FirePRACutsetAnalysisExercise#2
TypeofQuantification:FailedEventsareSettoTRUE
FireScenario:3BCP09/08EC81
Cutset#1 CutsetProb.
5.10E01
BEProb BEID
Description 1.00E+00 EINITNCLPSF SONGSINITNCLPLANTSPECIFICFACTOR(PSF) 5.10E01 FUBECCW07_H HV6223SPURIOUSCLOSUREFIRE 1.00E+00 INITFIRE
FIREINITIATINGEVENT 1.00E+00 LOCA
DUMMYFLAGEVENTTOINDICATELOCA(SIAS)CONDITIONS 1.00E+00 NOATWS
DUMMYEVENTFORNONATWSCONDITION 1.00E+00 XHOS3PE453A 1.00E+00 XHOSMSIS
SPURIOUSMSISSIGNALDUETOFIRE 1.00E+00 XHOSRCPFT
RCPFAILSTOTRIPFOLLOWINGLOSSOFCCWFIRE
BasicEventsSettoTRUEor1.0 Event
Probability Description
3BCP09/08EC81
4.08E05 Initiator AMV9325P
1.22E03 MTROPERATEDVLV9325FTOPENONDEMAND
AMV9328P
1.22E03 MTROPERATEDVLV9328FTOPENONDEMAND
DAV9200N
1.00E03 AIROPTDVLV9200FTCLOSEONDEMAND
DAV92001DQ
2.38E06 AIROPERATEDVLV9200FTREMOPEN24H
DMP190S
9.38E04 MTRDRIVENPP190FTSTARTONDEMAND
DMP192S
9.56E04 MTRDRIVENPP192FTSTARTONDEMAND
DMV9201P
1.07E03 MTROPERATEDVLV9201FTOPENONDEMAND
EINITNCLPSF
1.00E+00 SONGSINITNCLPLANTSPECIFICFACTOR(PSF)
FMP053S
1.00E03 MTRDRIVENPP053FTSTARTONDEMAND
FUBE2010110
1.00E12 DIGITALFWPANEL2L049FTREMAINAVAILABLE
FUBEA01MDEN
1.00E12 BUSA01FAILSTODEENERGIZE FUBEAFW05
1.00E12 SG2CHANNELANRINDICATOR2LI11231FAILS
FUBEAFW08
1.00E12 SG2CHANNELDNRIINDICATOR2LI1123A4FAILS
FUBEAFW09
1.00E12 SG1CHANNELANRINDICATOR2LI11131FAILS
FUBEAFW12
1.00E12 SG1CHANNELDNRINDICATOR2LI11134FAILS
FUBECCW07_H
5.10E01 HV6223SPURIOUSCLOSUREFIRE
FUBECCW10
1.00E12 MOTOROPERATEDVALVE6366TRANSFERSCLOSED
FUBECCW12
1.00E12 MOTOROPERATEDVALVE6370TRANSFERSCLOSED
FUBECVCS001
1.00E12 2P191OFF:ONTRNA
FUBECVCS003
1.00E12 2P191OFF:ONTRNB
FUBEELEC99999
1.00E12 BKR(CNTL)4160VA0413FTCLOSEONDEMAND
FUBEELECT02
1.00E12 RESAUXTXFRSNOTENERGIZEDFROMPOS4
FUBEELECT1201
1.00E12 PANEL2L344FAILSDUETOFIRE FUBEELECT50
1.00E12 480VMCC2BDFTOPERATE24H
FUBEELECT6000T
FUBEELECT6002
1.00E12 PANEL2L071A3FAILTOREMAINENERGIZEDDUETOFIRE
FUBEELECT6400
1.00E+00 PANEL2L071X1FAILTOREMAINENERGIZEDDUETOFIRE
FUBEELECT6401
1.00E12 PANEL2L071X2FAILTOREMAINENERGIZEDDUETOFIRE
FUBEELECT6500
1.00E12 PANEL2L0731FAILSTOREMAINENERGIZEDDUETOFIRE
FUBEELECT6501
1.00E12 PANEL2L0732FAILSTOREMAINENERGIZEDDUETOFIRE
FUBEELECT6502
1.00E12 PANEL2L0733FAILSTOREMAINENERGIZEDDUETOFIRE
FUBEELECT6503
1.00E12 PANEL2L0734FAILSTOREMAINENERGIZEDDUETOFIRE
FUBEMSO07
1.00E12 LOOPAHV6293AFRMLETDOWNHXSPURIOUSOPENFIRE
FUBEMSO08
1.00E12 LOOPAHV6293BTOLETDOWNHXSPURIOUSOPENFIRE
FUBEMSO103
1.00E12 CHARGINGPUMPP190FAILSTOSTARTDUEFIRE
FUBEMSO105
1.00E12 CHARGINGPUMPP192FAILSTOSTART FUBEMSO154
PZRHEATERE122FAILSTODEENERGIZEWHILEALIGNTOCHANNELX FUBEMSO155
PZRHEATERE122FAILSTODEENERGIZEWHILEALIGNTOCHANNELY FUBEMSO158
PZRHEATERE123FAILSTODEENERGIZEWHILEALIGNTOCHANNELX
FUBEMSO159
PZRHEATERE123FAILSTODEENERGIZEWHILEALIGNTOCHANNELY FUBEMSO16
1.00E12 VALVE2HV9342OPENSSPURIOUSLYDUETOFIRE
FUBEMSO162
PZRHEATERE124FAILSTODEENERGIZEWHILEALIGNTOCHANNELX FUBEMSO163
PZRHEATERE124FAILSTODEENERGIZEWHILEALIGNTOCHANNELY FUBEMSO166
PZRHEATERE125FAILSTODEENERGIZEWHILEALIGNTOCHANNELX FUBEMSO167
PZRHEATERE125FAILSTODEENERGIZEWHILEALIGNTOCHANNELY FUBEMSO170
PZRHEATERE126FAILSTODEENERGIZEWHILEALIGNTOCHANNELX FUBEMSO171
PZRHEATERE126FAILSTODEENERGIZEWHILEALIGNTOCHANNELY FUBEMSO174
PZRHEATERE127FAILSTODEENERGIZEWHILEALIGNTOCHANNELX FUBEMSO175
PZRHEATERE127FAILSTODEENERGIZEWHILEALIGNTOCHANNELY FUBEMSO178
PZRHEATERE128FAILSTODEENERGIZEWHILEALIGNTOCHANNELX FUBEMSO179
PZRHEATERE128FAILSTODEENERGIZEWHILEALIGNTOCHANNELY FUBEMSO18
1.00E12 VALVE2HV9352OPENSSPURIOUSLYDUETOFIRE
FUBEMSO182
PZRHEATERE129FAILSTODEENERGIZEWHILEALIGNTOCHANNELX FUBEMSO183
PZRHEATERE129FAILSTODEENERGIZEWHILEALIGNTOCHANNELY FUBEMSO19
1.00E12 VALVE2HV9361OPENSSPURIOUSLYDUETOFIRE
FUBEMSO25
1.00E12 AIROPTDVLV9201FTCLOSE
FUBEMSO52
1.00E12 TV0221FAILSOPEN
FUBEMSO53
1.00E12 LIC0110FAILURE
FUBEMSO54T
FUBEMSO55AT
FUBEMSO55BT
FUBEMSO56T
FUBEMSO71
1.00E12 PC0100FAILURE
FUBEMSO72
1.00E12 PT0100XFAILURE
FUBEMSO73
1.00E12 PT0100YFAILURE
FUBEMSO74
1.00E12 LT01101FAILURE
FUBEMSO94
1.00E12 RESAUXTXFRSNOTENERGIZEDFROMPOS17 FUBEMSO96
1.00E12 TV0221TRANSFERSCLOSED
FUBEMSO97
1.00E12 HV9204TRANSFERSCLOSED
FUBEPPS40
1.00E12 LT11131FAILSONDEMANDFIRE
FUBEPPS41
1.00E12 2LT11131SPURIOUSLOWLEVELSIGNALDUETOFIREESFASINPUT
FUBEPPS46
1.00E12 LT11134FAILSONDEMANDFIRE
FUBEPPS47
1.00E12 2LT11134SPURIOUSLOWLEVELSIGNALDUETOFIREESFASINPUT
FUBEPPS48
1.00E12 LT11231FAILSONDEMANDFIRE
FUBEPPS49
1.00E12 2LT11231SPURIOUSLOWLEVELSIGNALDUETOFIREESFASINPUT
FUBEPPS54
1.00E12 2LT11234SPURIOUSLOWLEVELSIGNALDUETOFIREESFASINPUT
FUBEPPS55
1.00E12 LT11234FAILSONDEMANDFIRE
FUBEPPS56
1.00E12 SPURIOUSHIHISUMPLEVELLT93861:FIRE
FUBEPPS58
1.00E12 SPURIOUSLOWPZRPRESS.PT01021FIRE
FUBEPPS59
1.00E12 PRESSURIZERPRESS.TRANSMITTERPT01021FAILS
FUBEPPS64
1.00E12 SPURIOUSLOWPZRPRESS.PT01024FIRE
FUBEPPS65
1.00E12 PRESSURIZERPRESS.TRANSMITTERPT01024FAILS
FUBEPPS66
1.00E12 SPURIOUSHICONT.PRESS.PT03511FIRE
FUBEPPS67
1.00E12 CONTAINMENTPRESS.TRANSMITTERPT03511FAILS
FUBEPPS72
1.00E12 SPURIOUSHICONT.PRESS.PT03514FIRE
FUBEPPS73
1.00E12 CONTAINMENTPRESS.TRANSMITTERPT03514FAILS
FUBEPPS75
1.00E12 CONTAINMENTHIHIPRESS.XMTRPT03521FAILSFIRE FUBEPPS80
1.00E12 CONTAINMENTHIHIPRESS.XMTRPT03524FAILSFIRE FUBEPPS82
1.00E12
FUBEPPS83
1.00E12 SPURIOUSLOWPRESSURESIGNAL2PT10131
FUBEPPS88
1.00E12
FUBEPPS89
1.00E12 SPURIOUSLOWPRESSURESIGNAL2PT10134
FUBEPPS90
1.00E12
FUBEPPS91
1.00E12 SPURIOUSLOWPRESSURESIGNAL2PT10231
FUBEPPS96
1.00E12
FUBEPPS97
1.00E12 SPURIOUSLOWPRESSURESIGNAL2PT10234
FUBERCS10
1.00E12 RCP#1FAILSTOTRIP
FUBERCS101
MANUALRCP#1TRIPFAILED
FUBERCS102
MANUALRCPTRIPFAILED
FUBERCS103
MANUALRCPTRIPFAILED
FUBERCS104
MANUALRCPTRIPFAILED
FUBERCS11
1.00E12 RCP#2FAILSTOTRIP
FUBERCS12
1.00E12 RCP#3FAILSTOTRIP
FUBERCS13
1.00E12 RCP#4FAILSTOTRIP
GAV9205N
1.20E03 AIROPTDVLV9205FTCLOSEONDEMAND
GMV9267N
1.00E03 MTROPERATEDVLV9267FTCLOSEONDEMAND
HLT9386H
9.92E06 LEVELXMTR9386HIGHOUTPUTSIGNALW/I24H
HMV9305P
8.43E04 MTROPERATEDVLV9305FTOPENONDEMAND
HMV9306N
5.73E04 MTROPERATEDVLV9306FTCLOSEONDEMAND
HMV9307N
5.73E04 MTROPERATEDVLV9307FTCLOSEONDEMAND
HMV9324P
6.87E04 MTROPERATEDVLV9324FTOPENONDEMAND
HMV9327P
6.87E04 MTROPERATEDVLV9327FTOPENONDEMAND
HMV9330P
6.87E04 MTROPERATEDVLV9330FTOPENONDEMAND
HMV9333P
6.87E04 MTROPERATEDVLV9333FTOPENONDEMAND
HMV9347N
5.73E04 MTROPERATEDVLV9347FTCLOSEONDEMAND
HMV9348N
5.73E04 MTROPERATEDVLV9348FTCLOSEONDEMAND
HPT1A3MI
1.70E03 PRESSURETRANSMITTERONRCSLOOP1AFAILS HPT1B3MI
1.70E03 PRESSURETRANSMITTERONRCSLOOP1BFAILS INITFIRE
1.00E+00 FIREINITIATINGEVENT INITFIRET
KOOLOV1Z
5.09E03 LOVSTARTSIGNALFORDIESELGENERATOR2G2FAILS
LHCAFWCNTRL
7.29E01 OPFTOVERRIDE&CONTROLAFWVALVES
1.00E+00 DUMMYFLAGEVENTTOINDICATELOCA(SIAS)CONDITIONS
MCHE336S
4.70E03 CHILLERE336FTSTARTONDEMANDLOOPAESFHVAC
MMPP162S
1.25E03 MTRDRIVENPPP162FTSTARTONDEMANDLOOPAESFHVACE33
NFNE399S
6.00E04 FANE399FTSTARTONDEMAND
NFNE3991DR
2.40E04 FANE399FTRUNFOR24H
NFNE401S
6.00E04 FANE401FTSTARTONDEMAND
NFNE4011DR
2.40E04 FANE401FTRUNFOR24H
NMV6367P
6.67E04 MTROPERATEDVLV6367FTOPENONDEMAND
NMV6371P
6.67E04 MTROPERATEDVLV6371FTOPENONDEMAND
NMV9367P
5.15E04 MTROPERATEDVLV9367FTOPENONDEMAND
NOATWS
1.00E+00 DUMMYEVENTFORNONATWSCONDITION
TNV8423N
1.37E03 PNEUMATICVLV8423FTCLOSEONDEMAND
TNV8423P
4.88E04 PNEUMATICVLV8423FTOPENONDEMAND
TNV8424N
1.37E03 PNEUMATICVLV8424FTCLOSEONDEMAND
TNV8424P
4.88E04 PNEUMATICVLV8424FTOPENONDEMAND
TNV8425N
1.37E03 PNEUMATICVLV8425FTCLOSEONDEMAND
TNV8425P
4.88E04 PNEUMATICVLV8425FTOPENONDEMAND
TNV8426N
1.37E03 PNEUMATICVLV8426FTCLOSEONDEMAND
TNV8426P
4.88E04 PNEUMATICVLV8426FTOPENONDEMAND
UB2A031DR
9.60E06 4160VBUSA03FTOPERATE24H
UB2A071DR
2.09E06 4160VBUSA07FTOPERATE24H
UB2A091DR
2.09E06 4160VBUSA09FTOPERATE24H
UB3B161DR
9.60E06 480VBUSB16FTOPERATE24H UB4Q0651DR
9.60E06
<=120VBUSQ065FTOPERATE24H
UC3B10131DO
3.60E06 BKR(CNTL)480VB1013FTREMCLOSED24H
UDG2G2S
2.33E03 DIESELGENERATOR2G2FTSTARTONDEMANDTRAINAESFPOWER
UDG2G21DR
2.39E02 DG2G2FQAILSTORUNFOR24HOURSFOLLOWINGFIRE
UDG2G28HR
7.95E03 DIESELGENERATOR2G2FTRUNTRAINAESFPOWER UDG2G2GROUNDZ
4.72E04 PROBOF2G002TRIPDUETOAGROUNDFAULT UDUMMYA08Z
1.00E12 A08UNAVAILABLEDUMMYEVENT
UDUMMYXR1Z
RESAUXTXFRXR1UNAVAILABLEDUMMYEVENT
UFNA274S
2.17E04 FANA274FTSTARTONDEMAND
UFNA2741DR
3.11E03 FANA274FTRUNFOR24H
UFNA275S
2.17E04 FANA275FTSTARTONDEMAND
UFNA2751DR
3.11E03 FANA275FTRUNFOR24H
ULX2T035J
1.00E03 LEVELSWITCH2T035FTACT/DEACTONDEMAND
UMP2P093S
1.04E03 2P093FTS
UMP2P0936HR
1.25E04 2MDP93FTR6HR
UMP2P096S
1.04E03 2P096FTS
UMP2P0966HR
1.25E04 2MDP96FTR6HR
UOO3A03Z
1.45E02 INSUFFICIENTPOWERFROM4160VSWGR3A03 UOO3A07Z
1.45E02 INSUFFICIENTPOWERFROM4160VSWGR3A07 U3B2A081DR
2.09E06 INSUFFICIENTPOWERON4KVBUS3A08
WTK0082D
5.00E07 TANK008LEAK/RUPTUREW/I1H
WTK0102D
5.00E07 TANK010LEAK/RUPTUREW/I1H
XHOS3PE453A
1.00E+00
XHOS3PE453AT
XHOSLOPT
XHOSMFWT ?
XHOSMSIS
1.00E+00 SPURIOUSMSISSIGNALDUETOFIRE
XHOSRCPFT
1.00E+00 RCPFAILSTOTRIPFOLLOWINGLOSSOFCCWFIRE
YSV297AJ
1.00E03 PZRVENTVALVE297AFAILSTOOPENONDEMAND(SOLENOID)
YSV299J
1.00E03 PZRVENTVALVE299FAILSTOOPENONDEMAND(SOLENOID)
CutsetAnalysis Scenario Sequence InitiatingEventImpact MitigationSystemImpact ProposedRecovery ProposedModification 3BCP09/08EC81