ML19086A272

From kanterella
Jump to navigation Jump to search
Oak Ridge Associated Universities - Letter Report for Analytical Results for Five Soil Samples Associated with the Humboldt Bay Power Plant in Eureka, CA
ML19086A272
Person / Time
Site: Humboldt Bay
Issue date: 09/12/2012
From: Ivey W
Oak Ridge Associated Universities
To: Schlapper G
NRC Region 4
References
DCN: 5201-LR-01-0, DE-AC05-060R23100
Download: ML19086A272 (3)


Text

September 5, 2012

}.fr. Gerald Schlapper U.S. Nuclear Regulatory Commission, Region IV 1600 East Lamar Boulevard Arlington,TX 76011 ORISE CONTRACT NO. DE-AC05-060R23100 ORAU OAK RIDGE ASSOCIATED UNIVERSITIES

SUBJECT:

LETTER REPORT FOR ANALYTICAL RESULTS FORFIVE SOIL SAMPLES ASSOCIATED \\VITH THE HUMBOLDT BAY POWER PLANT IN EUREKA, CALIFORNIA

.[INSPECTION REPORT NO. 05000133/2012011] (RFTANO.12-001)

DCN: 5201-LR-01-0

Dear :

tvir. Schlapper:

Oak Ridge Associated Universities (ORAU), tinder the Oak Ridge Institute for Science and Education (OIUSE) contract, received five soil samples on August.21, 2012 from the Humboldt Bay Power Plant in Eureka, California. The samples were analyzed for gamma emitting radionuclides by gamma spectroscopy.

The samples were split samples and were received directly from tl1e Humboldt Bay laboratory. There was no NRC Form 303 or Form 303A supplied witl1 tl1e samples. The sample identification numbers are presented in Table 1 and tl1e gamma spectros.copy data are presented in Table 2. The pertinent procedure reference is included with the data table.

ORAU's Quality Cancro! (QC) requirements were*met for tl1ese analyses. The QC files are available for your review upon request.

My contact information is listed below. You may also contact Forrest Smith at 865.574.9802 with any questions or comments.

Sincerely,

/JM&fi Ir Wade Ivey, Manager Laboratory WPI:WFS:km Enclosures c:

T. Carter, NRC/FS:tvIE/D\\'<'1'IEP T-8F5 Electronic:

S. Nesmith, NRC/FSivIE/PBPA/T\\VFN 8A23 R. Evans, NRC Region N S. Roberts, ORAU T. Vitkus, OR.AU Telephone: 865.576.9184 Fax: 865.241.3248 File 5201 E-mail: wadc.ivey@orau.org P.O. Box 117 I Oak Ridge, TN 37831 I www.orise.orau.gov

ORISE Sample ID 5201S0001 5201S0002 5201S0003 5201$0004 5201SOOOS Humboldt Bo.y Power Pinnt TABLE!

SAMPLE IDENTIFICATIONS AND COLLECTION INFORMATION HUMBOLDTBAYPOWERPLANT EUREKA, CALIFORNIA NRC Region IV Collection Sample ID Date

. FSS-0025 7/5/2012*

FSS-028

. 7/5/2012 FSS-030 7/5/2012.

FSS-032 7/5/2012 FSS-038 7/5/2012 Collection Time 11:22AM 11:35AM 11:46AM 11:55AM 12:06 PM

  • s201-LR-01.0

ORISE Sample NRC Region IV ID SampldD TABLE2 CONCENTRATIONS OF SELECTED GAMMA EMITTING RADIONUCLIDES IN SOIL SAMPLES I

BY GAMMA SPECTROSCOPY CP1, REVISION. _17 HUMBOLDT BAY POWER PLANT EUREKA, CALIFORNIA Radionuclide Concentrations, TPUs8, and MDCl (pCi/g)

Ra-226 by Pb-214 K-40 Th-232 by Ac-228 U-238 by Tb-234

. 5201S0001 FSS-0025 0.38 + 0;05 0.07 7.47 +

5201S0002 -

FSS-028 0.26 + 0.04- ' 0;05 6.28 +/-

5201S0003

-FSS-030 0.31 + 0.05 0.07 7.12 +

5201$0004 FSS-032 0.35 + 0.05

  • 0.05 7.40

+

5201S0005 FSS-038 0.35 + 0.05_

0.06 - 6.84 +/-

"Unccnaintics represent the 95% confidence level, based on total propagated unccrminties.

bMDCs arc after the commas.

  • zero value is due to rounding or sample and background count rates being equal.

I lumholdt Bay Power 111ant 0.83 0.53 0.50 + 0.10

  • 0.11 0.72 +/- 0.34 0.76

- 0.61. 0.40 0.30 +/- 0.07

  • 0.09 0.29 +/- 0.23. 0.53 0.76 0.46 0.36 + 0.09 0.13 0~55 + 0.31 0.70 0.70. 0.45 0.37 + 0.10. 0.16 0.37 +/- 0.29
  • 0.68 0.74 0.45 0.35 + 0.09,
  • 0.15 0.64 + 0.34. 0.78 U-235 0.02 + 0.09 0.21 o.ooc +/- 0.07 0.15 0.03 +/- 0.07 0.16 0.02 +/- 0.09 0.18 0.07 +/- 0.07 0.15 5201-1,R-Ol-O