unknown continuous Found ok 4.0 2741 9-24-79 99

  1. 4 Camera Sec.

Drift Fuzzy picture Adjusted 4.0 1

I

~

U-

H POWER AUT110RITY OF TifE STATE OF NEW YORK JAh!ES A. FITZPATRICK NUCLEAR POWER PLANT Safety Related Electrical 6 Mechanical Maintenance Summary WORK REQUEST f, REPAIR DATE.

SYSTEM COMPONENT #

!!ON DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURIENCE TIME Il0URS 30 Aug 10 1183 Visual NRC Bulletin 79-02 Repaired 1110-503 526b 1110-503 Inspection 30 Aug 14 1379 Visual NRC Bulletin 79-02 Repaired 1114-18 814 3/4 1114-18 Inspection 30 Aug 29 2720 Visual NRC Bulletin 79-02 Modified 1129-150 65

!!29-150 Inspection i

30 Aug 29 2722 Visual NRC Bulletin 79-02 bbdified 1129-149 64 1129-149 Inspection 31 Aug 10 2681 Visual Drain line weld cracked Rewelded drain line 10 RilR Drain Line 31 Aug 03 2598 OPS CRD had " uncoupled" Replaced CRD 22-07 245 CRD 22-07 indication periodically SO Aug 27 2699 Visual Flange gasket Icak Replaced gasket 3

F-6B 1 Sept 71b 2705 OPS Loss of nitrogen pressure Meggered component's cables passing 4

m Drywell Elect.

at drywell penetration through penetration Penetration

~

104D C

e

POWER AUT110RITY OF TIIE STATE OF NEW YORK JA5fES A. FITZPATRICK NUCLEAR POWER PLANT Safety Related Electrical 6 Mechanical Maintenance Summary WORK REQUEST #

REP /IR DA.iE SYSTEM Il0W DETECTED CAUSE OF MALFUNCTION ACTION 'lAKEN TO f7ECLUDE RECURRENCE TIME COMPONENT,

Il0URS 1 Sep 23 2072 Visual NRC Bulletin 79-02 Modified 1123-28 635 1/4 1123-28 Inspection 2 Sep 15 2751 Visual NRC Bulletin 79-02 Repaired il15-New 70 II15-New Inspection 2 Sep 10 2377 Visual Flange gasket leak Tighten flange 19 P-3D Suction flange 27 Aug 10 2367 OPS Valve internals separated Repaired 6 reassembled valve 565%

RilR-42B during valve operation internals 2 Sep 46 1663 Visual NRC Bulletin 79-02 Repaired PFSK-1350 45 rFSK-1350 Inspection 3 Sep 10 2210 Visual NRC Bulletin 79-02 Modified !!10-203 332 1110-203 Inspection 3 Sep 15 2752 Visual NRC Bulletin 79-02 Repaired !!15-New 181 Ill5-New _

Inspection 29 Aug 00 2357 N/A None Performed visual snubber inspection 300 Ilydraulic Snubber Inspection

POWER Alfi'110RITY OF TIIE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT Safety Related Electrical 4 Mechanical Maintenance Summary WORK REQUEST 4 REPA'IR DATE SYSTEM IIOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONENT #

Il0VRS 30 Aug 03 2548 Audible Magnetic flux leakage Replaced pilot assembly 1

CRD 10-27 from scram pilot valve solenoid assembly 5 Sep 13 3035 OPS Improper maintenance Inspected operator and replaced motor 24 MOV-41 caused motor to burn 3 Sep 27 3011 OPS Burned solenoid coil Installed flux plate and replaced 6

SOV-123B caused by missing lower solenoid coil flux plate.

Without flux plate coil drew excessive current.

1 Sep 13 2687 OPS None Inspected motors for possible water 20 Various motcrs scepage after sump pump failed 29 Aug 29 2609 OPS Excessive force on Modified method of switch actuation 40 A0V-80C position switch arm was to reduce force on arm causing it to break 7 Sep 23 3037 OPS Motor burned due to Replaced motor and torque switch 20 MOV-17 defective torque switch and tested. Obtained motor from in valve operator.

23-MOV-57.

5 Sep 66 b 2754 Visual NRC Bulletin 79-02 Modified 1166-39 36 1166-39 Inspection N

U POWER AUTIIORITY OF TIIE STATE OF NEW YORK JAh1ES A. FITZPATRICK NUCLEAR POWER PLANT Safety Related Electrical 6 h!cchanical hfaintenance Summary i

WORK REQUEST #

REPAIR DATE SYSTEh!

110W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME C05!PONENT #

!!0URS 9 Sep 27 3116 Visual Packing leak Adjusted packing 2

PCV-122A 6 Sep 66 2597 Visual Filters dirty Replaced filters 20 UC-22A-K 11 Sep 23 3061 Maint.

None. Motor switched to Replaced motor.

Reference 20 MOV-57 23-MOV-17 WRED #23/3037 14 Sep 72 3159 Audible Fan noisy - sha ft had Installed shim 6 new bearing 16 AllU-30B rotated inside inner bearing race 14 Sep 93 3177 OPS Overspeed limit switch Readjusted limit switch after 20 EDG-C out of adjustment 6 loose tightening contact contact 14 Sep 10 2755 Visual NRC Bulletin 79-02 Repaired 1110-526 17015 1110-526 Inspection 18 Sep 76 1943 Visual NRC Bulletin 79-02 Repaired BFSK-659-il7 69 BFSK-659-li7 Inspection

{

2064 Visual NRC Bulletin 79-02 Repaired il46-171D 100 17 Sept 46 I!46-171D Inspection g

Va

POWER AUT110RITY OF Tile STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR PONER PLANT Safety Related Electrical 6 Mechanical Maintenance Summary W RK REQUEST #

REPAIR DATE SYSTEM 110N DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONENT #

Il0VRS 18 Sep 10 2067 Visual NRC Bulletin 79-02 Modified 1110-127 2413 1110-127 Inspection 18 Sep 10 2759 Visual NRC Bulletin 79-02 Repaired fl10-32A 40 fl10-32A Inspection 18 Sep 46 2071 Visual NRC Bulletin 79-02 Repaired Il46-177A 82 li46-177A CX 4

.