TMI-1 UFSAR CHAPTER 02 2.1-1 REV. 22, APRIL 2014 2.0 SITE AND ENVIRONMENT 2.1 GENERAL DESCRIPTION AND LOCATION 2.1.1 SITE LOCATION Three Mile Island is located approximately 2.5 miles south of Middletown, Pennsylvania, at longitude 7643'30" west and at latitude 4009'15 north (approximate midpoint of the station).

It is one of the largest of a group of several islands in the Susquehanna River and is situated about 900 ft from the east bank. It is elongated parallel to the flow of the river, with its longer axis oriented approximately due north and south. The island is about 11,000 ft in length and 1700 ft in width.

The southeasterly flowing Susquehanna River makes a sharp change in direction, to nearly due south, in the vicinity of Middletown. After this directional change just north of Three Mile Island, the river widens to approximately 1.5 miles.

The station is located on Three Mile Island, which is situated in the Susquehanna River upstream from York Haven Dam, in Londonderry Township of Dauphin County, Pennsylvania, about 2.5 miles north of the southern tip of Dauphin County, where Dauphin is coterminous with York and Lancaster Counties. Its location with respect to regional topographic and cultural features is shown on Figure 2.1-1 and with respect to local features on Figure 2.1-2.

2.1.2 SITE DESCRIPTION Figure 2.1-3 shows Three Mile Island and the designated Exclusion Area. For accident evaluations, the distance to the Exclusion Area in each direction is used. Those distances may be determined from Figure 2.1-3.

2.1.2.1 Exclusion Area Control The exclusion area is a 2,000 foot radius from a point equidistant between the center of the TMI-1 and TMI-2 Reactor Buildings. It includes portions of Three Mile Island, the river surface around it, and a licensee owned portion of Shelley Island, as shown on Figure 2.1-3. The site is located on the northern third of Three Mile Island. The licensee directly owns the TMI-1 site and owns or controls all land within the exclusion area. The Exclusion Area Agreement by and among the GPU companies and Exelon provides Exelon with authority, within those parts of the exclusion area for TMI-1 owned and controlled by the GPU companies, to determine and control all activities in the exclusion area, including exclusion of personnel and property from the area, to the extent necessary to comply with the requirements of 10 CFR 100. Exelon owns and controls the remaining portion of Three Mile Island.

York Haven Dam, immediately to the south of the site, has no locks. Thus, no commercial river traffic exists in the area. In the event of an emergency where control of the river in the exclusion area is recommended, the licensee will contact PEMA who will be responsible for controlling or restricting boat traffic in the area to prevent access within the exclusion area.

TMI-1 UFSAR CHAPTER 02 2.1-2 REV. 22, APRIL 2014 2 1.2.2 Boundaries For Establishing Effluent Release Limits The boundary line forming the base for the Technical Specification Limits on the release of gaseous effluents will be as shown on Figure 2.1-3. This boundary line includes portions of the Susquehanna River surface between the east bank of the river and Three Mile Island and between Three Mile Island and Shelley Island. Land surface included within this boundary line is owned or controlled by the licensee. Access to the exclusion area is readily controlled as stated in Subsection 2.1.2.1.

TMI-1 UFSAR CHAPTER 02 2.2-1 REV. 18, APRIL 2006 2.2 POPULATION 2.2.1 POPULATION WITHIN 10 MILES The population within a 10 mile radius of TMI-1 is shown on Figures 2.2-1 through 2.2-5. The current population figures within the 10-mile radius are based upon the 1990 census data, which are the most recent available. The population projections, by decade through 2010, were based on information obtained from State and county planning boards, where available, or on projections estimated from past growth. Note also that the projections were based on 1980 census data.

2.2.2 POPULATION WITHIN 50 MILES The population within a 50 mile radius is shown on Figures 2.2-6 through 2.2-10. Population figures are based upon the 1980 census data, which are the most recent available (population within 10 miles based on 1990 census data). The population projections, by decade through 2010, were based on information obtained from State and county planning boards where available or on projections estimated from past growth. Counties and communities within a 50 mile radius of TMI are shown on Figure 2.2-11. The populations shown are from the 1990 census data.

2.2.3 LOW POPULATION ZONE The low population zone for Three Mile Island Unit 1 was chosen as a 2 mile radius from the station. The zone was based on a low 1980 population density of approximately 1805 people in the 2 mile radius together with the highway facilities available for evacuation within a reasonable time, should it become necessary. The current population by sector is shown on the 0 to 10 mile population wheel, Figure 2.2-3. The population in the LPZ has decreased from 2539 (1980 census) to 1598 (1990 census).

2.2.4 TRANSIENT POPULATION There are no schools or major industries within the low population zone; thus, no significant shift in population is expected to occur on a daily basis in the area.

There is some seasonal shift in population within approximately 5 miles of the station since there are over 100 summer cabins on the islands in the Susquehanna River within 5 miles of the site. The seasonal population has been included in the 0 to 10 mile population distribution described above.

Additional transient shifts in population may occur during the summer due to boating activity on the Susquehanna River in the vicinity of the plant site.

2.2.5 POPULATION CENTER The nearest population center, as defined in 10CFR100, is Harrisburg, with a 1990 population of 52,376. The center of Harrisburg is located 12 miles northwest of the site.

TMI-1 UFSAR CHAPTER 02 2.2-2 REV. 18, APRIL 2006 2.2.6 PUBLIC FACILITIES AND INSTITUTIONS Public facilities and institutions, including county location and name within a 10 mile radius of Three Mile Island are given in Table 2.2-2.

The following is a summary of the facilities and institutions within a 10 mile radius: (Information based on the 1990 census data) a.

Schools There are 65 public, private, and parochial schools within 10 miles: 13 in York County; 3 in Cumberland County; 39 in Dauphin County; and 10 in Lancaster County.

The nearest school to the site is the Northumberland Center (Capital Area Intermediate Unit), located in Dauphin County. The school is approximately 13,000 feet from the site.

b.

Recreation Seventeen recreational facilities have been identified within the 10 mile emergency planning zone; 7 in York County; and 10 in Dauphin County.

The nearest public recreational facility is the boat launching facility constructed by Metropolitan Edison Company approximately 8000 feet north from the site in Dauphin County. For more details see Appendix 3 of the Evacuation Travel Time Estimate for the TMI Nuclear Generating Station Emergency Planning Zone, (i.e., Transient and Special Facility Population Data).

c.

Hospitals, Nursing Homes, and Similar Facilities There are 13 facilities located within the 10 mile emergency planning zone, the largest being the Milton S. Hershey Medical Center of the Pennsylvania State University. This hospital and teaching institution is located approximately 10 miles from the site. For more details see Appendix 3 of the Evacuation Travel Time Estimate for the TMI Nuclear Generating Station Emergency Planning Zone, (i.e., Transient and Special Facility Population Data).

2.2.7 BUSINESS FACILITIES WITHIN 5 MILES Table 2.2-1 lists all industrial and manufacturing facilities within 5 miles of the site. This information is based on the 1990 census data (Reference 29).

TMI-1 UFSAR CHAPTER 02 2.2-3 REV. 18, APRIL 2006 TABLE 2.2-1 (Sheet 1 of 1)

INDUSTRIAL AND MANUFACTURING FACILITIES WITHIN FIVE MILES OF SITE 1.

Chloe Textiles 2.

Intercon Systems 3.

Zeager Brothers, Inc.

4.

Olivetti Supplies, Inc.

5.

York Haven Power Co.

6.

DIE-TECH 7.

Brunner Island Station 8.

LASCO Bathware 9.

Fleetwood 10.

Tyson Warehouse 11.

American Air Filter

Reference:

1990 Evacuation Travel Time Estimates for Three Mile Island Nuclear Generating Station Plume Exposure Pathway Emergency Planning Zone

TMI-1 UFSAR CHAPTER 02 2.2-4 REV. 18, APRIL 2006 Table 2.2-2 (Sheet 1 of 3)

PUBLIC FACILITIES & INSTITUTIONS WITHIN A 10 MILE RADIUS LANCASTER COUNTY Donegal School District Maytown Elementary School Elizabethtown Area School District Elizabethtown Area High School Elizabethtown Area Middle School Bainbridge Elementary School East High Elementary School Fairview Elementary School Millroad Elementary School Rheems Elementary School St. Peter Parochial School Mt. Calvary Christian Center Elizabethtown College YORK COUNTY Northeastern School District Northeastern Senior High School Northeastern Junior High School Conewago Elementary School Mount Wolf Early Learning Center Orendorf Elementary School York Haven Elementary School West Shore School District Fairview Elementary Fishing Creek Elementary Mount Zion Elementary Newberry Elementary Red Land High School Red Mill Elementary The Circle School

TMI-1 UFSAR CHAPTER 02 2.2-5 REV. 18, APRIL 2006 Table 2.2-2 (Sheet 2 of 3)

PUBLIC FACILITIES & INSTITUTIONS WITHIN A 10 MILE RADIUS DAUPHIN COUNTY Middletown Area School District Alice Demey Elementary School George D. Mansberger Elementary School John C. Kunkel Elementary School Lyall J. Fink Elementary School Middletown Senior High School George W. Feaser Middle School Middletown Christian School Seven Sorrows BVM School Lower Dauphin Area School District Conewago Township Elementary School Londonderry Township Elementary School A.B. Nye Elementary School E.Z. Price Elementary School South Hanover Township Elementary School Lower Dauphin Junior High School Lower Dauphin Senior High School Derry Township School District M.S. Hershey Middle School Hershey Elementary School Hershey Senior High School Mountain View Christian School St. Joan of Arc School Milton Hershey School Steelton-Highspire School District Steelton-Highspire Elementary School Steelton-Highspire Junior/Senior High School St. John Newmann Consolidated School

TMI-1 UFSAR CHAPTER 02 2.2-6 REV. 18, APRIL 2006 Table 2.2-2 (Sheet 3 of 3)

PUBLIC FACILITIES & INSTITUTIONS WITHIN A 10 MILE RADIUS DAUPHIN COUNTY (cont'd)

Central Dauphin School District Paxtang Elementary School Chamber Hill Elementary School Rutherford Elementary School Southside Elementary Tri-Community Elementary School Swatara Junior High School Town and Country Day School St. Catherine Laboure School Lawnton Capital Area Intermediate Units Northumberland Center Camp Harris Oberlin School Aspin Center The Pennsylvania State University at Harrisburg The Capital College Harrisburg School District Foose Early Childhood Center CUMBERLAND COUNTY West Shore School District New Cumberland Middle School Hillside Elementary School St. Theresa School

Reference:

1990 Evacuation Travel Time Estimates for Three Mile Island Nuclear Generating Station Plume Exposure Pathway Emergency Planning Zone.

TMI-1 UFSAR CHAPTER 02 2.3-1 REV. 18, APRIL 2006 2.3 LAND USE Land within a 10 mile radius of the site is used primarily for farming. Farm produce includes dairy, tobacco, poultry, vegetable, fruit, alfalfa, soybeans, corn, wheat, and other products.

Agricultural characteristics for Dauphin, York, and Lancaster Counties are listed in Table 2.3-1.

The nearest dairy farm is located on Gingrich Road. It is approximately one mile from the center of Three Mile Island Nuclear Station and is known as the Alwine Farm.

A summary of land use for Dauphin County, in which the site lies, and for the two other adjacent counties (York and Lancaster) is as follows:

Percent of Land Used Use Dauphin York Lancaster Forest 48.7 27.8 16.2 Crops 29.6 45.3 61.8 Pasture 3.6 7.6 3.4 Other 18.1 19.3 18.6 The location of these counties is shown on Figure 2.2-1. Typical industries in the site region are listed in Table 2.3-2. The predominant industrial areas are around Harrisburg and Middletown, up river from the site.

Transportation routes in the site vicinity on the east bank of the river include State Highway 441, a two-lane blacktop road passing north and south, and a Norfolk Southern Railroad one-track line adjacent and parallel to this highway; each is outside the exclusion boundary. On the west bank, there is a multitrack Norfolk Southern Railroad line at the river's edge about l.25 miles west of the site and a blacktop, two-lane road parallel to it. There is no commercial water transportation on the river adjacent to the site. The river is transected south of the site by the York Haven Dam, which does not have locks.

There is no commercial fishing in the Susquehanna River in the vicinity of TMI. Recreational fishermen can expect to catch about 42 species of fish in the Susquehanna River. Species other than those listed in Table 2.3-3 may be taken, but not in significant numbers.

TMI-1 UFSAR CHAPTER 02 2.3-2 REV. 18, APRIL 2006 TABLE 2.3-1 (Sheet 1 of 1)

AGRICULTURAL CHARACTERISTICS (AS OF 1987)*

Lancaster Dauphin York Number of farms (1987) 5,080 790 2,340 Land in farms (acres) 417,296 112,821 299,879 Percent of total land area 68.5 33.4 51.7 Average size of farm (acres) 84 145 130 Value of Products Sold ($)

109,295,000 13,086,000 41,942,000 Field crops ($)

101,635,000 11,761,000 33,161,000 Vegetables ($)

6,019,000 774,000 4,285,000 Fruits & nuts ($)

1,641,000 551,000 4,496,000 Forest products & horticultural products ($)

10,824,000 1,267,000 5,388,000 Poultry & poultry products ($)

Chickens 21,488,000 1,190,000 1,434,800 Eggs 85,943,000 5,381,000 7,840,000 Milk/Dairy Products($)

203,741,000 14,582,000 30,106,000 Livestock & Livestock Products ($)

201,551,500 17,272,500 38,692,350 Crops Harvested Corn (acres) Grain 105,500 26,000 70,000 Silage 75,100 6,700 16,500 Wheat (acres) 17,500 4,000 23,500 Potatoes (acres) 1780 80 2,040 Tobacco (acres) 10,010 20 110

  • Source:

Statistical Summary 1987-88 and PA Dept. of Ag. Annual Reports; Natl. Ag.

Statistics Service U.S. Dept. of Agriculture/PA Dept. of Agriculture Publ. PASS-99

TMI-1 UFSAR CHAPTER 02 2.3-3 REV. 18, APRIL 2006 TABLE 2.3-2 (Sheet 1 of 3)

TYPICAL MAJOR* INDUSTRIES WITHIN 10 MILES OF THREE MILE ISLAND COMPANY LOCATION/DIRECTION

1. Covenco Lower Swatara 6-7 miles NW
2. Bethlehem Steel Steelton 7-8 miles NW
3. SAIC Londonderry 5-6 miles N
4. AMP Inc.

Lower Swatara 5-6 miles NNW

5. AMP Swatara 8-9 miles NW
6. Mack Trucks Lower Swatara 5-6 miles NW
7. Turnpike Ind. Park Lower Swatara 5-6 miles NW
8. Advanced Conversion Lower Swatara 5-6 miles NNW
9. Chloe Textiles Lower Swatara 3-4 miles NNW
10. UPS Swatara 9-10 miles NW
11. UPS Lower Paxton 9-10 miles NNW
12. Pa Workers Comp Harrisburg 8-9 miles NW
  • Business with greater than 100 employees

TMI-1 UFSAR CHAPTER 02 2.3-4 REV. 18, APRIL 2006 TABLE 2.3-2 (Sheet 2 of 3)

TYPICAL MAJOR* INDUSTRIES WITHIN 10 MILES OF THREE MILE ISLAND COMPANY LOCATION/DIRECTION

13. Jackson Manufacturing Harrisburg 9-10 miles NW
14. Hershey Foods 1 Derry 9-10 miles NNE
15. Hershey Foods 2 Derry 9-10 miles NNE
16. Hershey Foods 3 Derry 9-10 miles NNE
17. Hershey Foods 4 Derry 9-10 miles NNE
18. Hershey Foods 5 Derry 9-10 miles NNE
19. Hershey Foods 7 Derry 9-10 miles NNE
20. Maple Press Manchester 7-8 miles S
21. Offsite Advantage Fairview 6-7 miles WNW
22. Admin Center for Education Fairview 6-7 miles WNW
23. DuPont Electronics Manchester 9-10 miles S
24. DuPont Electronics Fairview 5-6 miles W
25. FES, Inc.

Manchester 9-10 miles S

  • Business with greater than 100 employees

TMI-1 UFSAR CHAPTER 02 2.3-5 REV. 18, APRIL 2006 TABLE 2.3-2 (Sheet 3 of 3)

TYPICAL MAJOR* INDUSTRIES WITHIN 10 MILES OF THREE MILE ISLAND COMPANY LOCATION/DIRECTION

26. Trenwyth Manchester 9-10 miles S
27. Preston Trucking Manchester 9-10 miles S
28. Progressive Typeset Manchester 9-10 miles S
29. Pa Auto Dealers Assoc.

Conawago 5-6 miles SSW

30. New Cumberland Depot Fairview 7-8 miles WNW
31. USA Direct Manchester 7-8 miles S
32. M&M Mars Elizabethtown 6-7 miles E
33. Armstrong Industries E. Donegal 9-10 miles SE
34. Wengers Feed Mill Mount Joy 7-8 miles E
35. Verdelli Farms Derry 8-9 miles N
36. Turnpike Commission Lower Swatara 5-6 miles NW

Reference:

1990 Evacuation Travel Time Estimates for Three Mile Island Nuclear Generating Station Plume Exposure Pathway Emergency Planning Zone.

  • Business with greater than 100 employees

TMI-1 UFSAR CHAPTER 02 2.3-6 REV. 18, APRIL 2006 TABLE 2.3-3 (Sheet 1 of 2)

FISH SPECIES OF THE SUSQUEHANNA RIVER Common Name Scientific Name Trout Brown Trout Salmo trutta Pikes Northern Pike Esox lucius Muskellunge Esox masquinongy Minnows Goldfish Carassius auratus Carp Cyprinus carpio Cutlips minnow (rare)

Exoglossum maxillinqua Golden shiner Notemigonus crysoleucas River chub (rare)

Nocomis micropogon Common shiner Notropis cornutus Spottail shiner Notropis hudsonius Swallowtail shiner Notropis procne Spotfin shiner Notropis spilopterus Bluntnose minnow Pimephales notatus Blacknose dace (rare)

Rhinichthys atratulus Longnose dace Rhinichthys cataractae Creek chub Semotilus atromaculatus Fallfish (rare)

Semotilus corporalis Comely shiner Notropis amoenus Mimic shiner Notropis volucellus Suckers Quillback Carpiodes cyprinus White sucker Catostomus commersoni Northern hog sucker Hypentelium nigricans Shorthead redhorse Moxostoma macrolepidotum Catfish White catfish Ictalurus catus Black bullhead Ictalurus melas Yellow bullhead Ictalurus natalis Brown bullhead Ictalurus nebulosus Channel catfish Ictalurus punctatus Freshwater eels American eel Anquilla rostrata Herrings Gizzard shad Dorosoma cepedianum

TMI-1 UFSAR CHAPTER 02 2.3-7 REV. 18, APRIL 2006 TABLE 2.3-3 (Sheet 2 of 2)

FISH SPECIES OF THE SUSQUEHANNA RIVER Common Name Scientific Name Sunfish and Bass Rock bass Ambloplites rupestris Redbreast sunfish Lepomis auritus Green sunfish Lepomis cyanellus Pumpkinseed Lepomis gibbosus White crappie Pomoxis annularis Black crappie Pomoxis nigromaculatus Bluegill Lepomis macrochirus Smallmouth bass Micropterus dolomieui Largemouth bass Micropterus salmoides Perches and Darters Tessellated darter Etheostoma olmstedi Yellow perch Perca flavescens Walleye Stizostedion vitreum Other species may be found in the Susquehanna but not in significant numbers.

TMI-1 UFSAR CHAPTER 02 2.4-1 REV. 18, APRIL 2006 2.4 AIRPORT TO SITE RELATIONSHIP There are two airports in the site region, Harrisburg International Airport, formerly called Olmsted State Airport, 2.5 miles northwest, and Capital City Airport, formerly called Harrisburg-York Airport, 8 miles west northwest. The former handles primarily commercial and the latter primarily private aircraft. Runway location and use is discussed in Section 2.4.1, and the probability of airplane strikes on the plant is discussed in Section 2.4.2.

2.4.1 RUNWAY LOCATION AND USE Harrisburg International Airport is located on the east bank of the river and has only one runway (130o/310o). Instrument landing approaches to 310o would align with the runway direction and the aircraft would pass approximately 7500 feet NNE of the site. Aircraft intending to land on 3100 could pass near or over the site prior to turning on final approach; however, this would not be a standard VFR approach. The normal takeoff pattern on 130o is away from the site, i.e.,

the aircraft turns to the left after takeoff. Aircraft takeoff and landing patterns in the other respective direction are out of the site area. The missed approach holding pattern for Harrisburg International Airport is also not in the site area.

The Capital City Airport has two runways (120o/300o and 80o/260o. Instrument landing approaches to 3000 would align with the runway direction and the aircraft would pass approximately 1/2 mile to the NNE of the site at an elevation of about 2300 feet. Aircraft on VFR intending to land on 300o could pass near, or over, the site prior to turning on final approach.

However, 300o is seldom used due to high terrain considerations and short length (4000 feet).

Occasionally, strong crosswind effects on other landing approaches require the use of this runway. Aircraft departing on 120o would normally start a right turn approximately 1 to 3 miles from the end of the runway, depending upon type of aircraft. Aircraft takeoff and landing patterns in the other respective directions are out of the site area. The Capital City Airport has one missed approach holding pattern. It is located such that aircraft would pass near the site at an altitude of roughly 3000 feet. However, aircraft in the holding pattern would comprise considerably less than 1 percent of all aircraft instrument approaches. Most aircraft having missed the landing would immediately be vectored by radar to make another approach.

2.4.2 PROBABILITY OF AIRPLANE STRIKES*

2.4.2.1 General The Three Mile Island Station is 2.5 miles (straight-line distance) from the eastern end of the single runway of Harrisburg International Airport. The station is about 1.5 miles to the southwest of the extended runway center line. The respective locations of the station and the airport and its runway are shown on Figure 2.4-1 of the FSAR. Air traffic patterns in the site area are based on estimates made in 1991.

Estimates of the probability of various types of airplane crashes into the plant and of related fires are given in Table 2.4-1. The development of each estimate is summarized below.

  • Note: The original analyses and licensing bases can be found in the PSAR and Update-1 to the UFSAR and is based on the period of record 1956 to 1965.

TMI-1 UFSAR CHAPTER 02 2.4-2 REV. 18, APRIL 2006 2.4.2.2 Probability Of Strike By Large Aircraft Accident records in the annual statistical summaries of U.S. air carrier accidents (Reference 1) and in individual aircraft accident reports available from the National Transportation Safety Board covering about 118 million aircraft movements (landings plus takeoffs) during the 10 year period 1978 through 1987 were examined and are summarized in Tables 2.4-2, 2.4-3, and 2.4-4. This information along with data concerning the number and types of aircraft movements at Harrisburg International Airport were used to estimate the probability of a hypothetical aircraft incident as shown in Items 1 and 2 of Table 2.4-1.

The types of air carrier aircraft used in the aircraft incident study for Harrisburg International Airport in terms of approximate percent of total air carrier movements are:

DC-9 31%

Boeing 727 26%

Boeing 737 17%

Shorts 360 16%

Other 10%

100%

In addition to air carrier movements, there are some Air National Guard flights from a unit stationed at Harrisburg International Airport (using C-130 and C-5A type aircraft) and some small percentage of transient military flights including helicopters. Also, United Parcel Service (UPS) began daily flights to Harrisburg International Airport using Boeing 757 in October 1989.

Even though the accident records available for this study update do not go beyond 1987, this additional information has been incorporated in Section 2.4.2.3; "Probability of a strike by a very large aircraft".

Of all the aircraft using the airport, at the time of evaluation the C5A was the largest type.

Table 2.4-5 gives pertinent characteristics of typical air carrier aircraft. Since most of the aircraft movements at Harrisburg International Airport are of the air carrier type, the use of air carrier accident statistics were considered appropriate.

In estimating the probability of an air carrier aircraft strike, it was assumed that there are 80,000 air carrier movements per year at Harrisburg International Airport, which was about five times the 1989 annual rate. During the 10 year period 1979 to 1988, total air carrier movements in the U.S. increased by a factor of about 37 percent. If the national increase in the next ten years is like that in the past ten and Harrisburg International Airport increases at twice that national rate, it would have about 62,000 movements per year by 1999, but would not reach 177,000 movements during the plant lifetime if movements continued to increase by the same increment each year. Even if a doubling of the movements in five to ten years is assumed and if this very fast increase were achieved and sustained, 177,000 movements per year could be realized by sometime between 1990 and 2000. Since the midpoint of assumed plant life will be about 1994, the assumption of 177,000 air carrier movements a year as a basis for statistical analysis is believed to be reasonable.

Using the data of the National Transportation Safety Board summarized in Table 2.4-2, individual accident briefs were examined to determine the portion of the total fatal accidents which occurred in the proximity of airports (i.e., within a 5 mile radius of the end of the runway

TMI-1 UFSAR CHAPTER 02 2.4-3 REV. 18, APRIL 2006 being used). The results are summarized in Table 2.4-3. The types of aircraft involved in these accidents are listed in Table 2.4-4.

The accidents which involved one or more fatalities were chosen as the basis for estimating the probability of the types of crashes which could have a significant effect on the plant because the occurrence of fatalities is usually due to high deceleration rates and/or large fires. Nonfatal accidents were not included because examination of the records indicates that those occurring away from the airport runways usually have some direction and altitude control before impact and are of the type in which there is a good chance large structures could have been avoided.

Fatal landing accidents inside the area +/- 0.5 mile from the runway extended centerline were excluded.

Fatal takeoff accidents within a radius of 1 mile were excluded. Fatal accidents outside a 5 mile radius were excluded on the grounds that accidents further out were not representative of the type which would affect the plant due to its proximity to the airport.

Random geographic distribution within a 4 mile radius was assumed for the fatal accidents selected as a data base. Random distribution was assumed because the actual distribution with respect to a runway in use appeared to be random.

The estimates of strike probability are based on statistics for the probability of a fatal accident per landing or takeoff for the 10 year period 1978 through 1987, inclusive. Accident statistics for the future will probably be different. However, fatal accident probability per landing and takeoff is expected to decrease in the future because of expected improvements in aircraft and engine reliability, new aircraft testing, navigation equipment and methods, pilot training, and fire control after impact. Further, Harrisburg International Airport has a long runway (8000 ft) which should contribute to the safety of landing and takeoff operations (it is about 1500 ft longer than the main runway at Washington National Airport and has a 1000 ft overrun on each end).

For the reason discussed above, it is probable that the fatal accident probability chosen for the statistical analysis is reasonable and may be conservative.

During the 10 year period 1978 - 1987, there were approximately 59 million aircraft arrivals and 59 million departures. Therefore, the applicable accident frequency (f) is about 4/(59 x 106), or 6.8 x 10-8 per departure and 7/(59 x 106), or 1.2 x 10-7 per landing considering the selection criteria aforementioned.

The probability of a crash on the station for any one landing or takeoff was taken to be the applicable accident frequency times the ratio of the "target area" of the plant to the "total area" in which the applicable accidents are assumed to happen with random distribution. These areas were estimated as follows:

a.

The "target area" for arrival (landing) accidents was assumed to be approximately the horizontal area (on the ground) which would be covered by the plant plus the shadow cast by the largest vertical cross section of the plant (excluding cooling towers) assuming light rays emanate from the plane as it approaches the plant along a line inclined 10 degrees above the horizontal. This angle was chosen as being a typical descent line for airplanes crashing on landing. (If the angle were greater, the area would be less and the probability of a strike would be less.) The area of the shadow so

TMI-1 UFSAR CHAPTER 02 2.4-4 REV. 18, APRIL 2006 obtained was increased by 50 percent to account for airplanes which might crash in front of the plant and slide into it. The resulting target area for arrival accidents (here called Aa) is about 0.0225 square miles.

b.

The "target area" for departure (takeoff) accidents was similarly estimated using a 45-degree approach angle believed typical of departure crashes. This area (here called Ad) was estimated to be 0.0066 square miles.

c.

The "total area" for random distribution of departure accidents (here called Atd) is (4)2 -

(1)2 = 47.1 square miles. Similarly, the "total area" for arrival accidents (Ata) is approximately (4)2 - (0.5)2 = 49.5 square miles.

For any one arrival, the probability (Pa) of hitting the plant is:

Pa = fa Aa/Ata = 1.2 x 10-7 x 0.0225 = 5.4 x 10-11 49.5 Similarly, for any one departure, the probability of hitting the plant is:

Pd = fd Ad/Atd = 6.8 x 10-8 x 0.0066/47.1 = 9.5 x 10-12 and for both departures and arrivals the average probability is:

Pa +/- Pd = 3.2 x 10-11 2

This is equivalent to a recurrence interval of one strike every 3.1 x 1010 years per aircraft movement per year.

If it is assumed that there are about 177,000 aircraft movements a year at Harrisburg International Airport and that half of the takeoffs (44,250) and half the landings (44,250) are from the end of the runway nearest the plant and therefore could affect it, the chance for the plant being hit is:

p = 44,250 (Pa+Pd) = 44,250 (5.4 x 10-11 + 9.5 x 10-12) = 2.8 x 10-6 This is equivalent to a recurrence interval for a crash on the plant of about once in 0.36 million years.

In estimating the effect of impact on the plant, it has been assumed that the impact speed is up to 200 knots. The fact that the speed limit in the geographical area of interest is 180 knots would indicate that the assumption of a 200 knot impact speed is reasonable.

Analyses have been performed to determine the effects of the unlikely event of the simultaneous rupture of four steam lines outside the Reactor Building as a result of an aircraft impact. Blowdown of both steam generators will cause the Reactor Coolant System Temperature to decrease to about 490F at 43 seconds. Reactor trips on high neutron flux or low reactor coolant pressure caused by the initial cooldown.

TMI-1 UFSAR CHAPTER 02 2.4-5 REV. 18, APRIL 2006 Both steam generators blow dry in 43 seconds after the ruptures. Since feedwater has been isolated, the accident is terminated, and the core does not return to criticality.

An equilibrium reactor system cooldown and depressurization is achieved by operator-controlled emergency feedwater flow with steam relief out of the steam line breaks.

2.4.2.3 Probability Of A Strike By A Very Large Aircraft

) At a High Angle (

On a Critical Structure The critical structures referred to in the title of this Subsection are those which are protected for direct strikes of large aircraft as described in Chapter 5.

It is assumed that very large aircraft comprise 3 percent of the total assumed air carrier movements at Harrisburg International Airport or 0.03 x 177,000 = 5310 movements/year.

Flight path angle (relative to the horizontal) was assumed to be randomly distributed from 0to 20for landing accidents and 0to 90for takeoff accidents. The probability of a strike from selected directional quadrants was assumed to be 40 percent from a quadrant from 300 through north to 30; 40 percent from a quadrant from 30to 120; 10 percent from 120to 210; and 10 percent from 210through 300.

These percentages were selected by considering the plant location with respect to the airport and surrounding terrain. The horizontal angle of approach in any quadrant was assumed to be random.

The strike probability for large aircraft was taken to be 2.8 x 10-6/yr based on an assumed virtual target area of 630,000 ft2 for landing and 185,000 ft2 for takeoff accidents. About 64 percent of the strike probability was due to landing and 36 percent due to takeoff accidents.

(b) (5)

(b)

(5)

(b) (5)

(b) (5)

(b) (5)

TMI-1 UFSAR CHAPTER 02 2.4-6 REV. 18, APRIL 2006 For takeoff accidents, the probability of a very large airplane strike from a given quadrant is:

PT = 2.8 x 10-6 x 0.03 x 0.36 x Q = 3.0 x 10-8 Q and for landing accidents it is:

PL = 2.8 x 10-6 x 0.03 x 0.64 x Q = 5.4 x 10-8 Q Where Q represents the fraction of total strikes arriving from a given directional quadrant.

The result indicates that the sum of probabilities from all quadrants is about 1.7 x 10-8/yr.

2.4.2.4 Probability Of Small Aircraft Strike The amount of general aviation movements in the Harrisburg area has been estimated by reviewing information received directly from airport records. In 1989, there were a total of 124,700 landings plus takeoffs, or 62,350 landings and 62,350 takeoffs at Harrisburg area airports. Of these, about 46 percent occurred at Capital City and 54 percent at Harrisburg International Airport. Typical types of aircraft involved are Beechcraft, Piper, and Cessna.

Characteristics of the largest and smallest of each aircraft of these types are given in Table 2.4-6.

Accident data for general aviation operations were obtained from the National Transportation Safety Board Annual Review Reports (Reference 22) and are given in Table 2.4-7. In 1986 and 1987, there were a total of 58,525,000 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> flown under the category of general aviation. In order to relate these data to numbers of landings and takeoffs, it is necessary to make a judgment of the average flight duration. This is assumed to be 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Thus, the assumed total number of landings plus takeoffs is 11.7 x 107 for the years 1986 and 1987.

Of the general aviation accidents, only the fatal accidents are considered because in nonfatal accidents the pilot is assumed to have enough control to be able to avoid the plant. Some fatal accidents may also be of this type.

(b) (5)

TMI-1 UFSAR CHAPTER 02 2.4-7 REV. 18, APRIL 2006 The ranges of interest are 2 to 3 miles for Harrisburg International Airport traffic and 7 to 8 miles for Capital City traffic. From a smooth curve fitted to the data in Table 2.4-7, the respective numbers of accidents are 60 and 15 over the 2 year period for these two ranges.

For Harrisburg International Airport operations, the probability (PH) of there being a fatal crash within 2 to 3 miles is as follows for any landing or takeoff operation:

PH = 60 = 0.51 x 10-6/operation (11.7 x 107)

The projected number of landing plus takeoff operations at Harrisburg International Airport is 0.54 (124,700) = 67,300 per year. Thus, the probability of there being a fatal airplane crash within the 2 to 3 miles is:

0.51 x 10-6 x 67,300 = 0.34 x 10-1/year The average "virtual target" area assumed for the plant for landing and takeoff accidents is approximately 0.015 square miles. This is 0.95 x 10-3 times the area within the 2 and 3 mile circles.

Thus, assuming random geographical distribution of the crashes within the 2 to 3 mile radius, the probability that a fatal crash resulting from Harrisburg International Airport operations would strike the Three Mile Island plant in any one year is:

PH = 0.34 x 10-1 x 0.95 x 10-3 = 0.32 x 10-4/year Similarly, the probability (PC/C) of a strike by a fatal crash resulting from Capital City operations would strike the Three Mile Island plant in any one year is:

PC/C = 15 = 0.13 x 10-6/operation (11.7 x 107)

The projected number of landings plus takeoffs at Harrisburg/York is 0.46 (124,700) = 57,400 per year. Thus, the probability of there being a fatal crash between 7 and 8 miles of the airport is:

0.13 x 10-6 x 57,400 = 0.75 x 10-2/year The area between the 7 and 8 mile circles is 47.1 square miles so that the Three Mile Island plant occupies only 0.32 x 10-3 times this area. Thus, the probability that a fatal crash resulting from Harrisburg/York operations would strike the Three Mile Island plant in any one year is:

PC/C = 0.75 x 10-2 x 0.32 x 10-3 = 0.24 x 10-5/year The combined probability (P) of the Three Mile Island plant being hit by a fatal crash in any one year is then:

P = PH + PC/C = 0.32 x 10-4 + 0.24 x 10-5 = 3.4 x 10-5/year

TMI-1 UFSAR CHAPTER 02 2.4-8 REV. 18, APRIL 2006 The probabilities estimated above are based on the approximate number of general aviation operations in 1989. If general aviation operations in the Harrisburg area increase by a factor of 5 on the average, during life of the plant, and if the accident rates remain the same as assumed, the probability (P'S) would increase by a similar factor and would be about:

P'S = 2 x 10-4/year 2.4.2.5 Probability Of Fire From An Aircraft Strike a.

Small Fires As indicated in Table 2.4-7 for general aviation aircraft, about 32 percent of fatal crashes have postaccident fires. If this ratio is assumed valid for crashes on the plant, then the probability (P) of crash fires would be about:

P = 2 x 10-4 x 0.32 = 6.4 x 10-5/year This assumes that the general aviation movement rate is five times the 1989 rate.

Examination of Table 2.4-6 indicates these crashes will probably involve less than 400 gallons of fuel and average less than 100 gallons.

b.

Medium Fires Medium fires are taken to be those wherein more than 400 but less than 3000 gallons of fuel are involved. At the present time, about 57 percent of movements at Harrisburg International Airport involve airplanes with a maximum fuel capacity of 3000 gallons, or less. If, however, it is assumed that at the time air carrier movements reach 177,000 per year, 50 percent of the airplanes involved carry less than 3000 gallons when landing or taking off, then the probability (P) of a medium fire is:

P = 2.8 x 10-6 x 0.5 = 1.4 x 10-6/year assuming all air carrier crashes on the plant result in fires.

c.

Large Fires Similarly, the probability (P) of large fires (where more than 3000 gallons of fuel are involved) can be estimated assuming 50 percent of air carrier operations have more than 3000 gallons aboard when landing or departing. Thus:

P = 2.8 x 10-6 x 0.5 = 1.4 x 10-6/year Improvements in aircraft design, fire prevention systems, and fuel technology, especially for large aircraft, are expected to reduce the probability of postcrash fires in the future.

By the time air traffic movement rates reach those assumed in making the probability estimates above, significant improvements should be realized. Thus, from this viewpoint, the probability of postcrash fires, especially for large aircraft, should be less than assumed.

TMI-1 UFSAR CHAPTER 02 2.4-9 REV. 18, APRIL 2006 d.

Fuel or Fires Affecting Critical Ventilation Openings The probability of fire or fuel from a small airplane crash affecting the ventilation intake or outlet for the Control Room and other protected areas can be approximated by assuming that the "virtual target" is the area of the opening plus the area around it which could be hit and cause the opening to be subjected to fire or to liquid fuel or vapors at flammable concentrations. The openings are less than 400 ft2. For a small plane crash carrying an average of about 100 gallons of fuel, it is assumed the fuel-affected area could be about 10 ft x 50 ft or 500 ft2. This is believed to be a larger area than would be affected on the average.

The "virtual target" area assumed in deriving the probability for a small plane crash in Subsection 2.4.2.4 above is 0.015 miles2 or about 4 x 105 ft2, and the probability of a crash (at five times present traffic density) is 2 x 10-4/year. The probability (P) of a strike on the ventilation openings can be estimated by multiplying this probability by the ratio of "virtual target" areas or:

P = 2 x 10-4 x 500 = 2.5 x 10-7/Year 4 x 105 Ft2 This neglects the effect of protection afforded to the openings by structures which could intercept an approaching aircraft.

Consequently, the probability has been taken as being one half that estimated above or 1.3 x 10-7/year.

To estimate the probability contribution from large aircraft (air carrier planes), the average amount of fuel carried has been assumed to be 5000 gallons, assuming that only a very few, if any, very large planes (i.e., B747's) will use Harrisburg International Airport.

The area affected by spread of fuel from the crash of an aircraft carrying 5000 gallons is assumed to be about 25 ft x 1000 ft or 25,000 ft2.

The probability (P) for arriving and departing accidents is given as 2.8 x 10-6. If these are multiplied by the ratio of the "virtual target" area estimated above to the average virtual target area assumed in deriving the large plane strike probability, the result is an approximate estimate of the probability of fuel or fire from a large aircraft crash affecting critical ventilation openings. Thus, P = 2.8 x 10-6 x 2.5 x 104 = 1.8 x 10-7/year 4 x 105 This also neglects the effect of protection afforded the ventilation openings by structures which could intercept the approaching aircraft. Consequently, the probability is taken to be about one half that estimated above, or 9 x 10-8/year.

TMI-1 UFSAR CHAPTER 02 2.4-10 REV. 18, APRIL 2006 The combined probability (P) for large and small aircraft crashes affecting the ventilation opening is:

P = 2.2 x 10-7/year.

TMI-1 UFSAR CHAPTER 02 2.4-11 REV. 18, APRIL 2006 TABLE 2.4-1 (Sheet 1 of 1)

APPROXIMATE PROBABILITIES FOR AIRCRAFT CRASH EFFECTS ON THE THREE MILE ISLAND PLANT Approximate Approximate Mean Strike Recurrence Probability/yr1 Interval/yrs 1.

Large aircraft on plant (see Section 2.4.2.2) 2.8 x 10-6 3.6 x 105 2.

Large aircraft at high angle (

on surface of critical structures2 (see Section 2.4.2.3) 1.7 x 10-8 5.9 x 107 3.

Small aircraft on plant (see Section 2.4.2.4) 2 x 10-4 5 x 103 4.

Fire from an aircraft strike on the plant (see Section 2.4.2.5)

Small fires

(<400 gal. of fuel) 6.4 x 10-5 1.6 x 104 Medium fires (400-3000 gal of fuel) 1.4 x 10-6 7.1 x 105 Large fires

(>3000 gal of fuel) 1.4 x 10-6 7.1 x 105 Fuel or fire affecting critical ventilation openings3 2.2 x 107-7 4.5 x 106 1

In making these approximations of strike probability, the effect of overflights has been ignored. In a region of medium air traffic overflight density this probability may be in the range of 10-7/yr for light aircraft and 10-8/yr for large aircraft if the same type of assumptions are used as in devising the probabilities in this table.

2 Critical structures are those protected against strikes of large aircraft and against crash fires. They are discussed in Chapter 5 of the FSAR.

3 Critical ventilation openings are protected against the effects of fuel or fire. The probability represents the chance that fuel or fire will occur in the immediate vicinity of the openings.

(b) (5)

(b)

(5)

TMI-1 UFSAR CHAPTER 02 2.4-12 REV. 18, APRIL 2006 TABLE 2.4-2 (Sheet 1 of 1)

SUMMARY

OF U.S. AIR CARRIER ACCIDENTS (1,2)

YEAR TOTAL ACCIDENTS FATAL ACCIDENTS3 1978 22 5

1979 29 5

1980 19 1

1981 26 4

1982 20 5

1983 24 4

1984 17 1

1985 22 7

1986 24 3

1987 36 5

1 From "Annual Review Aircraft Accident Data, U.S. Air Carrier Operations, Calendar year 1987", National Transportation Safety Board, PB91-119693, NTSB/ARC-90/01 2 All 14CFR121, 125 and 127 operations.

3 Fatal accidents are those in which one or more human fatalities occurred.

TMI-1 UFSAR CHAPTER 02 2.4-13 REV. 18, APRIL 2006 TABLE 2.4-3 (Sheet 1 of 1)

FATAL ACCIDENTS IN THE PROXIMITY OF AIRPORTS1,2 (14CFR121, 125, 127 OPERATIONS)

NUMBER YEAR TOTAL ARRIVING DEPARTURE 1978 2

2 0

1979 3

1 2

1980 0

0 0

1981 0

0 0

1982 3

1 2

1983 1

1 0

1984 0

0 0

1985 4

2 2

1986 0

0 0

1987 2

1 1

15 8

7 1

Source: Aircraft Accident Briefs, National Transportation Safety Board, Department of Transportation.

2 Within a 5 mile radius of the end of the runway being estimated. National Transportation Safety Board started in 1982 compiling data for airport proximity based on the following three categories: on airport, on airstrip, and off airport/airstrip.

TMI-1 UFSAR CHAPTER 02 2.4-14 REV. 18, APRIL 2006 TABLE 2.4-4 (Sheet 1 of 1)

TYPES OF AIRCRAFT INVOLVED IN THE FATAL ACCIDENTS LISTED IN TABLE 2.4-31,2 YEAR AIRCRAFT 1978 B727, B727 1979 L188C, DHC6, DC10 1980 None 1981 None 1982 B737, DC10, B727 1983 Hawker HS748 1984 None 1985 L188A, L188C, L1011, DC9 1986 None 1987 B707, DC9 1

Source: Aircraft Accident Briefs, National Transportation Safety Board, Department of Transportation.

2 Within a 5 mile radius of the end of the runway being estimated. National Transportation Safety Board started in 1982 compiling data for airport proximity based on the following three categories: on airport, on airstrip, and off airport/airstrip.

TMI-1 UFSAR CHAPTER 02 2.4-15 REV. 18, APRIL 2006 TABLE 2.4-5 (Sheet 1 of 2)

CHARACTERISTICS OF TYPICAL AIR CARRIER AIRCRAFT1 TYPE MODEL WEIGHT2 DIMENSIONS Maximum Maximum Wing Length Takeoff Landing Span (Overall)

(lb)

(lb)

C-121 135,400 Conv.

580 58,140 52,000 105'4" 81'6" DC-9 30 98,000 93,400 93'5" 119'3-1/2" F-27 J

42,000 40,000 95'2" 77'2" B-707 331-C) 331,000 247,000 145'9" 162'11" 320-C) 331,000 Shorts 360 27,100 26,500 74'9-1/2" 70'9-5/8" 1 Others-Not Used at Harrisburg International But inOperation in U.S.

B-737 200 107,000 97,000 93' 100' B-727 200 169,000 148,000 108' 153'2" B-720 B

234,000 175,000 130'10" 136'9" B-707 120B 257,000 190,000 130'10" 145'1" C-130 E

155,000 130,000 132' 7" 97'9" Electra 128,000 91,300 99'8" 116'10" (185 Orion) 1 Other Planned for Operation in U.S.

DC-10 386,500

?

155'4" 179'8" B-747 680,000 564,000 195'8" 231'4" C5A (107-C) 764,500 635,850 222'8-1/2" 245'11 1 Unless otherwise noted, from Jane's All the World's Aircraft (1967-68 and 1990-91 editions).

2 Weight for heaviest model.

TMI-1 UFSAR CHAPTER 02 2.4-16 REV. 18, APRIL 2006 TABLE 2.4-5 (Sheet 2 of 2)

CHARACTERISTICS OF TYPICAL AIR CARRIER AIRCRAFT1 TYPE MODEL ENGINES FUEL SPEED PASSENGERS Number Gallons Cruise Stall Max. No.

(Max. No.

Flaps Down)

C-121 Conv.

580 2

2,800 50 DC-9 30 2

2,786 561 90 F-27 J

2 2,786 324 48 B-707 331-C) 4 23,855 600 100 202 320-C)

Shorts 360 2

576 216 --

36 1 Others-Not Used at Harrisburg International But In Operation in U.S.

B-737 200 2

4,670 600 100 113 B-727 200 3

7,680 592 115 189 B-720 B

4 14,880 557 100 116 B-707 120B 4

17,334 627 110 185 C-130 E

4 9,680 368 --

Electra 4

9,200 476 --

(185 Orion) 1 Others Planned for Operation in U.S.

DC-10 4

600 100 250 B-747 4

50,320 615 100 490 C5A (107-C) 4 49,000 577 1 Unless otherwise noted, from Jane's All the World's Aircraft, (1967-68 and 1990-91 editions).

TMI-1 UFSAR CHAPTER 02 2.4-17 REV. 18, APRIL 2006 TABLE 2.4-6 (Sheet 1 of 1)

TYPICAL GENERAL AVIATION AIRCRAFT CHARACTERISTICS1,2 Type Piper Beechcraft Cessna Model Cherokee Navajo Bonanza 99 150 421 (PA 28-180)

(V-35)

Weight, lb 2400 6200 3400 10,200 1600 6800 Engines-1 2

1 2

1 2

number Fuel 50 190 80 374 38 202 Gallons (max.)

Type gas jet gas jet gas jet Cruise Speed 152 224 210 250 123 238 Flaps down 57 77 63 48 87 stall speed 1 From Jane's All the World's Aircraft, (1967-1968 edition).

2 Includes Largest and Smallest of each Type.

TMI-1 UFSAR CHAPTER 02 2.4-18 REV. 18, APRIL 2006 TABLE 2.4-7 (Sheet 1 of 1)

GENERAL AVIATION TOTAL FATAL ACCIDENTS IN CONTINENTAL U.S.

(1956-1966 Inclusive)

Phase of Operation (Estimated Distance from Airport)*

(miles)

Fatal Accidents Standing, Taxi, Takeoff, Approach 311 or Landing (0-2)

Climb or Descent (2-5) 102 Maneuvering or Cruise (Beyond 5) 470 Other or not reported 44 Total 927 Fire after impact 296 Due to change in how General Aviation Accident Data is compiled, assumptions regarding estimated accident distance from airport were made to keep the methodology for this update consistent with the original FSAR.

TMI-1 UFSAR CHAPTER 02 2.5-1 REV. 18, APRIL 2006 2.5 METEOROLOGY 2.5.1 GENERAL General climatic conditions in the site region are characterized by a continental type climate, modified and protected somewhat from more severe weather by the Appalachian Mountain Ridge to the north. Summers tend to be warm and humid, and winters are cool, with frequent periods of precipitation. Severe weather conditions are discussed in Subsection 2.5.2.

An on site meteorological data collection program has been in operation since May 1967. Wind speed and direction have been continuously recorded 100 ft above grade elevation on Three Mile Island; and, 2.5 miles north, at the 25 ft above grade elevation at Crawford Station for a 2 year period of record ending May 1969. Identical data were analyzed to provide a basis for evaluation of routine gas release limits, as described in Subsection 2.5.3. Accident meteorology is described in Subsection 2.5.4. Tables 2.5-1A through 2.5-1D show histograms of the valid wind speed and direction data (an X represents a good data hour) for the Three Mile Island weather tower from May 1967 through May 1969.

Wind roses based on measured data (1967 through 1969) at the site and at Crawford Station are shown on Figures 2.5-1 and 2.5-2, respectively.

2.5.2 SEVERE WEATHER In more than 75 years of record at the Harrisburg-York Municipal Airport and 56 years of record at the Harrisburg International Airport, the highest and lowest temperatures recorded were 107 and

-22F, respectively. Maximum monthly rainfall was 18.55 inches, maximum 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> rainfall 12.55 inches, and maximum 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> snowfall 24.0 inches. Maximum annual snow accumulation was 81.3 inches.

During the 92 year period 1871 through 1963, 33 hurricane or tropical storm center paths passed within about 100 miles of the site. Most of these were in dissipation stages. The most severe was "Hazel," the center of which passed just west of Harrisburg on October 15, 1954. A peak gust of 80 mph was recorded at the Harrisburg-York Municipal Airport during the passage of Hazel.

In June 1972, Hurricane Agnes passed through causing severe flooding in Harrisburg, Middletown, and surrounding areas.

During the 52 year period from 1917 through June 1969, 22 tornados were reported within a 25 mile radius of the plant site (Reference 2). They are listed in Table 2.5-1. During this same period, four were reported within 10 miles and one within 5 miles of the site. Based on these observations, the probability of a tornado occurring within a 25 mile radius would be about 0.4 per year. However, during the 10 year period 1958 through 1968, the frequency was about 0.7 per year. The higher frequency in the later period probably reflects an improvement in observations rather than a real increase. A small tornado occurred on October 18, 1967, which caused minor damage in Londonderry Township, approximately 3 miles from the plant.

Based on studies by the Weather Bureau (Reference 3) wind speeds 30 ft above the site grade are expected to exceed 78 mph once in 100 years. As used here, wind speed is taken as the average speed during the passage of one linear mile of air past the wind instrument. Taking account of the relationship between maximum wind speeds and short term gusts (Reference 4)

TMI-1 UFSAR CHAPTER 02 2.5-2 REV. 18, APRIL 2006 it is not expected that gusts will exceed 103 mph at the site more than once in 100 years. The fastest mile wind during 27 years of records at Harrisburg was 68 mph from the west in March 1955.

2.5.3 ANNUAL AVERAGE ATMOSPHERIC DIFFUSION CONDITIONS Annual average atmospheric diffusion conditions at the site have been developed for use in determining routine gas release limits discussed in Chapter 11. Using 2 years of TMI site data (1967 through 1969), averaged values of X/Q for each direction sector were determined according to the following relationship:

1 X/Q Sector Average = 2.03 (1/x) (1/û) z{x+x'}

This is an integrated form of the Pasquill diffusion relationship (References 5 and 6) and assumes a ground level source at a virtual source distance x' upwind from the actual source to account for dilution vertically from the building wake.

The symbols have the following meaning:

x

= Distance from source (m) x'

= Virtual source distance (m)

X

= Average concentration at ground level in a given 22-1/2 degree sector (curies/m3)

Q

= Average release rate (curies/sec) 1

= Harmonic mean of the reciprocal of wind speed (sec/m)

û z(x+x') = Vertical diffusion coefficient (m),

evaluated at (x+x')

Using the site data to determine wind speed, atmospheric diffusion, and wind direction, values of X/Q were computed for each of 48 combinations of wind speed and diffusion categories.

These values were then time weighted and added in each of the 16 direction sectors to determine the average values. The wind speed (mph) categories were: 1 to 3, 4 to 7, 8 to 12, 13 to 18, 19 to 25, 26 to 32, 33 to 40, and 40+. The stability categories were A through F as discussed below. The type of diffusion condition was assumed to be a function of wind direction range using relationships suggested in Reference 7. It was assumed that the standard deviation of horizontal wind direction is related to Pasquill diffusion conditions as in the following table:

TMI-1 UFSAR CHAPTER 02 2.5-3 REV. 18, APRIL 2006 Measured Values of Wind Direction Range Divided by 6 Type of Diffusion Condition 0 to 3.67 F

3.67 to 7.5 E

7.5 to 12.5 D

12.5 to 17.5 C

17.5 to 22.5 B

Greater than 22.5 A

Values for the standard deviation of wind direction were determined by dividing the maximum wind direction range measured over a 1 hr period by a factor of 6, as suggested in Reference 7.

The values used for the vertical diffusion coefficient z were taken as a function of distance and diffusion condition as shown in Reference 6. The virtual source distances assumed for diffusion conditions A through F are 100, 100, 100, 300, 400, and 700 meters, respectively.

In evaluating the data, it was found that during periods of low wind speed (usually during nighttime), the wind was unsteady, resulting in large values of wind direction range. These highly variable wind direction measurements probably represent good lateral diffusion conditions (higher values of y); however, the vertical diffusion coefficient may not be conservatively represented. To account for this, any range values exceeding 120during the daytime with wind speeds less than 3 mph were given a value of 120corresponding to B type diffusion. For nighttime hours, any range values exceeding 75with wind speeds less than 3 mph were given a range value of 30corresponding to E type diffusion. Thus, the valley inversion condition which might be expected to occur under these conditions is conservatively taken into account.

Calm conditions were assumed to have the same diffusion (X/Q) and direction value as the next noncalm hour of data.

Using methods described above, isopleths of average annual (X/Q) were derived. They are shown with respect to the local area around the site on Figure 2.5-3. The nearest uncontrolled land area would have an estimated ground level average annual dispersion factor (X/Q) of about 4.5 x 10-6.

Figure 2.5-7 shows an isopleth of average annual X/Q based on the methods described above except that delta-T from the north tower and the AEC Safety Guide 23 diffusion categories were used to determine z. The data were from the 1 yr period April 1971 through March 1972.

Based on this figure, the nearest uncontrolled land area would have an estimated dispersion factor (X/Q) of about 7.5 x 10-6 sec/m3.

Summary tables of the reduced data, corrected as discussed above for unsteady conditions, used in this analysis are shown in Tables 2.5-8 through 2.5-13. The measured data are given

TMI-1 UFSAR CHAPTER 02 2.5-4 REV. 18, APRIL 2006 in Tables 2.5-2 through 2.5-7. The number of calms and time of day during which they occurred are given in Table 2.5-14.

2.5.4 ACCIDENT METEOROLOGY Accident atmospheric dispersion coefficients (X/Q) have been determined at the Exclusion Area Boundary (EAB), Low Population Zone (LPZ), and various locations of potential contaminant entrance into the Control Room to provide a basis for assessing radiation exposure during accidents described in Chapter 14. Hourly site meteorological data for the years 1992, 1993, 1995, and 1996 were used to determine the dispersion coefficients. The data included wind speed and wind direction collected at the 100-Ft. instrument level and vertical temperature difference determined from the 150-Ft. and 33-Ft. instrument levels. The combined data recovery of speed, direction and delta temperature is indicated below:

Year Combined Percent Recovery 1992 99.3 1993 99.3 1995 99.2 1996 98.9 2.5.4.1 EAB and LPZ Dispersion Coefficients Atmospheric dispersion coefficients for the EAB and LPZ were determined utilizing the methodology described in NRC Regulatory Guide 1.145 Revision 1. The analysis (Ref. 32) was performed using the proprietary WINDOW computer code of PLG Inc. and the meteorological data described above. The analysis assumed the total of all releases as ground level releases from point sources at the containment building surface. The effects of building wake and plume meander were evaluated for these releases per R.G. 1.145. Distances to the EAB were determined in accordance with the methods of R.G. 1.145 for each of the 16 direction sectors.

The distance measurements excluded the containment radius in each of the sixteen directions.

The LPZ distance consisted of a 2-mile radius circle (3218 meters) centered on the containment building.

Wind speed measurements taken at the 100-Ft. instrument level were corrected to 33-Ft. level (10 meters) for use with the R.G. 1.145 equations. The correction was made using the following relation:

U33Ft = U100Ft (h33Ft / h100Ft) n U - wind speed h - height n - exponent as function of stability n =

0.25 for Pasquill Stability Classes A, B and C n =

0.33 for Pasquill Stability Class D n =

0.50 for Pasquill Stability Classes E, F and G The Pasquill diffusion class was determined using vertical temperature difference and the categories given in NRC Regulatory Guide 1.23. Values of y and z were determined as a

TMI-1 UFSAR CHAPTER 02 2.5-5 REV. 18, APRIL 2006 function of distance and stability class using the standard Pasquill - Gifford curves contained in Figures 1 and 2 of R.G. 1.145.

Cumulative probability distributions were determined in each of the 16 directions using the direction dependent method for the EAB and LPZ distances and the 4-year hourly data. An envelope was constructed around the 16 direction dependent curves to determine the sector with the maximum 0.5% probable value (i.e. the value exceeded no more than 0.5% of the time). An additional cumulative probability distribution was determined for both the EAB and LPZ using the direction independent method for all of the data. The two methods were compared as required by R.G. 1.145 to determine the higher X/Q value. The direction dependent method yielded higher X/Q values for the EAB and LPZ.

The results of the analysis yield the following X/Q values for the time intervals of interest.

EAB Interval (Hours)

X/Q (sec/m3) 0-2 8.0E-04 LPZ Interval X/Q (sec/m3) 0-2 Hours 1.4E-04 2-8 Hours 6.0E-05 8-24 Hours 3.9E-05 1-4 Days 1.6E-05 4-30 Days 4.0E-06 2.5.4.2 Control Room Dispersion Coefficients The site geometry for structures and ventilation intakes relative to the various release locations and potential contaminant entrance pathways into the control room establish several site-specific pathways for the determination of atmospheric dispersion coefficients. These have included releases to the designed control building ventilation system intake (Yard Intake). Yard Intake scenarios evaluate dose release points from the Reactor Building (general location), Unit Vent, Personnel Hatch, Equipment Hatch, and Equipment Airlock. In addition, releases from the containment building to the ventilation exhaust, releases from the auxiliary building to the yard intake, and releases from the borated water storage tank (BWST) vent to the yard intake are evaluated. The methodology for determining the dispersion coefficients is varied and dependent upon the type of release, its relative distance to the intake locations, and the meteorological conditions. The meteorological data described above was used for these analyses. Each release pathway and the methodology used for the determination of the dispersion coefficients are described below.

2.5.4.2.1 Containment Release to Yard Intake The atmospheric dispersion coefficients for a containment release to the control building ventilation system via the yard intake have been determined using the diffuse leak approach of the ARCON96 computer code. This approach transforms the diffuse release into a virtual point source located upstream of the containment structure. The analysis (Ref. 33) utilizes the NRC recommended 3-sigma approach for conservatively estimating initial diffusion coefficients required by the code for establishing the virtual source distance. The shortest distance

TMI-1 UFSAR CHAPTER 02 2.5-6 REV. 18, APRIL 2006 between the containment building surface and the yard intake was used as input to the analysis. Release from the containment building was assumed to be ground level.

The results of the analysis are indicated below:

Containment to Yard Pathway Interval X/Q (sec/m3) 0-2 Hours 3.40E-04 2-8 Hours 2.25E-04 8-24 Hours 1.02E-04 1-4 Days 7.61E-05 4-30 Days 4.99E-05 Additional 95% confidence atmosphere dispersion coefficients for the fuel handling accident in the containment involving release through containment venting or open hatches to the control building ventilation system via the yard intake have also been determined using the ARCON96 computer code (Reference 36). These releases can be from the unit vent, personnel hatch, equipment hatch, or emergency air lock with the bounding of these being from the unit vent.

Worst-Case Fuel Handling Accident in Containment to Yard Pathway Interval X/Q (sec/m3) 0-2 Hours 5.34E-04 2-8 Hours 3.10E-04 8-24 Hours 1.36E-04 1-4 Days 9.70E-05 4-30 Days 6.02E-05 2.5.4.2.2 Containment Release to Ventilation Exhaust The control building ventilation exhaust point normally discharges ventilation system exhaust from the control building to the environment. During postulated failure conditions this discharge point has been determined to be a source of contaminant entrance into the control building ventilation system. To assess the consequences of this point as a contaminant entry location it was necessary to determine a dispersion coefficient for a release from the containment structure to the ventilation exhaust opening.

The analysis (Ref. 34) utilized data sources from wind tunnel experiments to provide a conservative estimate of X/Q values. This method was used in lieu of the ARCON96 or Murphy-Campe methods because of the short distance that exists between the nearest containment release point and entrance to the ventilation exhaust. Both the ARCON96 and Murphy-Campe methods are unsuitable for this short distance and unique arrangement.

The TMI-model evaluates selective release points on the containment surfaces exposed to the environment. A fractional release is determined for each release point representative of a release area. Experimental surface concentration coefficients for buildings are used to determine X/Q. The concentration coefficient, K, is equal to (X/Q) Au, where A is the blockage area and u is wind speed. From a known blockage area associated with wind direction and speed, the sector (X/Q) u value is determined. Using the above hourly meteorological data hourly X/Qs are calculated and the applicable 95th, 90th, 80th, and 60th percentile values are determined. The resulting X/Q values at the respective intervals are as follows:

TMI-1 UFSAR CHAPTER 02 2.5-7 REV. 18, APRIL 2006 Containment to Ventilation Exhaust Pathway Interval X/Q (sec/m3) 0-2 Hours 1.96E-03 2-8 Hours 1.96E-03 8-24 Hours 1.37E-03 1-4 Days 9.14E-04 4-30 Days 5.09E-04 2.5.4.2.3 Auxiliary Building Release to Yard Intake The auxiliary building houses engineered safeguards equipment that has the potential to release contaminants to the building and environment. To assess the radiological impact of any potential releases from the auxiliary building upon the control room, it was necessary to determine an atmospheric dispersion coefficient for this type of release.

The dispersion coefficients were determined using the ARCON96 computer code and a point source release approach. The analysis (Ref. 32) assumed a ground level release from the nearest point of the auxiliary building to the yard intake. The model neglected the enhanced dispersion effects produced by adjacent structures. The resulting X/Q values were determined at the respective intervals of interest:

Auxiliary Building Release Pathway Interval X/Q (sec/m3) 0-2 Hours 3.02E-03 2-8 Hours 2.08E-03 8-24 Hours 1.02E-03 1-4 Days 6.63E-04 4-30 Days 4.37E-04 2.5.4.2.4 Borated Water Storage Tank (BWST) Release to Yard Intake Engineered safeguards equipment interfaces with the BWST and has the potential to release contaminants to the environment through the tanks vent. An atmospheric dispersion coefficient has been determined for this type of release to assess the radiological impact on the control room.

The model (Ref. 32) utilizes the ARCON96 code to determine the dispersion coefficient from the BWST to the yard intake. The release is assumed to be a vent type release from the tanks vent and is considered a point source in accordance with the ARCON96 methodology. The effects of adjacent structures on the dispersion were neglected for this analysis. The results of the analysis are indicated below:

TMI-1 UFSAR CHAPTER 02 2.5-8 REV. 18, APRIL 2006 BWST Release Pathway Interval X/Q (sec/m3) 0-2 Hours 8.45E-04 2-8 Hours 5.23E-04 8-24 Hours 2.49E-04 1-4 Days 1.77E-04 4-30 Days 1.19E-04 2.5.5 Deleted 2.5.6 Deleted

TMI-1 UFSAR CHAPTER 02 2.5-9 REV. 18, APRIL 2006 TABLE 2.5-1 (Sheet 1 of 1)

TORNADOS WITHIN 25 MILES OF THREE MILE ISLAND1 Date Time Location Approx.

Direction of (Closest approach Path Length Movement to site,miles) 11-17-1918 11:30 PM N of Harrisburg(10+)

?

?

6-15-1926 3:00 PM Paradise, Lancaster Co. (25) 2.5 Miles S

4-25-1929 8:00 PM Center of York Co. (12)

?

?

6-12-1938 2:30 PM W. Central Dauphin Co. (15) 10 Miles SE 7-15-1938 3:45 AM Southern York Co.(15) 12-13 Miles NNE 8-13-1944 2:15 PM Central York Co. (14) 8 Miles NE 5-22-1949

?

N. Harrisburg (9) 8 Miles ENE 4-5 -1952 1:15 PM Steelton (14) 3 Miles NNE 4-5 -1952 l:15 PM Wrightsville York Co.(10) 4 Miles NNE 4-5-1952 1:45 PM C. of Lancaster (19) 3 Miles NNE 11-23-1953 2:00 AM Landisville, Lancaster Co. (15) 3 Miles NE 6-13-1956 7:45 PM Central York Co. (14) 4 Miles E

4-28-1957 8:00 PM Central Lancaster Co. (25) ?

?

8-21-1957 2:30 PM Harrisburg (1)

?

?

11-19-1957 2:30 PM West-Central Lebanon Co(15) 2 Miles NE 5-26-1961

?

Central Lancaster Co. (25) ?

?

7-29-1961 3:00 AM Central York Co. (16) 19 Miles ENE

?-1963

?

North-Central York Co.(7) 13 Miles ENE

?-1964

?

Central Lebanon Co. (21)

?

?

8-26-1965

?

Northern York Co. (12)

?

?

9-21-1967 6:00 PM Perry County (25)

Short

?

10-18-1967 Morning Dauphin County (3) 15 Miles 1 For Period 1917 - June 1969

TMI-1 UFSAR CHAPTER 02 2.5-10 REV. 18, APRIL 2006 TABLE 2.5-2 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group A (Measured Data)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E ESE SE SSE 1 - 3 31 4

6 17 25 33 67 65 4 - 7 9

2 7

0 5

10 13 19 8 -12 10 2

0 0

2 3

1 8

13-18 6

4 0

0 0

0 1

2 19-25 1

1 1

0 0

0 0

0 26-32 0

0 0

0 0

0 0

0 33-40 0

0 0

0 0

0 0

0 40+

0 0

0 0

0 0

1 1

Totals 57 12 14 17 32 46 83 95

TMI-1 UFSAR CHAPTER 02 2.5-11 REV. 18, APRIL 2006 TABLE 2.5-2 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group A (Measured Data)

Wind Speed Wind Direction Sector mph)

S SSW SW WSW W WNW NW NNW TOTALS 1 - 3 60 69 68 48 71 51 65 37 717 4 - 7 24 17 20 15 34 35 55 40 305 8 -12 7

9 10 4

7 13 13 13 102 13-18 2

1 1

0 4

5 10 2 38 19-25 0

0 1

1 0

1 3 0 8

26-32 0

1 0

0 0

0 2 0 3

33-40 0

0 0

0 0

0 0 0 0

40+

1 0

0 0

0 0

0 0 3

Totals 94 97 100 68 116 105 148 92 1176

TMI-1 UFSAR CHAPTER 02 2.5-12 REV. 18, APRIL 2006 TABLE 2.5-3 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group B (Measured Data)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E

ESE SE SSE 1 - 3 14 6 2 11 23 30 37 41 4 - 7 4 0 0 2

11 20 20 16 8 -12 2 0 0 1

0 3

3 7

13-18 1 0 0 0

0 0

3 1

19-25 0 0 0 0

0 0

0 1

26-32 0 0 0 0

0 0

0 0

33-40 0 0 0 0

0 0

0 0

40+ 0 0 1 0

0 0

0 0

Totals 21 6 3 14 34 53 63 66

TMI-1 UFSAR CHAPTER 02 2.5-13 REV. 18, APRIL 2006 TABLE 2.5-3 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group B (Measured Data)

Wind Speed Wind Direction Sector mph)

S SSW SW WSW W

WNW NE NNW Totals 1 - 3 36 25 25 36 29 31 25 25 396 4 - 7 28 23 19 14 35 31 32 10 265 8 -12 9 5 12 18 16 23 15 8 122 13-18 2 5 2 4

4 8

2 2 34 19-25 0 1 0 0

1 2

1 1 7

26-32 0 0 0 0

0 0

0 0 0

33-40 0 0 0 0

0 0

0 0 0

40+ 0 0 0 0

0 0

0 0 0

Totals 75 59 58 72 85 95 75 46 825

TMI-1 UFSAR CHAPTER 02 2.5-14 REV. 18, APRIL 2006 TABLE 2.5-4 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group C (Measured Data)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E

ESE SE SSE 1 - 3 36 8

6 41 63 37 50 44 4 - 7 17 1

2 15 33 47 42 46 8 -12 13 1

0 3

10 19 10 16 13-18 0

0 0

2 2

7 3

4 19-25 0

0 0

0 0

0 1

1 26-32 0

0 0

0 0

0 0

0 33-40 0

0 0

0 0

0 0

0 40+

0 0 0 0 0

0 0

0 Totals 66 10 8

61 108 110 106 111

TMI-1 UFSAR CHAPTER 02 2.5-15 REV. 18, APRIL 2006 TABLE 2.5-4 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group C (Measured Data)

Wind Speed Wind Direction Sector mph)

S SSW SW WSW W WNW NW NNW Totals_

1 - 3 55 48 64 36 34 34 37 48 641 4 - 7 47 49 56 52 62 71 44 55 639 8 - 12 20 18 32 39 58 78 47 36 400 13-18 9 5 10 20 49 40 8 5 164 19-25 1 0 3 4 9 6 5 2

32 26-32 0 0 0 0 0 1 1 0

2 33-40 0 0 0 0 0 0 0 0

0 40+ 0 0 0 0 0 1 0 0

1 Totals 132 120 165 151 212 231 142 146 1879

TMI-1 UFSAR CHAPTER 02 2.5-16 REV. 18, APRIL 2006 TABLE 2.5-5 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group D (Measured Data)

Wind Speed Wind Direction Sector _____________

mph)

N NNE NE ENE E

ESE SE SSE 1 - 3 70 34 32 93 52 44 62 63 4 - 7 76 19 6

65 79 90 70 82 8 -12 55 4

3 16 47 42 51 41 13-18 17 4

0 3

9 13 17 15 19-25 9

1 0

0 5

3 0

2 26-32 0

0 0

0 0

0 0

0 33-40 0

0 0

0 0

0 0

0 40+

0 0

0 0

0 0

0 0

Total 227 62 41 177 192 192 200 203

TMI-1 UFSAR CHAPTER 02 2.5-17 REV. 18, APRIL 2006 TABLE 2.5-5 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group D (Measured Data)

Wind Speed Wind Direction Sector _____________

(mph)

S SSW SW WSW W

WNW NW NNW Totals 1 - 3 63 65 57 46 43 36 34 44 838 4 - 7 78 73 73 52 130 82 78 70 1123 8 -12 30 38 42 53 115 121 106 86 850 13-18 10 14 10 32 110 126 95 34 509 19-25 0

0 1

7 24 54 35 13 154 26-32 0

0 0

1 2

4 11 0

18 33-40 0

0 0

0 0

1 1

0 2

40+

0 0

0 0

0 0

0 0

0 Totals 181 190 183 191 424 424 360 247 3494

TMI-1 UFSAR CHAPTER 02 2.5-18 REV. 18, APRIL 2006 TABLE 2.5-6 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group E (Measured Data)

Wind Speed Wind Direction Sector _

mph)

N NNE NE ENE E

ESE SE SSE 1 - 3 29 82 86 59 31 22 29 32 4 - 7 78 99 53 106 58 39 55 70 8 -12 64 28 14 24 22 35 33 36 13-18 32 7

4 4

8 6

15 18 19-25 19 1

0 0

3 0

0 3

26-32 0

0 0

0 0

0 0

0 33-40 0

0 0

0 0

0 0

0 40+

0 0

0 0

0 0

0 0

Totals 222 217 157 193 122 102 132 159

TMI-1 UFSAR CHAPTER 02 2.5-19 REV. 18, APRIL 2006 TABLE 2.5-6 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group E (Measured Data)

Wind Speed Wind Direction Sector (mph)

S SSW SW WSW W

WNW NW NNW Totals 1 - 3 73 30 17 16 9

27 25 18 585 4 - 7 57 66 29 28 65 72 72 57 1004 8 -12 43 35 11 9

77 156 102 59 748 13-18 12 6

5 9

48 175 116 39 504 19-25 0

1 3

2 19 64 54 11 180 26-32 0

0 0

0 0

9 9

0 18 33-40 0

0 0

0 0

0 1

0 1

40+

0 0

0 0

0 0

0 0

0 Totals 185 38 65 64 218 503 379 184 3040

TMI-1 UFSAR CHAPTER 02 2.5-20 REV. 18, APRIL 2006 TABLE 2.5-7 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group F (Measured Data)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E

ESE SE SSE__

1 - 3 7

8 39 4

2 4

10 7

4 - 7 22 32 42 11 8

7 19 12 8 -12 10 16 19 2

1 2

3 8

13-18 6

4 4

0 0

5 3

3 19-25 0

1 0

0 0

0 0

1 26-32 0

0 0

0 0

0 0

0 33-40 0

0 0

0 0

0 0

0 40+

0 0

0 0

0 0

0 0

Totals 45 61 104 17 11 18 35 31

TMI-1 UFSAR CHAPTER 02 2.5-21 REV. 18, APRIL 2006 TABLE 2.5-7 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group F (Measured Data)

Wind Speed Wind Direction Sector _____

(mph)

S SSW SW WSW W

WNW NW NNW Totals 1 - 3 25 3

4 2 1 3 1 4 124 4 -7 20 5

3 3

11 17 11 12 235 8 -12 5

4 3

2 14 34 5 7 135 13-18 0

0 0

0 6 27 4 7 69 19-25 0

0 0

0 2 4 3 1 12 26-32 0

1 0

0 1 0 0 0 2

33-40 0

0 0

0 0 0 0 0 0

40+

0 0

0 0

0 0 0 0 0

Totals 50 13 10 7

35 85 24 31 577

TMI-1 UFSAR CHAPTER 02 2.5-22 REV. 18, APRIL 2006 TABLE 2.5-8 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group A (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E

ESE SE SSE 1 - 3 16 1 1

5 5

7 18 28 4 - 7 9 2 7

0 5

10 13 19 8 -12 10 2 0 0

2 3

1 8

13-18 6 4 0 0

0 0

1 2

19-25 1 0 1

0 0

0 0

0 26-32 0 0 0

0 0

0 0

0 33-40 0 0 0 0

0 0

0 0

40+ 0 0 0 0

0 0

1 1

Totals 42 9 9 5

12 20 34 58

TMI-1 UFSAR CHAPTER 02 2.5-23 REV. 18, APRIL 2006 TABLE 2.5-8 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group A (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector (mph)

S SSW SW WSW W WNW NW NNW Totals 1 - 3 21 14 18 12 31 21 31 27 256 4 - 7 24 17 20 15 34 35 55 40 305 8 -12 7 9 10 4

7 13 13 13 102 13-18 2 1 1 0

4 5 10 2 38 19-25 0 0 1

1 0

1 3 0 8

26-32 0 1 0

0 0

0 2 0 3 33-40 0 0 0

0 0

0 0 0 0 40+ 1 0 0 0

0 0 0 0 3

Totals 55 42 50 32 76 75 114 82 715

TMI-1 UFSAR CHAPTER 02 2.5-24 REV. 18, APRIL 2006 TABLE 2.5-9 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group B (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E ESE SE SSE 1 - 3 14 5

4 13 23 35 37 35 4 - 7 4

0 0

2 11 20 20 16 8 -12 2

0 0

1 0

3 3

7 13-18 1

0 0

0 0

0 3

1 19-25 0

0 0

0 0

0 0

1 26-32 0

0 0

0 0

0 0

0 33-40 0

0 0

0 0

0 0

0 40+

0 0

1 0

0 0

0 0

Totals 21 5

5 16 34 58 63 60

TMI-1 UFSAR CHAPTER 02 2.5-25 REV. 18, APRIL 2006 TABLE 2.5-9 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group B (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector (mph)

S SSW SW WSW W

WNW NW NNW Totals 1 - 3 33 37 36 37 39 19 30 18 415 4 - 7 28 23 19 14 35 31 32 10 265 8 -12 9

5 12 18 16 23 15 8 122 13-18 2

5 2

4 4 8 2 2 34 19-25 0

1 0

0 1 2 1 1 7

26-32 0

0 0

0 0 0 0 0 0

33-40 0

0 0

0 0 0 0 0 0

40+

0 0

0 0

0 0 0 0 1

Totals 72 71 69 73 95 83 80 39 844

TMI-1 UFSAR CHAPTER 02 2.5-26 REV. 18, APRIL 2006 TABLE 2.5-10 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group C (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E

ESE SE SSE 1 - 3 23 4 2 29 41 21 31 30 4 - 7 17 1 2 15 33 47 42 46 8 -12 13 1 0 3

10 19 10 16 13-18 0 0 0 2

2 7

3 4

19-25 0 0 0 0

0 0

1 1

26-32 0 0 0 0

0 0

0 0

33-40 0 0 0 0

0 0

0 0

40+ 0 0 0 0

0 0

0 0

Totals 53 6 4 49 86 94 87 97

TMI-1 UFSAR CHAPTER 02 2.5-27 REV. 18, APRIL 2006 TABLE 2.5-10 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group C (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector (mph)

S SSW SW WSW W

WNW NW NNW Totals 1 - 3 26 32 46 24 21 19 22 28 399 4 - 7 47 49 56 52 62 71 44 55 639 8 -12 20 18 32 39 58 78 47 34 398 13-18 9

5 10 20 49 40 8 5

164 19-25 1

0 3

4 9 6 5 2

32 26-32 0

0 0

0 0 1 1 0

2 33-40 0

0 0

0 0 0 0 0

0 40+

0 0

0 0

0 1 0 0

1 Totals 103 104 147 139 199 216 127 124 1635

TMI-1 UFSAR CHAPTER 02 2.5-28 REV. 18, APRIL 2006 TABLE 2.5-11 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group D (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E

ESE SE SSE 1 - 3 70 34 32 93 52 44 62 63 4 - 7 76 19 6 65 79 90 70 82 8 -12 55 4 3 16 48 43 51 41 13-18 17 4 0 3 9 13 17 15 19-25 9 1 0 0 5 3

0 2

26-32 0 0 0 0 0 0 0

0 33-40 0 0 0 0 0 0

0 0

40+ 0 0 0 0 0 0

0 0

Totals 227 62 41 177 193 193 200 203

TMI-1 UFSAR CHAPTER 02 2.5-29 REV. 18, APRIL 2006 TABLE 2.5-11 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group D (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector (mph)

S SSW SW WSW W WNW NW NNW Totals 1 - 3 63 65 57 46 43 36 34 44 838 4 - 7 78 73 73 52 130 82 78 70 1123 8 -12 30 38 42 53 115 121 106 86 852 13-18 10 14 10 32 110 126 95 34 509 19-25 0

0 1

7 24 54 35 13 154 26-32 0

0 0

1 2

5 11 0

19 33-40 0

0 0

0 0

1 1

0 2

40+

0 0

0 0

0 0

0 0

0 Totals 181 190 183 191 424 425 360 247 3497

TMI-1 UFSAR CHAPTER 02 2.5-30 REV. 18, APRIL 2006 TABLE 2.5-12 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group E (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E ESE SE SSE 1 - 3 57 90 93 81 73 59 97 91 4 - 7 78 99 53 106 58 39 54 70 8 -12 64 28 14 24 22 35 33 36 13-18 32 7 4 4 8 6

15 18 19-25 19 1 0 0 3 0

0 3

26-32 0 0 0 0 0 0 0 0

33-40 0 0 0 0 0 0 0 0

40+ 0 0 0 0 0 0

0 0

Totals 250 225 164 215 164 139 199 218

TMI-1 UFSAR CHAPTER 02 2.5-31 REV. 18, APRIL 2006 TABLE 2.5-12 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group E (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector (mph)

S SSW SW WSW W WNW NW NNW Totals 1 - 3 144 89 74 63 52 84 69 55 1271 4 - 7 57 66 29 28 65 72 72 57 1003 8 -12 43 35 11 9

77 156 102 59 748 13-18 12 6

5 9

48 175 116 39 504 19-25 0

1 3

2 19 64 54 11 80 26-32 0

0 0

0 0

9 9

0 18 33-40 0

0 0

0 0

0 1

0 1

40+

0 0

0 0

0 0

0 0

0 Totals 256 197 122 111 261 560 423 221 3725

TMI-1 UFSAR CHAPTER 02 2.5-32 REV. 18, APRIL 2006 TABLE 2.5-13 (Sheet 1 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group F (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector mph)

N NNE NE ENE E

ESE SE SSE 1 - 3 7

8 39 4

2 4

10 7

4 - 7 22 32 42 11 8

7 19 12 8 -12 10 16 19 2

1 2

3 8

13-18 6

4 4

0 0

5 3

3 19-25 0

1 0

0 0

0 0

1 26-32 0

0 0

0 0

0 0

0 33-40 0

0 0

0 0

0 0

0 40+

0 0

0 0

0 0

0 0

Totals 45 61 104 17 11 18 35 31

TMI-1 UFSAR CHAPTER 02 2.5-33 REV. 18, APRIL 2006 TABLE 2.5-13 (Sheet 2 of 2)

WIND VELOCITY DISTRIBUTION VS PASQUILL DIFFUSION GROUP Three Mile Island Tower (5/15/67 - 5/14/69)

Diffusion Group F (Corrected for Unsteady Conditions)

Wind Speed Wind Direction Sector (mph)

S SSW SW WSW W WNW NW NNW Totals 1 - 3 25 3

4 2

1 3

1 4

124 4 - 7 20 5

3 3

11 17 11 12 235 8 -12 5

4 3

2 14 34 5

7 135 13-18 0

0 0

0 6

27 4

7 69 19-25 0

0 0

0 2

4 3

1 12 26-32 0

0 1

0 0

1 0

0 2

33-40 0

0 0

0 0

0 0

0 0

40+

0 0

0 0

0 0

0 0

0 Totals 50 12 11 7

34 86 24 31 577

TMI-1 UFSAR CHAPTER 02 2.5-34 REV. 18, APRIL 2006 TABLE 2.5-14 (Sheet 1 of 1)

NUMBER OF CALMS VS TIME OF DAY1 Hour of the Day TOTAL 1 AM 30 2

27 3

28 4

42 5

40 6

42 7

47 8

25 9

12 10 5

11 2

12 0

l PM 2

2 6

3 2

4 3

5 3

6 6

7 9

8 18 9

25 10 25 11 29 12 21 449 NOTES:

1 Three Mile Island Met Tower-Period of Record 5/67-4/69

TMI-1 UFSAR CHAPTER 02 2.5-35 REV. 18, APRIL 2006 TABLE 2.5-15 DELETED

TMI-1 UFSAR CHAPTER 02 2.5-36 REV. 18, APRIL 2006 TABLE 2.5-16 DELETED

TMI-1 UFSAR CHAPTER 02 2.5-37 REV. 18, APRIL 2006 TABLE 2.5-17 DELETED

TMI-1 UFSAR CHAPTER 02 2.5-38 REV. 18, APRIL 2006 TABLE 2.5-18 DELETED

TMI-1 UFSAR CHAPTER 02 2.5-39 REV. 18, APRIL 2006 TABLE 2.5-19 DELETED

TMI-1 UFSAR CHAPTER 02 2.5-40 REV. 18, APRIL 2006 TABLE 2.5-20 DELETED

TMI-1 UFSAR CHAPTER 02 2.6-1 REV. 22, APRIL 2014 2.6 HYDROLOGY 2.6.1 CHARACTERISTICS OF STREAMS IN VICINITY The major stream affecting the site is the Susquehanna River, having a drainage area at the site of approximately 25,000 square miles. The Susquehanna has a total drainage area of 27,400 square miles, of which 21,000 lie within the State of Pennsylvania. This constitutes approximately 46 percent of the total area of the state, embracing all of 21 and a portion of 22 other counties. Approximately 6200 square miles of the drainage area is in New York State and 200 square miles in western Maryland.

The drainage basin lies in the three main topographic divisions of Pennsylvania: The northern portion of the Allegheny Plateau, the central portion of the Allegheny Mountains, and the lower portion of the rolling Piedmont Plateau.

The main tributaries in the vicinity of the site are the following:

Stream Drainage Area Average Flow Conodoguinet Creek 506 sq.mi 1.20 cfsm Yellow Breeches Creek 219 sq.mi 1.26 cfsm Swatara Creek 571 sq.mi 1.66 cfsm Conewago Creek (East) 52 sq.mi West Conewago Creek 515 sq.mi 1.10 cfsm The Juniata River enters the Susquehanna River about 25 miles upstream from the site. Its drainage area is about 3404 square miles and its average flow is 1.26 cfsm.

The plant site on Three Mile Island is located approximately 11 river miles downstream from Harrisburg gauging station, which has a continuous period of record since 1890. The drainage area of the Susquehanna River at the Harrisburg gauge is 24,100 square miles. The average river flow per square mile at Harrisburg is 1.42 cfsm. The data for the Harrisburg gauge are assumed to be applicable to the site. Table 2.6-6 is the stage discharge table for the Susquehanna River at the TMINS intake structures.

The Susquehanna River is rather extreme in its flow characteristics, as is evident in the following summary of recorded data at Harrisburg:

Minimum daily flow 1,700 cfs Average annual discharge 34,000 cfs Average runoff per square mile 1.41 cfsm Mean annual flood 300,000 cfs Maximum flood of record (1972) 1,020,000 cfs The present uses of the streams in the vicinity are for water supply, both public and industrial, power generation, boating, fishing, and recreation. Sport fishing is done in all streams in the general area of the site. Commercial fishing is not practiced in the area.

Figure 2.6-1 shows the location of lakes and reservoirs within a 50 mile radius of the site. Table 2.6-1 lists all known data for these lakes and reservoirs.

TMI-1 UFSAR CHAPTER 02 2.6-2 REV. 22, APRIL 2014 Figure 2.6-2 shows the location of major water supplies within a 20 mile radius of the site which take water from streams in the vicinity or from wells. Table 2.6-2 lists all known data for these water supply systems.

2.6.2 STREAM USERS 2.6.2.1 Upstream Users No large dams or reservoirs exist immediately upstream from the site. A hydroelectric dam and reservoir on the Susquehanna River in Harrisburg are proposed as discussed in Section 2.6.2.2. The Army Corps of Engineers (ACOE) has constructed the Raystown Lake dam and reservoir project for flood control, low flow augmentation, and recreation, on the Raystown Branch of the Juniata River. Hydraulic studies performed by the Corps indicate that Three Mile Island is too far from the Raystown project for a failure of the dam to pose any threat to the site, even under worst case scenarios. Raystown Dam is an earth and rockfill dam with a maximum height of 230 ft. Raystown Lake has a volume of 762,000 acre-feet at full flood control pool.

In 1986, the ACOE performed hydraulic studies to evaluate the impact of a hypothetical dam failure as part of the emergency plan for Raystown Lake (Reference 26) under several scenarios. Based on the results of the studies, the ACOE concluded that Hazardous Conditions as a result of a Raystown Dam failure would not extend downstream of Harrisburg International Airport on the Susquehanna River, which is 115 miles downstream of Raystown dam and 2 miles upstream of TMINS. Hazardous Conditions are defined as flood depths exceeding 2 ft and velocities exceeding 4 ft per second. It is therefore evident that a failure of Raystown Dam during normal Susquehanna River flow conditions or relatively frequent floods would not top the TMINS dike. If failure of the Raystown Dam (at normal high pool or during the Spillway Design Flood) were to coincide with a major flood in the Susquehanna River river flow at TMINS could be increased by approximately 300,000 cubic feet per second, or less, depending on the magnitude of the flood. For example, during the 200 year flood of 800,000 cubic feet per second, an incremental flow increase from the failure of Raystown dam (300,000 cubic feet per second) would result in the design flood of 1,100,000 cubic feet per second at TMINS. At higher Susquehanna River flows, the incremental flow contribution from failure of the Raystown Dam would be somewhat less, due to increased valley storage. In any case, the site would have 20 to 28 hours3.240741e-4 days <br />0.00778 hours <br />4.62963e-5 weeks <br />1.0654e-5 months <br /> warning before the incremental flows resulting from a failure of the Raystown Dam peaked at TMINS.

Tables 2.6-3 and 2.6-4 demonstrate data on water quality and temperature for the Susquehanna River gathered by the Pennsylvania Department of Health for Harrisburg, Marietta, and Columbia from 1962 to 1966.

2.6.2.2 Other Power Projects In Vicinity The City of Harrisburg is seeking a license to construct a hydroelectric dam and reservoir across the Susquehanna River, approximately 11 river miles upstream from TMINS. The dam would be a gated spillway structure 17 ft high and would impound 35,000 acre-feet. Should the project be approved, an evaluation of the potential for downstream flood damage due to misoperation or failure of the dam would be performed.

TMI-1 UFSAR CHAPTER 02 2.6-3 REV. 22, APRIL 2014 Immediately downstream from the site is the York Haven hydroelectric project, consisting of a main dam averaging 10 ft in height, extending about 5000 ft across the main river channel from Three Mile Island; a secondary dam, about 8 ft high, extending 950 ft across the east channel of the river; the water impounded by these dams form a lake (Lake Frederick) which extends approximately 3.5 miles upstream from the dams, containing about 10,000 acre-feet of volume.

A head race wall about 20 ft in height extends approximately 3000 ft from the west end of the main dam to the powerhouse, which contains 20 units which can generate a total capacity of about 20,000 kW.

The lake formed by the York Haven Dam is a principal source of recreational use of the river in the vicinity of the site. Sport fishing is done along the river, but the primary use of the lake is for pleasure boating.

The York Haven Station is operated on a run-of-the-river basis, and its power output is dependent upon river flow. The reservoir is used for limited peaking operation during periods of low river flow. Under the peaking conditions, the drawdown of the lake is 1.1 ft maximum.

Brunner Island Station, a large generating plant owned by the Pennsylvania Power & Light Company, is located on the Susquehanna River approximately 1 mile downstream from York Haven powerhouse. This station uses water from the river on a run-through basis for cooling water. York Haven Station maintains a minimum flow in the river of 1000 cfs for Brunner Island.

Three other hydroelectric generating stations are located downstream from the project, with each project having a dam and reservoir on the Susquehanna River. The three stations are Safe Harbor, Holtwood, and Conowingo hydroelectric projects, located approximately 25, 31, and 47 miles south of Three Mile Island, respectively. The Muddy Run pumped storage project is associated with Conowingo Station. The Peach Bottom nuclear generating station is located along the Susquehanna River, just north of the Maryland-Pennsylvania border.

2.6.2.3 Downstream Users The following summarizes the available information on water supplies downstream from Three Mile Island Nuclear Station for a distance to 50 miles. The consumers include public water supplies, industries, and utilities. There are no points downstream from Three Mile Island where significant concentration of river flow occurs. Storage capacity for each supply is indicated; however, it was not possible to determine, in most cases, the amount of water in storage reserved for fire protection.

a.

Metropolitan Edison Company owns and operates a hydroelectric generating station at York Haven, total installed capacity 20,000 kW. A dam across the Susquehanna River impounds 10,000 acre-feet of water for electric generation, recreation, and fire protection. Potable water is obtained from two wells.

b.

The Pennsylvania Power & Light Company owns and operates a generating station (Brunner Island) on the west shore of the Susquehanna River 5 miles downstream from the Nuclear Station. The plant has a generating capacity of 1415 MWe and utilizes 1155 cfs of river water for the circulating water system and ash removal, which is returned to the river without reconcentration. River water for cycle makeup demineralizer requirements is treated prior to use.

TMI-1 UFSAR CHAPTER 02 2.6-4 REV. 22, APRIL 2014 c.

The Wrightsville Water Supply Company has a public water supply intake on the Susquehanna River 16.25 miles downstream from the Nuclear Station. The intake is utilized as a summer reserve supply with complete treatment facilities provided in the system.

d.

The Borough of Columbia takes an average supply of two million gallons per day from the Susquehanna River from an intake located 16.75 miles downstream from the Nuclear Station. The potable water receives complete treatment.

e.

The Susquehanna Water Treatment Plant (City of Lancaster) has its intake on the Susquehanna River 17 miles downstream from the TMINS, and is a partial water source for the city of Lancaster. The plant processes between 12,000,000 and 16,000,000 gallons per day with occasional summer highs of 20,000,000 gallons per day. The water receives complete treatment with a flow through time of two hours.

f.

The Red Lion Municipal Authority has an intake on the Susquehanna River approximately 25 miles downstream from TMINS, and is a backup source of water for the city of Red Lion. Operation is limited to typically once per week. Typically, 900,000 to 1.5 million gallons per day would be withdrawn. Operating permit will allow daily withdraw up to 3 million gallons. Water is treated through a filter treatment plant prior to distribution.

g.

The Safe Harbor Water and Power Corporation owns and operates a hydroelectric generating station in the Susquehanna River about 27.25 miles downstream from the Nuclear Station. The dam across the river impounds 92,000 acre-feet for power generating purposes. Water for a public water supply system for the village of Safe Harbor is withdrawn from the reservoir at a rate of 25,000 gallons per day and receives complete treatment.

h.

A public water supply system serves the village of Holtwood on the east side of the Susquehanna River 34.75 miles downstream from the Nuclear Station, at Holtwood Hydroelectric Station. Approximately 22,000 gallons per day are withdrawn from the 19,300 acre-foot Holtwood Reservoir and treated prior to distribution.

i.

The Muddy Run Pumped Storage generating station is located 38 miles downstream of the Nuclear Station. It is a remotely controlled plant, 800 MW capacity, operating between an upper reservoir and Conowingo Reservoir using reversible pump-turbines.

River water is used for fire protection. Potable water is supplied by deep wells.

j.

Peach Bottom Nuclear Generating Station is located along the west bank of the Susquehanna River about 41 miles downstream from Three Mile Island. Two nuclear units, each rated at 1065 MWe, withdraw approximately 3450 cfs from the river for cooling purposes.

k.

The City of Baltimore has an intake on the river which draws water from Conowingo Reservoir. The intake is located about 49 miles downstream from Three Mile Island.

Baltimore is permitted to withdraw up to 250 MGD when the river flow exceeds 5000 cfs, but is limited to 65 MGD at lower river flow. Two water treatment plants provide complete treatment.

TMI-1 UFSAR CHAPTER 02 2.6-5 REV. 22, APRIL 2014 l.

Philadelphia Electric Company owns and operates a hydroelectric generating station at Conowingo Dam which impounds 321,500 acre-feet in Conowingo Reservoir. The total installed capacity of the facility is 513,000 kW, which is located 50 miles downstream from Three Mile Island. Potable water supply is obtained from the reservoir to supply the station and Conowingo Village. Complete treatment is provided for an average supply of 12,000 gallons per day.

2.6.3 LOW FLOW STUDIES Low flow studies of the Susquehanna River were conducted using data from the Harrisburg and Marietta gauging station, as recorded by the U.S. Geological Survey (Reference 12). The Harrisburg gauge has a continuous period of record since 1890, and Marietta since 1931.

Figures 2.6-3 and 2.6-4 show annual low flow frequency and flow duration curves for the Susquehanna River at Harrisburg, based upon daily flow data. The minimum flow of 1600 cfs occurred on November 29, 1930, as a result of a freeze-up of the river. The minimum daily flow since the construction of a dam downstream from the water filtration plant on City Island was 1700 cfs on September 28, 1964. Average yearly flow at Harrisburg is 34,000 cfs. The following tabulation summarizes the percent of time the flow is equal to, or less than, that indicated as follows:

Flow (cfs)

Percent of Time 2,000 less than 1 3,000 2

4,000 4

5,000 6

6,000 8

7,000 11 8,000 13 9,000 18 10,000 22 20,000 50 34,000 average flow 69 Figure 2.6-5 shows a minimum flow summary of mean monthly flows for the Susquehanna River at Harrisburg. The data show mean monthly flows by months for recurrence intervals of 2, 5, 10, 20, and 50 years. The curves on Figure 2.6-5 were developed from mean monthly flow data for the period of record from 1890 to 1960. It will be noted on Figure 2.6-5 that characteristically the low flows occur in the late summer and fall, and that the minimum mean monthly flow of record, in general, follows the 50 year curve. Extrapolation of the individual monthly curves for August through December produces the following mean monthly flows for the recurrence interval of once in 100 years:

TMI-1 UFSAR CHAPTER 02 2.6-6 REV. 22, APRIL 2014 Month 100 Years (cfs)

August 2200 September 2000 October 1800 November 2500 December 3000 A minimum flow duration summary is presented on Figure 2.6-6, which shows not only the minimum daily flows, but also their probable frequency and duration. For example, a flow of 5000 cfs or less lasting for 90 consecutive days may be expected to occur one in 5 years. It will also be noted that a minimum daily flow of 2000 cfs will be expected to occur once in 25 years, and this flow, lasting for 20 consecutive days, will occur once in 50 years.

Hydraulic studies were conducted to determine the availability of emergency and shutdown cooling water from the intake structure during periods of extreme low flow (1700 cfs), assuming a failure of the east channel dam or main dam at York Haven.

Loss of York Haven Reservoir could result from failure of the main dam, failure of the east channel dam, or failure of both dams. Failure of a dam was considered to be complete removal of the structure as a barrier to flow. Loss of the east channel dam alone would cause only a partial loss of reservoir. The reservoir would still have ample capacity to furnish water for a safe shutdown, and would also furnish sufficient water for operation.

Loss of the main dam would return the river to normal open channel flow with the depth of the water, at any point, dependent upon the hydraulic continuum of the river channel systems. A hydraulic study was made of the river to determine such conditions, since the loss of the main dam is the critical condition.

A hydrographic survey was conducted over the entire reach of the river, involving horizontal and vertical control by normal methods of surveying procedure, determination of water surface elevations by an integrated gaging system, and the use of a fathometer survey to determine stream bed elevations. These results, shown as Figures 2.6-6A through 2.6-6G, gave the necessary information regarding actual channel geometry in order to enter an analytical process of flow distribution and water surface determinations.

The analytical process was carried out by using a general program of water surface profiles in a multidivided channel, using FORTRAN II language, for an IBM 1620 computer. With the channel characteristics, as determined by the hydrographic survey, inserted into the program, it became a specific program for the reach of the Susquehanna River in question. The program was run with the main dam removed and with a total flow of 1700 cfs in the river, which is the minimum daily flow on record. This represents the most severe restrictive effect possible under the existing conditions.

The results of the study show that, under the most conservative evaluations, approximately 430 cubic feet per second will be available at the service water screen and pump house based upon a minimum river flow of 1700 cfs. The quantity is many times the amount required for a safe and orderly plant shutdown, and corresponds to a pool surface elevation of 271.7 ft above mean sea level in the middle channel of the river (Reference 24). The intake structure was constructed at an elevation to take water from the bottom of the river and to maintain minimum submergence on the nuclear service

TMI-1 UFSAR CHAPTER 02 2.6-7 REV. 22, APRIL 2014 pumps at all times. The low-flow intake canal assures that the intake structure has continuous access to river waters at water surface elevations of 270 feet or above.

Hydrographic surveys of the pool performed from 1974 to 1993 have shown no substantial changes in the bathymetry of the pool. The computer program that calculates water surface profiles for flow in a multidivided channel was rerun using hydrographic data collected in 1987, and assuming a river flow of 1700 cubic feet per second and main dam removed. The results of the follow-up analysis confirmed that sufficient water would be available at the service water screen and pump house to provide for a safe and orderly plant shutdown (Reference 25).

Using additional hydrographic data collected in 1995, the water surface profiles in the pool were again reevaluated assuming a river flow of 1700 cubic feet per second, TMINS flow requirements totaling 47 cubic feet per second, and main dam removed. Based on this analysis, approximately 740 cubic feet per second will be available at the service water screen and pump house, corresponding to a river water surface elevation of 272.2 ft above mean sea level. The results of this analysis again confirmed that sufficient river water would be available under these conditions to provide for a safe plant shutdown (Reference 30).

Two supplementary analyses were performed assuming a river flow of 1700 cubic feet per second, TMINS flow requirements totaling 77 cubic feet per second and 130 cubic feet per second, respectively, and both the main and east channel (Red Hill) dams removed. Based on these analyses, approximately 620 cubic feet per second will be available at the service water screen and pump house, corresponding to a river water surface elevation of 272.0 ft above mean sea level (Reference 30 and 31, respectively).

In 2005, the TMI area hydrographic survey and analysis were repeated (Reference 37). This work is a continuation of and is consistent with the above previous studies. The 2005 study shows that with river flow of 1700 cfs (minimum daily flow of record at Harrisburg); TMI intake flow of 130 cfs; postulated failure and complete removal of the York Haven Dam; approximately 914 cfs of water will be available at the service water screen and pump house. This corresponds to a river water surface elevation of 271.96' above mean sea level.

The 2005 study also shows that with river flow of 1700 cfs (minimum daily flow of record at Harrisburg); TMI intake flow of 130 cfs; postulated failure and complete removal of both the York Haven Dam and the East Channel Dam; approximately 882 cfs of water will be available at the service water screen and pump house. This corresponds to a river water surface elevation of 271.93' above mean sea level.

An emergency procedure directs operational responses to low water level. Operational responses are required under specified conditions of low water level inside the service water screen and pump house, extreme low river flow, and availability of bar rakes and traveling screens. Operational responses include shutting down pumps, operating bar rakes and traveling screens at increased rates, actions to remove accumulated debris, and shutting down the plant.

2.6.4 FLOOD STUDIES Since the site is located on an island in the Susquehanna River, the flood conditions of the river are of prime importance in the planning of the project.

TMI-1 UFSAR CHAPTER 02 2.6-8 REV. 22, APRIL 2014 The Susquehanna River is the principal source of flooding in the Harrisburg area. The large tributaries such as the Conodoguinet, Paxton, Yellow Breeches, and Swatara overflow their banks at times; however, the major cause of flooding is the Susquehanna River. The generating station and its facilities will not have any effect on upstream conditions during the design flood.

Prior to June 1972, the 1936 flood was the flood of record. The 1936 flood was gauged at Harrisburg at 740,000 cfs and resulted from precipitation and snow melt over the entire basin.

The TMI-design flood was established based on the Probable Maximum Flood (PMF) as defined by the ACOE in 1967 (time of PSAR), which was 1,083,000 cfs at Harrisburg. The design flood established for the site is 1,100,000 cfs. The design of the dike which protects TMINS therefore was based upon a design flood of 1,100,000 cfs. The hydraulic design of plant inundation protection is based upon this design flood, with an ample margin of free board to account for wind driven waves.

In 1969, the ACOE issued a revised PMF which predicts a peak river flow of 1,625,000 cfs at TMI. The revised PMF and computations indicate that flood discharge of an unregulated river will be 1,750,000 cfs. This flood, as modified by existing upstream flood control projects, will produce a flow at Harrisburg of 1,600,000 cfs and of 1,625,000 cfs as the PMF at Three Mile Island. The probable maximum precipitation (PMI) for the Susquehanna watershed was obtained from Hydrometeorological Report No. 40. The precipitation at Lewisburg, Wilkes-Barre, and Harrisburg has been chosen as index figures. These precipitation values are shown in histogram form on Figure 2.6-14 and in Table 2.6-5. Figure 2.6-9 shows the resulting hydrographs of the PMF, as furnished by the Corps of Engineers.

The design basis flood event remains a flow of 1,100,000 cfs. The flood barrier system and protective measures described in Section 2.6.5 provide the capability to maintain safe shutdown in the event of a PMF in accordance with the 1973 licensing commitment to AEC.

In 2011, the validity of the PMF as determined in 1969 was reviewed. The ACOE HEC-HMS model was used to assess the Impact of the most significant changes on the PMF since 1969.

The model was prepared based on a HEC-1 model of the Susquehanna watershed completed in 1975 by ACOE to learn from the observations made after Tropical Storm Agnes. The rainfall input (PMP) was derived from the National Oceanic and Atmospheric Administration (NOAA),

Hydrometereological Report 40 (HMR-40). The most significant change since the 1969 PMF was the construction of three (3) dams in the upper portions of the watershed in 1979 (Tioga, Hammond, and Cowanesque Dams). This assessment concluded that the PMF flow determine in 1969 (i.e. 1,625,000 cfs) remains the bounding hazard. (Reference 39)

An analysis of flood discharge and frequency relationship was made using data gathered by U.S. Geological Survey on past floods, dating back to 1786 (References 8, 9, 10, and 11). The flood of record occurred in June 1972. This event, according to the U.S. Geological Survey, is the highest flood to have occurred since 1784 and probably the highest since 1740 or an earlier date. The 1972 flood resulted from the blowout of tropical storm "Agnes" which covered the 25,000 square mile drainage area with an average depth of approximately eight inches of rainfall. This rainfall produced a flood at Harrisburg estimated at 1,020,000 cfs. The June 1972 flood water level remained below the top of the protective dikes and observed water elevations

TMI-1 UFSAR CHAPTER 02 2.6-9 REV. 22, APRIL 2014 showed that the 1970 stage discharge analysis was a conservative assessment of the design flood. Preceding the flood of June 1972, the flood of 1936 was the flood of record. The 1936 flood was gauged at Harrisburg at 740,000 cfs and resulted from precipitation and snow melt over the entire basin.

The following table summarizes key TMI-1 flood hazard parameters (from Reference 38):

Event Definition River Flow Rate (cfs) at TMI Predicted Recurrence Interval (years)

Water Surface Elevation (ft.) at ISPH 200,000 1.4 284.2 350,000 4.5 287.4 2011 Tropical Storm Lee 600,000 45 292.1 1936 Flood 740,000 124 294.6 Flood of Record (Agnes 1972 1,042,000 705 300.4 Design Flood 1,100,000 911 301.6 Probable Maximum Flood (PMF) 1,625,000 8670 313.3 2.6.4.1 Discharge Frequency Analysis An analysis of flood discharge and frequency relationship was made using data gathered by U.S. Geological Survey on past floods. 119 years of peak annual stream flow records from the USGS Harrisburg Gage were used to complete the stage frequency analysis following the procedure outlined in USGS Bulletin 17B. The Log-Pearson Type III statistical analysis of stream-flow gage data was used to generate a discharge-frequency/probability curve. Figure 2.6-7 shows the predicted discharge frequency for the Susquehanna River at TMI (from Reference 38).

2.6.4.2 Stage Discharge Analysis The original analysis of flood discharge and frequency relationship was made using data gathered by U.S. Geological Survey on past floods, dating back to 1786 (References 8, 9, 10, and 11). Considerable study was devoted to the stretch of the Susquehanna River between the Middletown Rapids and Safe Harbor Dam to determine the profile of the design flood and to establish the elevation for flood protection facilities. Hydrographic surveys conducted over the entire reach of river under study established stream bed elevations and channel geometry for backwater computations. A computer model of the river was then established using known gaged floods and high water marks. The rationale for using such a computerized program was based upon the premise that the profile of a known flood can be matched by a computed profile over a significant stretch of the river, and the parameters thus established can be applied to the computation of profiles for higher floods. The original stage discharge analysis used the 1936 flood as the benchmark event to calibrate the model. This analysis completed in 1970 provided the basis for the original design and licensing of TMI-1.

The original analysis was superseded by Reference 38. The current river stage discharge analysis used NAVD-88 as the reference for elevation. Typical TMI design and operating documents, and all elevation references in UFSAR section 2.6 are referenced to NGVD-29.

Figures 2.6-8, 2.6-9b and 2.6-9c use NAVD-88 as the elevation reference. To convert values which are referenced to NAVD-88 to NGVD-29, add +0.8 ft.

TMI-1 UFSAR CHAPTER 02 2.6-10 REV. 22, APRIL 2014 The current river stage discharge analysis was completed as follows. A steady-state, one-dimensional hydraulic analysis was completed using the USACE Hydrologic Engineering Center's River Analysis System (HEC-RAS). The hydraulic model extends approximately 13.7 miles downstream of TMI and 5.4 miles upstream of TMI. The downstream study limit was established to minimize sensitivity to error in estimating the downstream boundary condition.

The downstream study limit is located at the Marietta USGS Gage Station. Topographic information for the model was obtained from the PA DCNR LiDAR data for Dauphin, York, and Lancaster Counties. Bathymetric data (from measurements obtained and evaluated by Ocean Surveys Inc in April 2005) along the Susquehanna River around TMI upstream of the York Haven Dams was incorporated into the HEC-RAS model. Additional survey data for the top of dams and the river bottoms, representing the East and Main Channels below each dam (the "Conewago Rapids"), were incorporated into the HEC*RAS model from the 1999 York Haven Hydrostation Fish Passage Project. For all other cross sections, bathymetric data was obtained from FEMA's effective (1978) HEC-2 hydraulic model.

Additional parameters (such as Manning's 'n' values, ineffective flow areas, and blocked obstructions) were added based on review of PAMAP orthophotographs for Dauphin, Lancaster, and York Counties as well as local observations. Structures, including the East Channel York-Haven Dam, West Channel York-Haven Dam, Shocks Mill Railway Bridge, upstream TMI access bridge, and downstream TMI access bridge, were included in the HEC-RAS model. A USGS stage-discharge rating curve for the Marietta Gage Station was used to establish the downstream boundary conditions of the HEC-RAS model.

A range of discharge values were used in the hydraulic analysis to develop a stage-discharge rating curve at each location of interest along TMI. Flow along the Susquehanna River at TMI splits into four (4) channels formed by TMI, Hill Island, and Shelly Island. Each channel has independent hydraulic characteristics due to the varying geometry, structures, and allocation of flow. As river flow increases, some islands become inundated, which changes flow characteristics into contiguous conveyance systems. This situation results in unique split flow scenarios, depending on the river discharge.

At lower flows, the river flow was split among all four (4) channels. During intermediate flows, when some or all of the islands are inundated, the river flow was split only among the channels separated by islands not inundated. When all of the islands are inundated at high flows, the full river section (bank to bank) was included in the model, treating the entire river as a contiguous system. Because of these varying conditions, separate HEC-RAS models were developed:

Split Flow Model for smaller flow rates (less than 500,000 cfs) - No islands are inundated (split flow around each island);

Split Flow Model for intermediate flow rates (between 500,000 cfs and 1,500,000 cfs) -

Only Shelly Island is inundated (split flow around TMI only);

Total Flow Model for higher flow rates (greater than 1,500,000cfs) - Shelly Island and TMI Inundated (no split flow).

The HEC-RAS model was run at the measured peak flow rate from the 1972 Tropical Storm Agnes event. The results (Figure 2.6-9b and 2.6-9c) were compared to observed flood elevations at corresponding locations. The model was calibrated by adjustment of the Manning

'n' values used. An analysis was conducted to assess the sensitivity of the computed Water Surface Elevations (WSE) to a range of overbank Manning's 'n' values for various land uses.

TMI-1 UFSAR CHAPTER 02 2.6-11 REV. 22, APRIL 2014 At PMF conditions, use of minimum or maximum 'n' values obtained from Table 5-6 in Chow's Open Channel Hydraulics (1959) for various overland conditions did not change the WSE by more than 1.1 feet.

Flow pattern complexities along the Susquehanna River in the vicinity of TMI, caused by islands, dams, and bridges, raised concerns that the 1D HEC-RAS model would produce unacceptable errors in predicting flood elevations. To address these concerns, a Two-Dimensional (2D) Finite-Element River Dynamics Computer Model was used to simulate the PMF hydraulics (flow depths and velocity vectors). The 2D model reach included Three Mile Island, Shelly Island, Hill Island, the York Haven Dams, and the two (2) access bridges. The 2D model was calibrated to observed peak WSEs from Tropical Storm Agnes.

WSEs from the appropriate models were used to develop stage-discharge rating curves (Figure 2.6-8). Figure 2.6-8 presents the series of stage-discharge curves for the indicated locations between PA Turnpike Bridge and Marietta.

Table 2.6-6 presents the stage discharge relationship at the TMI-1 ISPH.

2.6.5 DESIGN OF HYDRAULIC FACILITIES Designs were prepared for the structures associated with flood protection and cooling water facilities including earth dikes, channels, and pressure conduits. The design criteria are conservative and based on sound civil engineering practices. The strength parameters and other design characteristics of the foundations and of the materials which were used in constructing the facilities were determined from comprehensive field and laboratory testing programs. The facilities were constructed and will be maintained and inspected consistent with their design as integral parts of a nuclear station. The designs of the facilities were reviewed and approved by the appropriate state and federal agencies, including the Federal Power Commission, the Corps of Engineers, and the Water and Power Resources Board of the Commonwealth of Pennsylvania, where applicable.

The dikes are earth embankments, constructed of clay and silt. Approved borrow material has been excavated, hauled, placed, and compacted to produce a stable, impervious facility. The material is compacted in layers to a minimum of 95 percent of Standard Proctor density. The permeability of the dike is of the order of 10-6 cm/sec. The dike dimensions are: A top width of 20 ft, side slopes of two horizontal to one vertical, and of height, ranging up to 20 ft. Soil tests were conducted during construction to control the placement of material and ensure adequate and proper compaction. The dikes are protected by a layer of dumped riprap of sufficient size and thickness, and with an adequate zone of sand and gravel embedment material, to withstand wave height of 2.25 ft, and a velocity in excess of 12.0 ft/sec, on a 2-on-1 slope. The riprap was sized according to the standards of the Tennessee Valley Authority for riprap on earth dams and in power house and spillway tailraces. The riprap continues downward into natural ground for a minimum depth of 2 ft to provide a cutoff against undermining. This system of dikes will protect the site against inundation and wave action for the site design flood of 1,100,000 cfs. Dikes are provided for the site to protect the plant from wave action for the design flood, since plant grade at 304 ft is above the design flood water surface elevation. The top elevation of the protective dike at the northern tip of Three Mile Island is 310 ft, providing a freeboard of at least 6 ft above the design flood at this location. The dikes along both sides of the island descend uniformly from elevation 310 ft to elevation 305 ft, extending sufficient distances to protect the entire plant site for the design flood. The

TMI-1 UFSAR CHAPTER 02 2.6-12 REV. 22, APRIL 2014 freeboard at the intake structure is at least 2 ft. Provision has been made for a cutoff at elevation 304 ft extending across the downstream end of the plant site.

The permanent access bridge (the north bridge) extends from the east shore a distance of 1600 ft to Three Mile Island, crossing the east channel and Sand Beach Island. The bridge is a combination rail-roadway structure with concrete slab and steel girders supported on 16 concrete piers and end abutments. The elevations of the deck slab are 306.3 ft at the east end of the bridge, 313.2 ft near the center, and 310 ft at the west end. Throughout the main spans of the bridge, the bottom of the supporting steel girders is approximately 9 ft below the deck. The bridge has been designed to withstand the forces of the design flood. The deck is high enough to ensure dry passage over the bridge during the design flood. The backwater effect of the bridge during the design flood is estimated to be in the order of 0.4 ft at the bridge.

A comparison of top of dike elevations and water surface elevations to define freeboard on the dikes, as well as the mean velocities, which can be expected during the design flood are shown on Figure 2.6-15. The plan of the access bridge is also shown on this figure. Elevations and sections of the access bridge are shown on Figure 2.6-16. A cross section of the dike showing riprap details is shown on Figure 2.6-17.

A Corps of Engineers' "Standard Project Flood," or roughly a repetition of the 1936 flood, is required before water can reach the elevation of the base of the dikes. Periodic inspection of the natural banks and the dikes after flow periods (i.e., ice flow and spring flow) will be made by the operators to determine any bank erosion or riprap weathering. Any required remedial actions will be taken.

The intake structure has been based upon competent rock and is a reinforced concrete structure with wing walls for erosion protection and concrete cutoff walls to resist undercutting.

The design ensures that the pumps remain operable if the site is subjected to the maximum flood level. The structure has been designed to be stable under all conditions of loading, including maximum flood and ice jams. The banks upstream and downstream have been rip-rapped to afford protection against erosion during flood. Recirculation has been provided from the unit to the intake to provide warm water to control ice problems that might develop during cold weather. The structure has been adequately protected from trash and debris by automated bar rakes and traveling screens.

A commitment was made to the Atomic Energy Commission that the plant would be provided with component protection to the degree which will assure a safe and orderly shutdown for the level of flooding postulated by the official value of the new Probable Maximum Flood, as modified by existing upstream flood control projects (Q = 1,625,000 cfs). Various components provide protection for achieving and maintaining a safe shutdown condition, in compliance with the commitment made to the Atomic Energy Commission.

These gates, seals and other barriers will prevent water intrusion into safety-related structures at a water surface elevation below 313.5 ft. These barriers and protective measures include, but are not limited to, the following locations and type of flood protection:

a.

Intake Screen and Pump House (ISPH) 1)

Flood Gates (TMI-FGE1, E2A/B/C, E4).

TMI-1 UFSAR CHAPTER 02 2.6-13 REV. 22, APRIL 2014 2)

Seals where pump shafts penetrate the floor slab.

3)

Manholes in slab at 308 feet floor elevation will be sealed. (U1-E-5 & 6) 4)

Floor Drain Penetrations in Pump Rooms will be plugged.

5)

Screen wash pump seal leak-off basin drains will be isolated.

6)

River pump seal leak-off funnels (12) will be plugged.

b.

Fuel Handling Building 1)

Flood Gate (TMI-FG-A1).

2)

Inflatable seal at railroad missile shield door (FH-208).

3)

Plugs will be installed in RB Personnel Hatch Access Area floor drains and WDL-V-531 will be closed.

c.

Control Building (CB) 1)

Flood Gate (TMI-FG-B1 and B2).

2)

Plugs will be installed in Turbine Bldg and CB elevator Machine Room Area floor drains.

3)

Check valves (SD-V-144 and SV-V-151) prevent flood water flow into Control Bldg through drain lines.

4)

Secondary chem. lab drain will be isolated (SS-V-257) to prevent flood water flow into Control Bldg.

d.

Auxiliary Building (AB) 1)

Inflatable seal at truck unloading missile shield door (A-116).

2)

Isolate BWST Tunnel sump pump discharge (WDL-V-612).

e.

Intermediate Building (IB) 1)

Flood Gate (TMI-FG-C1).

2)

Close Sump Pump Discharge Isolation Valve (SD-5A/5B/7A/7B) if a sump pump is unavailable and check valve does not prevent flood water from the Turbine Bldg into IB.

f.

Diesel Generator Building 1)

Flood Gates (TMI-FG-D1 &D3) will be installed.

2)

Flood gates (TMI-FG-D2A, D2B, D4A &D4B) are normally installed.

g.

Air Intake Tunnel 1)

Air inlet is located at an elevation above PMF level.

TMI-1 UFSAR CHAPTER 02 2.6-14 REV. 22, APRIL 2014 2)

Check valves (SD-V-3 & SD-V-10A/B) prevent flood water from entering AIT through the AIT sump pump discharge pit.

h.

Diesel Fuel Oil Storage Tank 1)

The 30k underground tank design is sufficient to withstand the hydraulic forces with flood water at 313.5' elev.

i.

General All penetrations on flood barrier system boundary below PMF elevation (ducts, pipes, conduits, cable trays, seismic gaps, and so forth) are sealed. The 3 inch seismic gap between interfacing bldgs (IB, Alligator PIT, FHB, Aux Bldg) and the Reactor Building was made watertight.

The actions to be taken preceding and during a flood will be initiated based on projected discharge rates or actual river stage at the plant. Actions required for safe shutdown are performed in accordance with the flood protection procedures. The capability to successfully mitigate a PMF is based on the PMF hydrograph on Figure 2.6-9. These procedures include the following actions:

a)

A 36 hour4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> forecast of 350,000 cfs or greater will initiate the Flood Protection Procedure.

b)

If a 36 hour4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> forecast exceeds 900,000 cfs, then EMERGENCY CLOSURE will be initiated. The flood barrier system (gates, covers, etc. discussed above) boundary will be closed.

c)

If the River Water level at the TMI1 Intake Structure reaches 300 feet (corresponding to 900,000 cfs river flow), an UNUSUAL EVENT will be declared.

d)

If the river water level at the TMI-1 Intake Structure reaches 300 feet, then the reactor will be shutdown.

The precipitation necessary to cause a PMF type flood is given for various locations in Hydrometeorological Report No. 40, by the U.S. Weather Bureau. The precipitation at Lewisburg, Wilkes-Barre, and Harrisburg has been chosen as index figures. These precipitation values are shown in histogram form on Figure 2.6-14 and in Table 2.6-5.

A comparison of top of dike elevations and water surface elevations to define freeboard on the dikes, as well as the mean velocities, which can be expected during the design flood are shown on Figure 2.6-15. The plan of the access bridge is also shown on this figure. Elevations and sections of the access bridge are shown on Figure 2.6-16.

A cross section of the dike showing riprap details is shown on Figure 2.6-17. A Corps of Engineers "Standard Project Flood," or roughly a repetition of the 1938 flood, is required before water can reach the elevation of the base of the dikes. Periodic inspection of the natural banks and of the dikes after flow periods (i.e., Ice flow and spring fIow), will be made by the operators to determine any bank erosion or riprap weathering. Any required remedial actions will be taken.

TMI-1 UFSAR CHAPTER 02 2.6-15 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 1 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Total Surface Storage Area No.Reservoir Stream Owner (Acre-Feet) (Acres) 1 Lake E. Br. Codorus York Water 3,440 220 Williams Creek Company 2

Lake E. Br. Codorus York Water 5,530 290 Redman Creek Company 3

Pinchot Beaver Creek Pa. Dept.

2,800 342 Lake Forest & Waters 4

Lake Pa Ha Branch of P.H. Glatfelter 3,350 137 Ga Co.

Bunch Creek Co.

5 Lake W. Br. Codorus P.H. Glatfelter 48,500 1275 Marburg Creek Co.

6 Indian W. Br. Codorus U.S. Corp. of 28,000 1430 Rock Res.

Creek Engineers 7

Long Arm Long Arm Creek Hanover Municipal 5,220 185 Reservoir Water Works 8

Sheppard-Long Arm Creek Hanover Municipal 615 46.8+

Myers Water Works 9

Trout Run Shippensburg 640 35 Borough Authority 10 Carbaugh Run Pa. Dept. Health 20 11 Lake Plum Creek Lake Heritage, Inc.

Heritage 146 12 Lake Mead Mud Run Lake Mead, Inc.

3,680 291 13

  1. 6 Dam S. Br. Roaring Roaring Creek 4,080 185 Creek Water Company 14
  1. 4 Dam Trout Creek Roaring Creek 108 12 Water Company 15
  1. 2 Dam S. Br. Roaring Bear Gap Water 592 65 Creek Co.

16 Clark Clark Creek City of Harrisburg 23,600 650 Valley 17 Muddy Run Muddy Run Philadelphia 60,500 985 Pumped Electric Company Storage Pond 18 Conowingo Susquehanna Philadelphia 6975 River Electric Company 19 Holtwood Susquehanna Pennsylvania Power 2048 Dam River

& Light Co.

20 Safe Susquehanna Safe Harbor Power 92,200 Harbor Dam River Co.

TMI-1 UFSAR CHAPTER 02 2.6-16 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 2 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Total Surface Storage Area No. Reservoir Stream Owner (Acre-Feet) (Acres) 21 Dock Susquehanna City of Harrisburg Street Dam River 22 Hammer Creek Penna. Fish 106.4 Commission 23 Conodoguinet U.S. Corp of 1,012 54 Creek Engineers Letterkenny Ordinance Depot 24 No.1 W. Br. Hammer City of Lebanon 55 Creek 25 No.2 W. Br. Hammer City of Lebanon 150 Creek 26 DAM REMOVED - - - -

27 Octoraro Octoraro Lake Chester Municipal 7,700 669 Lake Authority 28 Blue Tulpehocken U.S. Corp 49,000 1000(2)

Marsh (1)

Creek of Engineers 29 Antietam Stony Creek City of Reading 310 30 Angelica Angelica City of Reading 147 22.5 Creek 31 Lake Maiden Creek City of Reading 11,900 1082 Ontelaunee 32 Furnace Creek Womelsdorf-108 Robesonia Auth.

33 Peters Spring Maiden Creek 92 35 Run Township 34 High Bridge Fishing Creek City of Lebanon 1,170 55 Dam 35 Wolf Creek Tar Run Pottsville Water 492 25.6 Co.

36 Indian Run Indian Run Pottsville Water Co.

52 1,470 37 Upper Dam Tumbling Run Borough of 725 30 Schuykill Haven 38 Lower Dam Tumbling Run Borough of 530 28 Schuykill Haven 39 Mud Run Mud Run Mahanoy Township 620 54 Authority 40 No. 2 Dam Little Borough of 330 13 Mahanoy Creek Ashland 2.6-21

TMI-1 UFSAR CHAPTER 02 2.6-17 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 3 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Total Surface Storage Area No. Reservoir Stream Owner (Acre-Feet)

(Acres) 41 Dam No.4 Dyers Run Minersville Water 204 21.7 Company 42 Sweet E.Br. Swatara Pennsylvania Power 1,100 100 Arrow Lake Creek

& Light Co.

43 Kauffman Kauffman Run Pottsville Water 320 19 Dam Co.

44 Rock Run Rock Run City of Coatsville 1,020 61 Dam 45 Liberty N.Br. Patapsco City of Baltimore 132,000 3,100 River 46 Pretty Boy Gun Powder City of Baltimore 61,400 1,500 Falls 47 Lock Raven Gun Powder City of Baltimore 70,600 2,400 Falls 48 Long Pine Long Pine Run Borough of 5,370 150 Run Dam Chambersburg 49 Chambers-Conococheague Borough of 1,037 49 burg Reser-Creek Chambersburg voir 50 Little Little Buffalo Pa. Dept. Forest 880 88 Buffalo Creek

& Waters Dam

TMI-1 UFSAR CHAPTER 02 2.6-18 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 4 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Dead Surface Storage Area No.

Reservoir Stream Owner (Acre-Feet) (Acres) 1 Lake E. Br. Codorus York Water 0

0 Williams Creek Company 2

Lake E. Br. Codorus York Water 0

0 Redman Creek Company 3

Pinchot Beaver Creek Pa. Dept.

0 0

Lake Forest & Waters 4

Lake Pa Ha Branch of P.H. Glatfelter 0

0 Co.

Bunch Creek Co.

5 Lake W. Br. Codorus P.H. Glatfelter 0

0 Marburg Creek Co.

6 Indian W. Br. Codorus U.S. Corp. of 0

0 Rock Creek Engineers 7

Long Arm Long Arm Creek Hanover Municipal 0

0 Reservoir Water Works 8

Sheppard-Long Arm Creek Hanover Municipal 0

0 Myers Water Works 9

Trout Run Shippensburg Borough Authority 10 Carbaugh Run Pa. Dept. Health 0

0 11 Lake Plum Creek Lake Heritage, Inc.

0 0

Heritage 12 Lake Mead Mud Run Lake Mead, Inc.

0 0

13

  1. 6 Dam S. Br. Roaring Roaring Creek 0

0 Water Company 14

  1. 4 Dam Trout Creek Roaring Creek 0

0 Water Company 15

  1. 2 Dam S. Br. Roaring Bear Gap Water 0

0 16 Clark Clark Creek City of Harrisburg 0

0 Valley 17 Muddy Run Muddy Run Philadelphia 640 Pumped Electric Company Storage Pond 18 Conowingo Susquehanna Philadelphia River Electric Company 19 Holtwood Susquehanna Pennsylvania Power Dam River

& Light Co.

20 Safe Susquehanna Safe Harbor Power Harbor Dam River Co.

TMI-1 UFSAR CHAPTER 02 2.6-19 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 5 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Dead Surface Storage Area No.

Reservoir Stream Owner (Acre-Feet) (Acres) 21 Dock Susquehanna City of Harrisburg Street Dam River 22 Hammer Creek Penna. Fish 0

0 Commission 23 Conodoguinet U.S. Corp of 0

0 Creek Engineers Letterkenny Ordinance Depot 24 No.1 W. Br. Hammer City of Lebanon 0

0 Creek 25 No.2 W. Br. Hammer City of Lebanon 0

0 Creek 26 DAM REMOVED - - - -

27 Octoraro Octoraro Lake Chester Municipal 0

0 Lake Authority 28 Blue Tulpehocken U.S. Corp of 1500 Marsh (1)

Creek Engineers 29 Antietam Stony Creek City of Reading 0

0 30 Angelica Angelica City of Reading 0

0 Creek 31 Lake Maiden Creek City of Reading 0

0 Ontelaunee 32 Furnace Creek Womelsdorf-0 0

Robesonia Auth.

33 Peters Spring Maiden Creek 0

0 Run Township 34 High Bridge Fishing Creek City of Lebanon 0

0 Dam 35 Wolf Creek Tar Run Pottsville Water 0

0 Co.

36 Indian Run Indian Run Pottsville Water Co.

0 0

37 Upper Dam Tumbling Run Borough of 0

0 Schuykill Haven 38 Lower Dam Tumbling Run Borough of 0

0 Schuykill Haven 39 Mud Run Mud Run Mahanoy Township 0

0 Authority 40 No. 2 Dam Little Borough of 0

0 Mahanoy Creek Ashland

TMI-1 UFSAR CHAPTER 02 2.6-20 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 6 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Dead Surface Storage Area No.

Reservoir Stream Owner (Acre-Feet) (Acres) 41 Dam No.4 Dyers Run Minersville Water 0

0 Company 42 Sweet E.Br. Swatara Pennsylvania Power 0

0 Arrow Lake River

& Light Co.

43 Kauffman Kauffman Run Pottsville Water 0

0 Dam Co.

44 Rock Run Rock Run City of Coatsville 0

0 Dam 45 Liberty N.Br. Patapsco City of Baltimore 0

0 46 Pretty Boy Gun Powder City of Baltimore 0

0 Falls 47 Lock Raven Gun Powder City of Baltimore 0

0 Falls 48 Long Pine Long Pine Run Borough of 0

0 Run Dam Chambersburg 49 Chambers-Conococheague Borough of 0

0 burg Reser-Creek Chambersburg voir 50 Little Little Buffalo Pa. Dept. Forest 0

0 Buffalo Dam Creek

& Waters

TMI-1 UFSAR CHAPTER 02 2.6-21 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 7 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Average Flow Distance No.

Reservoir Stream Owner (CFS)

(Miles) 1 Lake E. Br. Codorus York Water 18 Williams Creek Company 2

Lake E. Br. Codorus York Water 18 Redman Creek Company 3

Pinchot Beaver Creek Pa. Dept.

50 10 Lake Forest & Waters 4

Lake Pa Ha Branch of P.H. Glatfelter 21 Co.

Bunch Creek Co.

5 Lake W. Br. Codorus P.H. Glatfelter 25 Marburg Creek Co.

6 Indian W. Br. Codorus U.S. Corp. of 97 16 Rock Creek Engineers 7

Long Arm Long Arm Creek Hanover Municipal 31 Reservoir Water Works 8

Sheppard-Long Arm Creek Hanover Municipal 32 Myers Water Works 9

Trout Run Shippensburg 50 Borough Authority 10 Carbaugh Run Pa. Dept. Health 43 11 Lake Plum Creek Lake Heritage, Inc.

34 Heritage 12 Lake Mead Mud Run Lake Mead, Inc.

20 13

  1. 6 Dam S. Br. Roaring Roaring Creek 49 Water Company 14
  1. 4 Dam Trout Creek Roaring Creek 46 Water Company 15
  1. 2 Dam S. Br. Roaring Bear Gap Water 48 16 Clark Clark Creek City of Harrisburg 21 Valley 17 Muddy Run Muddy Run Philadelphia 32 Pumped Electric Company Storage Pond 18 Conowingo Susquehanna Philadelphia 5985(3) 44 River Electric Company 19 Holtwood Susquehanna Pennsylvania Power6505(4) 30 Dam River

& Light Co.

20 Safe Susquehanna Safe Harbor Power 24 Harbor Dam River Co.

TMI-1 UFSAR CHAPTER 02 2.6-22 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 8 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Average Flow Distance No.

Reservoir Stream Owner (CFS)

(Miles) 21 Dock Susquehanna City of Harrisburg 11 Street Dam River 22 Hammer Creek Pennsylvania Fish 23 Commission 23 Conodoguinet U.S. Corp of 14 Creek Engineers Letterkenny Ordinance Depot 24 No.1 W. Br. Hammer City of Lebanon 21 Creek 25 No.2 W. Br. Hammer City of Lebanon 21 Creek 26 DAM REMOVED 27 Octoraro Octoraro Lake Chester Municipal 183 43 Lake Authority 28 Blue Tulpehocken U.S. Corp of 40 Marsh (1)

Creek Engineers 29 Antietam Stony Creek City of Reading 47 30 Angelica Angelica City of Reading 43 Creek 31 Lake Maiden Creek City of Reading 47 Ontelaunee 32 Furnace Creek Womelsdorf-33 Robesonia Auth.

33 Peters Spring Maiden Creek 48 Run Township 34 High Bridge Fishing Creek City of Lebanon 29 Dam 35 Wolf Creek Tar Run Pottsville Water 48 Co.

36 Indian Run Indian Run Pottsville Water 42 Co.

37 Upper Dam Tumbling Run Borough of 47 Schuykill Haven 38 Lower Dam Tumbling Run Borough of 46.5 Schuykill Haven 39 Mud Run Mud Run Mahanoy Township 49 Authority 40 No. 2 Dam Little Borough of 48 Mahanoy Creek Ashland

TMI-1 UFSAR CHAPTER 02 2.6-23 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 9 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius Average Flow Distance No.

Reservoir Stream Owner (CFS)

(Miles) 41 Dam No.4 Dyers Run Minersville Water 45 Company 42 Sweet E.Br. Swatara Pennsylvania Power 35 Arrow Lake River

& Light Co.

43 Kauffman Kauffman Run Pottsville Water 49 Dam Co.

44 Rock Run Rock Run City of Coatsville 49 Dam 45 Liberty N.Br. Patapsco City of Baltimore 49 46 Pretty Boy Gun Powder City of Baltimore 36 Falls 47 Lock Raven Gun Powder City of Baltimore 48 Falls 48 Long Pine Long Pine Run Borough of 43 Run Dam Chambersburg 49 Chambers-Conococheague Borough of 42 burg Reser-Creek Chambersburg voir 50 Little Little Buffalo Pa. Dept. Forest 30 Buffalo Dam Creek

& Waters

TMI-1 UFSAR CHAPTER 02 2.6-24 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 10 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius No.

Reservoir Stream Owner Direction 1

Lake E. Br. Codorus York Water S

Williams Creek Company 2

Lake E. Br. Codorus York Water S

Redman Creek Company 3

Pinchot Beaver Creek Pa. Dept.

SW Lake Forest & Waters 4

Lake Pa Ha Branch of P.H. Glatfelter SSE Co.

Bunch Creek Co.

5 Lake W. Br. Codorus P.H. Glatfelter SSE Marburg Creek Co.

6 Indian W. Br. Codorus U.S. Corp. of S

Rock Creek Engineers 7

Long Arm Long Arm Creek Hanover Municipal SW Reservoir Water Works 8

Sheppard-Long Arm Creek Hanover Municipal SW Myers Water Works 9

Trout Run Shippensburg W

Borough Authority 10 Carbaugh Run Pa. Dept. Health WSW 11 Lake Heritage Plum Creek Lake Heritage, Inc. SW 12 Lake Mead Mud Run Lake Mead, Inc.

WSW 13

  1. 6 Dam S. Br. Roaring Roaring Creek NNE Water Company 14
  1. 4 Dam Trout Creek Roaring Creek NNE Water Company 15
  1. 2 Dam S. Br. Roaring Bear Gap Water NNE 16 Clark Clark Creek City of Harrisburg N

Valley 17 Muddy Run Muddy Run Philadelphia SE Pumped Electric Company Storage Pond 18 Conowingo Susquehanna Philadelphia SE River Electric Company 19 Holtwood Susquehanna Pennsylvania Power SE Dam River

& Light Co.

20 Safe Susquehanna Safe Harbor Power SE Harbor Dam River Co.

21 Dock Susquehanna City of Harrisburg NW Street Dam River 22 Hammer Creek Pennsylvania Fish E

Commission

TMI-1 UFSAR CHAPTER 02 2.6-25 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 11 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius No.

Reservoir Stream Owner Direction 23 Conodoguinet U.S. Corp of NW Creek Engineers Letterkenny Ordinance Depot 24 No.1 W. Br. Hammer City of Lebanon ENE Creek 25 No.2 W. Br. Hammer City of Lebanon ENE Creek 26 DAM REMOVED -

27 Octoraro Octoraro Lake Chester Municipal SE Lake Authority 28 Blue Tulpehocken U.S. Corp of ENE Marsh (1)

Creek Engineers 29 Antietam Stony Creek City of Reading ENE 30 Angelica Angelica City of Reading ENE Creek 31 Lake Maiden Creek City of Reading NE Ontelaunee 32 Furnace Creek Womelsdorf-ENE Robesonia Auth.

33 Peters Spring Maiden Creek ENE Run Township 34 High Bridge Fishing Creek City of Lebanon NNE Dam 35 Wolf Creek Tar Run Pottsville Water NNE Co.

36 Indian Run Indian Run Pottsville Water NE Co.

37 Upper Dam Tumbling Run Borough of NE Schuykill Haven 38 Lower Dam Tumbling Run Borough of NE Schuykill Haven 39 Mud Run Mud Run Mahanoy Township NNE Authority 40 No. 2 Dam Little Borough of NNE Mahanoy Creek Ashland

TMI-1 UFSAR CHAPTER 02 2.6-26 REV. 18, APRIL 2006 TABLE 2.6-1 (Sheet 12 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Data On Reservoirs and Lakes Within a 50 Mile Radius No.

Reservoir Stream Owner Distance 41 Dam No.4 Dyers Run Minersville Water NNE Company 42 Sweet E.Br. Swatara Pennsylvania Power NNE Arrow Lake River

& Light Co.

43 Kauffman Kauffman Run Pottsville Water NNE Dam Co.

44 Rock Run Rock Run City of Coastville ESE Dam 45 Liberty N.Br. Patapsco City of Baltimore S

46 Pretty Boy Gun Powder City of Baltimore S

Falls 47 Lock Raven Gun Powder City of Baltimore S

Falls 48 Long Pine Long Pine Run Borough of WSW Run Dam Chambersburg 49 Chambers-Conococheague Borough of WSW burg Reser-Creek Chambersburg voir 50 Little Little Buffalo Pa. Dept. Forest NW Buffalo Dam Creek

& Waters

  • Information not available (1) Proposed construction to be completed in 1971, begin about 1968.

Multi-purpose, flood control, water supply, recreation (2) Area of recreation pool at storage capacity of 14,500 acre-feet (3) 90% of time as recorded for 33 year period (4) 90% of time as recorded for 31 year period

TMI-1 UFSAR CHAPTER 02 2.6-27 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 1 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Well Water Gallons Depth Diam.

No.

Authority per Day Source (Ft.) (In.)

1 Marysville Water 140,000 Stony Creek in Company Dauphin Lambs Gap Run (100,000 gal.

pond)

Trout Run (50,000 gal. pond)

Sitterly Spring Run 2.

Summerdale Water

  1. 1 Well Company
  1. 2 Well 200 6

3.

William Grove Park 9,000 Spring in Company center of lake (Covered and protected from lake water) 4.

Pennsylvania 50,000 Riverton 66 8

Industrial Consolidated School Water Company Well 5.

Mechanicsburg Trindle Spring Water Company

  1. 1 Well 115 8

6.

Gulf Oil Company

  1. 1 Well 348 6

(Turnpike Service

  1. 2 Well 150 6

Area) 7.

Mechanicsburg 1,240,000 Yellow Breeches Water Company Creek 8.

Riverton 8,100,000 Yellow Breeches Consolidated Creek Water Company 9.

Center Square 11,400

  1. 1 Well Water Company 10.

Grantham Water 35,000

  1. 1 Spring Company
  1. 2 Spring Well 500 6

11.

Dillsburg Borough 85,000 12 Springs Council

  1. 1 Well 179 6
  1. 3 Well 300 6
  1. 4 Well 130 8

TMI-1 UFSAR CHAPTER 02 2.6-28 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 2 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Well Water Gallons Depth Diam.

No.

Authority per Day Source (Ft.) (In.)

12.

Gifford Pinchot 100,000 Pinchot Lake State Park 13.

Dover Borough

  1. 1 Well 310 8
  1. 2 Well 408 8
  1. 3 Well 311 8
  1. 4 Well 800 8
  1. 5 Well 311 8

14.

Gleneagles Water 50,000 Well 258 8

Company 15.

Mt. View Water 26,386 Well 210 6

Company 16.

Dover Township 143,000

  1. 1 Well 300 8

Authority

  1. 2 Well 300 8
  1. 3 Well 383 8
  1. 4 Well 230 8

17.

West Manchester 275,000 4 Wells Township Authority 18.

Ivan R. Lehr Well 312 8

Water Company 19.

Penvale Water 15,000 Well 785 12 Company 20.

Hallam Borough 60,000 8 Spring Authority 1 Well 177 8

21.

Jackson 2 Springs Township Water District #1 22.

Pine Springs 25 houses 1 Well 830 8

Water Company 23.

New Salem

  1. 1 Well 140 6

Borough

  1. 2 Dug Well 7

Authority 100,000

  1. 1 Spring

TMI-1 UFSAR CHAPTER 02 2.6-29 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 3 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Well Water Gallons Depth Diam.

No.

Authority per Day Source (Ft.) (In.)

24.

Sylvan Hills 50 Homes Well 200 8

Development Water Works 25.

Windsor 65,000 8 Springs Water 2 Wells Authority 26.

Red Lion Cabin Creek Municipal Reservoir (50 MG)

Authority 27.

Red Lion Beaver Creek Municipal Reservoir (5.6 MG)

Authority 28.

Wrightsville 144,000 6 Springs Water Supply

  1. 1 Well Company Abandoned quarry 425 6

(5.5 acres, 140 MG) filled by Susque-hanna River intake 29.

Dauphin 3,500,000 Stony Creek Consolidated (2 acre lake)

Water Company 30.

Linglestown 25 homes Well 150 6

Water Company 31.

Sky Line 170 homes Well 400 6

View Extension 32.

Annville 450,000 Springs Water Company 33.

Cleona 25,000 2 Springs from Water City of Lebanon Company

TMI-1 UFSAR CHAPTER 02 2.6-30 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 4 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Well Water Gallons Depth Diam.

No.

Authority per Day Source (Ft.) (In.)

34.

Dauphin 1,200,000 Open Quarry Consolidated (1 acre, 10 MG)

Water Company 35.

Gulf Oil 10,000

  1. 1 Well 242 Company
  1. 2 Well 239 (Turnpike
  1. 3 Well 214 Service Area) 36.

Steelton 2,000,000 Susquehanna Water River Company 37.

Dauphin 1,700,000 Beaver Creek Consolidated (1.2 acre lake)

Water Well Company 38.

Dauphin 2,000,000 Swatara Creek 178 13 Consolidated (5 acre lake)

Water Company 39.

Cambelltown 700 people 9 Springs Water 1 Well 350 8

Company 40.

Mt. Gretna 12,000 Well 165 Heights Water Company 41.

Mt. Gretna 25,000 Well 200 8

Camp Meeting Association 42.

Quentin 10,000

  1. 1 Well 223 6

Water

  1. 2 Well 314 Company 43.

Cornwall 270,000

  1. 1 Well Borough
  1. 4 Well 360 6

Municipal White Quarry Authority Tract Spring Freeman's Springs Saddler Run

TMI-1 UFSAR CHAPTER 02 2.6-31 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 5 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Well Water Gallons Depth Diam.

No.

Authority per Day Source (Ft.) (In.)

44.

Highspire 314,000

  1. 1 Well 255 Water
  1. 2 Well 806 Company
  1. 3 Well 878 10 2 Springs 45.

Carroll

  1. 1 Well 253 8

Acres Quarry (4.5 Development acres, 68 MG) 46.

Olmstead 1,000,000 Wells Air Force Base

47. -

48.

Middletown 880,000

  1. 1 Well 400 8

Water

  1. 2 Well 800 10 Company 49.

Gulf Oil 15,000

  1. 1 Well 475 Company
  1. 2 Well 806 (Turnpike
  1. 3 Well 350 Service Area)
  1. 4 Well 250 50.

Elizabethtown 500,000 7 Springs Water

  1. 1 Well Company
  1. 2 Well 219 18
  1. 3 Well 476 10
  1. 4 Well 700
  1. 5 Well 500 10 W. Br. Conoy Creek (1500 gal. pond)

Conewago Creek (emergency) 51.

Masonic Homes 250,000 7 Springs

  1. 3 Well (emergency)
  1. 4 Well
  1. 5 Well 200 8
  1. 6 Well 500

TMI-1 UFSAR CHAPTER 02 2.6-32 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 6 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Well Water Gallons Depth Diam.

No.

Authority per Day Source (Ft.) (In.)

52.

Rheems Water 40,000 Well 380 6

Company 53.

Mt. Joy Spring Water Authority 54.

Mt. Joy 700,000 Little Chickies Water Creek Authority 55.

Manheim Water 460,000 Reiffs Run Company Quarry (0.23 acres) 56.

Bainbridge 12,000

  1. 1 well 182 6
  1. 2 Well 242 6

57.

Shocks Mill 7,000 1 Well 101 4

58.

East Donogal 100,000 Glatfelter Springs Municipal Authority 59.

Marietta 380,000 Dugans Run (0.2 Water acre, 660,000 gal.

Company lake)

Wildcat Reservoir (0.36 acres, 1,000,000 gal. lake) 60.

Marietta

  1. 1 Well 116 8

Water

  1. 2 Well 133 8

Company Spring 61.

Columbia 2,000,000 Susquehanna River 230 12 62.

Lancaster, 8,000,000 Susquehanna River 230 12 City of 63.

Safe Harbor 25,000 Susquehanna River 64.

Holtwood 290,000 Susquehanna River 65.

Riverton 2,000,000 Conodoguinet Creek Consolidated Water Company 66.

Pa. Dept.

  1. 1 Well Agriculture
  1. 2 Well at Summerdale

TMI-1 UFSAR CHAPTER 02 2.6-33 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 7 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Water Gallons Yield Pump No.

Authority per Day Source (Ft.) (In.)

1 Marysville Water 140,000 Stony Creek in Company Dauphin Lambs Gap Run (100,000 gal.

pond)

Trout Run (50,000 gal. pond)

Sitterly Spring Run 2.

Summerdale Water

  1. 1 Well 40 Company
  1. 2 Well 60 3.

William Grove Park 9,000 Spring in Company center of lake (Covered and protected from lake water) 4.

Pennsylvania 50,000 Riverton 200 275 Industrial Consolidated School Water Company Well 5.

Mechanicsburg Water Trindle Spring 500 Company

  1. 1 Well 500 500 6.

Gulf Oil Company

  1. 1 Well 100 (Turnpike Service
  1. 2 Well 100 Area) 7.

Mechanicsburg Water1,240,000 Yellow Breeches Company Creek 8.

Riverton 8,100,000 Yellow Breeches Creek Consolidated Water Company 9.

Center Square 11,400

  1. 1 Well 120 120 Water Company 10.

Grantham Water 35,000

  1. 1 Spring Company
  1. 2 Spring 30 Well 30 11.

Dillsburg Borough 85,000 12 Springs Council

  1. 1 Well 50
  1. 3 Well 40
  1. 4 Well 200 200

TMI-1 UFSAR CHAPTER 02 2.6-34 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 8 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Water Gallons Yield Pump No.

Authority per Day Source (Ft.) (In.)

12.

Gifford Pinchot 100,000 Pinchot Lake State Park 13.

Dover Borough

  1. 1 Well 30
  1. 2 Well 15
  1. 3 Well 30
  1. 4 Well 35
  1. 5 Well 21 14.

Gleneagles Water 50,000 Well 57 55 Company 15.

Mt. View Water 26,386 Well 23 23 Company 16.

Dover Township 143,000

  1. 1 Well 112 100 Authority
  1. 2 Well 201 100
  1. 3 Well 70 70
  1. 4 Well 50 50 17.

West Manchester 275,000 4 Wells Township Authority 18.

Ivan R. Lehr Well 89 45 Water Company 19.

Penvale Water 15,000 Well 75 75 Company 20.

Hallam Borough 60,000 8 Spring Authority 1 Well 100 21.

Jackson 2 Springs 20 Township Water District #1 22.

Pine Springs 25 houses 1 Well 300 125 Water Company 23.

New Salem

  1. 1 Well 19 Borough
  1. 2 Dug Well 10 Authority 100,000
  1. 1 Spring

TMI-1 UFSAR CHAPTER 02 2.6-35 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 9 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Water Gallons Yield Pump No.

Authority per Day Source (Ft.) (In.)

24.

Sylvan Hills 50 Homes Well 22 Development Water Works 25.

Windsor 65,000 8 Springs Water 2 Wells Authority 26.

Red Lion Cabin Creek Municipal Reservoir (50 MG)

Authority 27.

Red Lion Beaver Creek Municipal Reservoir (5.6 MG)

Authority 28.

Wrightsville 144,000 6 Springs Water Supply

  1. 1 Well Company Abandoned quarry 25 (5.5 acres, 140 MG) 150 filled by Susque-200 hanna River intake 29.

Dauphin 3,500,000 Stony Creek (2 acre Consolidated lake)

Water Company 30.

Linglestown 25 homes Well 60 50 Water Company 31.

Sky Line 170 homes Well 75 View Extension 32.

Annville 450,000 Springs Water Company 33.

Cleona 25,000 2 Springs from Water City of Lebanon Company

TMI-1 UFSAR CHAPTER 02 2.6-36 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 10 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Water Gallons Yield Pump No.

Authority per Day Source (Ft.) (In.)

34.

Dauphin 1,200,000 Open Quarry Consolidated (1 acre, 10 MG)

Water Company 35.

Gulf Oil 10,000

  1. 1 Well Company
  1. 2 Well (Turnpike
  1. 3 Well Service Area) 36.

Steelton Water 2,000,000 Susquehanna Company River 37.

Dauphin 1,700,000 Beaver Creek Consolidated (1.2 acre lake)

Water Well 753 700 Company 38.

Dauphin 2,000,000 Swatara Creek Consolidated (5 acre lake)

Water Company 39.

Cambelltown 700 people 9 Springs Water 1 Well 38 25 Company 40.

Mt. Gretna 12,000 Well Heights Water Company 41.

Mt. Gretna 25,000 Well 65 Camp Meeting Association 42.

Quentin 10,000

  1. 1 Well 60 Water
  1. 2 Well 80 Company 43.

Cornwall 270,000

  1. 1 Well Borough
  1. 4 Well 150 150 Municipal White Quarry Authority Tract Spring Freeman's Spring Saddler Run

TMI-1 UFSAR CHAPTER 02 2.6-37 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 11 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Water Gallons Yield Pump No.

Authority per Day Source (Ft.) (In.)

44.

Highspire 314,000

  1. 1 Well 100 Water
  1. 2 Well 150 Company
  1. 3 Well 250 2 Springs 45.

Carroll

  1. 1 Well 20 Acres Quarry (4.5 Development acres, 68 MG) 46.

Olmstead 1,000,000 Wells Air Force Base

47. - -

48.

Middletown 880,000

  1. 1 Well 600 Water
  1. 2 Well 575 435 Company 49.

Gulf Oil 15,000

  1. 1 Well Company
  1. 2 Well (Turnpike
  1. 3 Well Service Area)
  1. 4 Well 50.

Elizabethtown 500,000 7 Springs Water

  1. 1 Well Company
  1. 2 Well 50
  1. 3 Well 120 150
  1. 4 Well 400
  1. 5 Well 440 300 W. Br. Conoy Creek (1500 gal. pond)

Conewago Creek (emergency) 51.

Masonic Homes 250,000 7 Springs

  1. 3 Well (emergency)
  1. 4 Well
  1. 5 Well 405 250
  1. 6 Well 400

TMI-1 UFSAR CHAPTER 02 2.6-38 REV. 18, APRIL 2006 TABLE 2.6-2 (Sheet 12 of 12)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

DATA ON OTHER WATER SUPPLIES WITHIN A 20 MILE RADIUS Consumption Water Gallons Yield Pump No.

Authority per Day Source (Ft.) (In.)

52.

Rheems Water 40,000 Well 50 60 Company 53.

Mt. Joy Spring 600 Water Authority 54.

Mt Joy 700,000 Little Chickies Water Creek Authority 55.

Manheim Water 460,000 Reiffs Run Company Quarry (0.23 acres) 225 56.

Bainbridge 12,000

  1. 1 well 60
  1. 2 Well 60 57.

Shocks Mill 7,000 1 Well 20 18 58.

East Donogal 100,000 Glatfelter Springs Municipal Authority 59.

Marietta 380,000 Dugans Run (0.2 Water acre, 660,000 gal.

Company lake)

Wildcat Reservoir (0.36 acres, 1,000,000 gal. lake) 60.

Marietta

  1. 1 Well 550 300 Water
  1. 2 Well 700 300 Company Spring 50 61.

Columbia 2,000,000 Susquehanna River 10 62.

Lancaster, 8,000,000 Susquehanna River 100 City of 63.

Safe Harbor 25,000 Susquehanna River 64.

Holtwood 290,000 Susquehanna River 65.

Riverton 2,000,000 Conodoguinet Creek Consolidated Water Company 66.

Pa. Dept.

  1. 1 Well Agriculture
  1. 2 Well at Summerdale
  • Data not available

TMI-1 UFSAR CHAPTER 02 2.6-39 REV. 18, APRIL 2006 HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Table 2.6-3

TMI-1 UFSAR CHAPTER 02 2.6-40 REV. 18, APRIL 2006 HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

Table 2.6-4

TMI-1 UFSAR CHAPTER 02 2.6-41 REV. 18, APRIL 2006 TABLE 2.6-5 (Sheet 1 of 3)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

TABULAR PRECIPITATION FOR PMF - HYDROMET NO. 40 TOTAL DURATION (HOURS) 6 12 18 24 PERIODS (HOURS) 6 6

6 6

WILKES-BARRE WARNING:

18 HOURS 8.4 RAIN 24 HOURS 9.6 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 4.9 1.9 6.8 1.6 1.2 2.8 9.6 LEWISBURG WARNING:

18 HOURS 10.1 RAIN 24 HOURS 11.5 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 6.2 2.3 8.5 1.6 1.4 3.0 11.5 HARRISBURG WARNING:

18 HOURS 6.6 RAIN 24 HOURS 7.8 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 3.4 1.8 5.2 1.4 1.2 2.6 7.8

TMI-1 UFSAR CHAPTER 02 2.6-42 REV. 18, APRIL 2006 TABLE 2.6-5 (Sheet 2 of 3)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

TABULAR PRECIPITATION FOR PMF - HYDROMET NO. 40 TOTAL DURATION (HOURS) 30 36 42 48 PERIODS (HOURS) 6 6

6 6

WILKES-BARRE WARNING:

18 HOURS 8.4 RAIN 24 HOURS 9.6 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 1.0 0.8 1.8 0.8 0.6 1.4 3.2 12.8 LEWISBURG WARNING:

18 HOURS 10.1 RAIN 24 HOURS 11.5 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 1.1 0.9 2.0 0.8 0.6 1.4 3.4 14.9 HARRISBURG WARNING:

18 HOURS 6.6 RAIN 24 HOURS 7.8 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 1.1 0.9 2.0 0.7 0.7 1.4 34 11.2

TMI-1 UFSAR CHAPTER 02 2.6-43 REV. 18, APRIL 2006 TABLE 2.6-5 (Sheet 3 of 3)

HISTORICAL INFORMATION This information was accurate at the time the plant was originally licensed, but is not intended or expected to be updated for the life of the plant.

TABULAR PRECIPITATION FOR PMF - HYDROMET NO. 40 TOTAL DURATION (HOURS) 54 60 66 72 PERIODS (HOURS) 6 6

6 6

WILKES-BARRE WARNING:

18 HOURS 8.4 RAIN 24 HOURS 9.6 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 0.5 0.4 0.9 0.3 0.2 0.5 1.4 14.2 LEWISBURG WARNING:

18 HOURS 10.1 RAIN 24 HOURS 11.5 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 0.6 0.4 1.0 0.3 0.2 0.5 1.5 16.4 HARRISBURG WARNING:

18 HOURS 6.6 RAIN 24 HOURS 7.8 RAIN CUMULATIVE RAINFALL IN INCHES 6 HOUR 12 HOUR 24 HOUR 48 HOUR 72 HOUR 0.6 0.4 1.0 0.3 0.2 0.5 1.5 12.7

TMI-1 UFSAR CHAPTER 02 2.6-44 REV. 22, APRIL 2014 TABLE 2.6-6 (Sheet 1 of 1)

SUSQUEHANNA RIVER LEVEL VERSUS FLOW AT TMI ISPH Flow (cfs)

Level (feet) 125000 282.4 200000 284.2 250000 285.4 300000 286.4 350000 287.4 400000 288.3 450000 289.2 500000 290.0 550000 291.0 600000 292.1 650000 293.0 700000 293.9 750000 294.8 800000 295.8 850000 296.8 900000 297.8 950000 298.8 1000000 299.8 1050000 300.5 1100000 301.6 1150000 302.6 1200000 303.5 1250000 304.4 1300000 305.3 1350000 306.2 1400000 307.6 1450000 309.3 1500000 311.0 1550000 311.9 1600000 312.8 1625000 313.3 1650000 313.6 1700000 314.2 1750000 314.8

TMI-1 UFSAR CHAPTER 02 2.7-1 REV. 18, APRIL 2006 2.7 ENGINEERING GEOLOGY AND FOUNDATION CONSIDERATIONS 2.7.1 GENERAL Three Mile Island is located approximately 2.5 miles south of Middletown, Pennsylvania, at longitude 7643'30" west and at latitude 408' north. The reactor vessel coordinates are N300.827; E2,286,878, based on the Pennsylvania State coordinate system (UTM coordinates, Zone 18, 4,446,102 meters north, 353,062 meters east). It is one of the largest of a group of several islands in the Susquehanna River and is situated about 900 ft from the east bank. It is elongated parallel to the flow of the river, with its longer axis oriented approximately due north and south. The island is about 11,000 ft long and 1700 ft wide. This unit is located in the northern one third of the island.

The southeasterly flowing Susquehanna River makes a sharp change in direction, to nearly due south, in the vicinity of Middletown. After this directional change just north of Three Mile Island, the channel widens to approximately 1.5 miles.

The island on which the site is located is basically composed of fluvially deposited sand and gravel of adequate density to support moderately heavy loads. The underlying rock is a sedimentary sequence of interbedded sandstone, shaley siltstone, and shaley claystone which belongs to the Gettysburg Formation of Triassic Age. Below the weathered surface, bedrock is capable of safely bearing loads imposed by the heaviest structures (Reference 16).

A program of test borings and a seismic refraction survey, supplemented by field geology, photogeology, and a tectonic evaluation, have been employed to determine and evaluate the suitability of the geology at the site to support a nuclear powered generating station.

Groundwater occurs above the bedrock-soil interface and varies in response to fluctuating river levels. Foundation design includes the effect of such hydrostatic variations.

The site is not considered to be deleteriously affected by faulting, and it is concluded that regional tectonic elements are inactive and present no threat to the structural integrity of local geology.

Historically, earthquakes in Pennsylvania have been infrequent and of low intensity. The resultant intensity at the site of past quakes greater than 50 miles distance was between III and IV. The highest recorded intensity within a 50 mile radius of the site was modified Mercalli VI which was rapidly attenuated with distance from the epicenter. Assuming that the closest future earthquake activity would occur 5 to 6 miles north of the site at the Triassic Border Fault, which to this time has produced a maximum epicentral intensity of VI, the intensity would be attenuated to V at the site. If the focal depth is greater than the previous earthquakes, the intensity at the station site might approach the epicentral intensity and not be rapidly attenuated. Therefore, based on intensity at the site to be a low intensity VI, a ground acceleration of 0.04g should be expected, according to Figure 4 as referenced in Reference 21.

The design is conservatively based on a basic ground motion of 0.06g maximum.

Acceleration response spectra for the design earthquake were partially developed using records from the March 1957 San Francisco earthquake normalized to a basic ground motion of 0.06g. Data from this earthquake were recorded by an instrument located on rock in Golden Gate Park. The instrumented records provide valuable data on the attenuation of a moderate

TMI-1 UFSAR CHAPTER 02 2.7-2 REV. 18, APRIL 2006 earthquake occurring a short distance from the recording station. These field conditions are considered to best approximate those at the Three Mile Island site. The acceleration response spectra were further developed on the basis of the spectra for the 1940 El Centro earthquake, again normalized to a basic ground motion of 0.06g. The resultant spectra (Figure 2.7-1) therefore are controlled in the low frequency region by the El Centro Spectra.

Without qualification, the site is considered to be geologically competent to safely support a nuclear-powered generating station.

2.7.2 FIELD INVESTIGATION Supplemented by a ground surface survey team, aerial photographs, and a geologic surface investigation, a subsurface exploration program consisting of 21 borings in conjunction with a seismic refraction survey was initiated in August and September of 1966 to establish the general range of soil depths, types, and engineering properties, and to examine and evaluate the condition of the bedrock and depth of weathering (Figure 2.7-2). This work was done to ascertain the capabilities of the site to safely and economically support a nuclear-powered generating station.

The borings and seismic profiles covered the entire length of the island. From the initial interpretation of the longitudinal seismic line and accompanying borings, the general area of the island appearing to offer the best subsurface conditions was selected, and the seismic cross lines and additional borings were concentrated in that area.

In January 1967, 20 borings were added in the plant site area for further soil investigation and to obtain reliable water table information.

The Phase I drilling program consisted of continuous sampling of overburden using the Standard Penetration Method and coring (NX core) a minimum of 10 feet into sound rock.

Phase II drilling, in all but a few holes, consisted of continuous split-barrel soil sampling of overburden to bedrock and the installation of 3 inch slotted standpipes in drilled holes, comprising a system of groundwater observation points.

Forty eight additional borings were then taken in Phase III: 15 at the cooling towers, 12 at the Reactor Building, and 21 at other structure locations. These borings substantiated the conclusions drawn from the Phase I drilling program. Phase III drilling consisted of continuous split-barrel soil sampling of overburden to bedrock and core drilling into bedrock to various depths; the deepest hole penetrating 128 feet into rock.

A seismic survey was conducted (Reference 17). A twelve trace seismic refraction system with a recording oscillograph was used. Seismic energy was generated with explosives. Data were collected using two 100 foot long geophone spreads, with 20 foot geophone intervals and with three 10 foot intervals on both ends of the geophone spreads. The standard continuous profiling technique was used. In addition to end shots, two intermediate shot point determinations were made on each spread.

Seismic results were interpreted (Reference 17) and incorporated in the text of this report and on the soils profile, Figure 2.7-3. The location of the seismic lines and borings are shown on the boring location plan, Figure 2.7-4.

TMI-1 UFSAR CHAPTER 02 2.7-3 REV. 18, APRIL 2006 2.7.3 GEOLOGY 2.7.3.1 Geographic Setting The site lies within the Gettysburg Basin section of the physiographic division known as the Piedmont Province. The topography of the area immediately surrounding Three Mile Island is of a slightly undulating nature with maximum relief of about 200 feet and highest elevation seldom above 500 feet. From the east, drainage is largely represented by the southwesterly flowing Swatara Creek which has its mouth near Middletown, and by the more westerly flowing Conewago Creek which empties into the Susquehanna River at the south end of Three Mile Island. Fishing Creek flows into the Susquehanna west of the site, and the northeasterly flowing Conewago Creek terminates at York Haven. Three Mile Island has very little relief, with elevations ranging from about 280 feet at the water's edge to slightly more than 300 ft in the north central portion.

2.7.3.2 Regional Geologic History A geologic history of the Three Mile Island area was prepared (Reference 18), which summarized the regional structural, geologic, and tectonic aspects of this locale. The site is located in the Triassic lowland of Pennsylvania, one of a series of long narrow basins of Triassic deposits which extend in broken patches from Connecticut to North Carolina. The Triassic lowland in the vicinity of the site is referred to as the Gettysburg Basin. North and west of the Triassic lowland are the folded and thrust faulted Paleozoic rocks which comprise the Appalachian Mountains. Southeast of the Triassic lowland is the Piedmont, of Pre-Cambrian and Early Paleozoic Age, composed of granites, gneisses, and schists.

Reference 14 states after the late Paleozoic mountain making during which compression had been relieved by folding and overthrusting, large blocks of the region settled along nearly vertical joint planes, resulting in normal faulting and tilting of blocks, which formed a vast sunken basin or trough with a northeast trend and a highland to the southeast. In the following Triassic period torrential rains washed the waste from the disintegrated crystalline rocks of this highland into the trough, and arkosic sand, argillaceous sand and fine sandy mud accumulated.

Much of this sediment was of a pronounced red color, owing to the fact that the iron content of the rocks was highly oxidized when they disintegrated, apparently under acid conditions. After the accumulation of a thickness of many thousands of feet of these red rocks, which now form the Newark group, further adjustment of earth blocks by tilting and normal faulting, took place on a still larger scale than before, and in places mountains were formed on the northwest side of the basin by differential uplift of several thousand feet. Catoctin Mountain in Southern Pennsylvania is an example.

The Newark group is believed to have a thickness of approximately 16,000 feet and tilts toward the northwest. This is due to subsidence and faulting along the northwest border.

Later, intrusion of Triassic diabase dikes and sills cut through the Newark group and metamorphism took place along the edges of these intrusions. Since Triassic times an erosional period has been prevalent except for glacio-fluvial deposition from Pleistocene glacial advances. The farthest advance occurred during the Illinoian stage when a lobe of the glacier extended down the Susquehanna Valley to near Fisher's Ferry, approximately 45 miles north of Three Mile Island. Glacial meltwater was responsible for the deposition of some alluvial terrace deposits now present in the region.

TMI-1 UFSAR CHAPTER 02 2.7-4 REV. 18, APRIL 2006 The tectonic history of the area (Reference 18) indicates that the region has been extremely stable for at least the last 10,000 to one million years, and that studies did not establish the existence of minor faults or fractures at the site. Reference 18 concludes, "In the event that such inconspicuous features do exist, the probability of future movement along such zones is so small as to be negligible."

2.7.3.3 Depositional History Of Three Mile Island Three Mile Island, along with Shelley Island and other small islands in the vicinity, were formed as a result of fluvial deposition by the Susquehanna River. The carrying capacity of the river sharply decreases as the channel width increases after the stream crosses an east-west trending, very resistant diabase dike just downstream from Middletown. At this point the channel has been incised into the more easily erodable Gettysburg shale, resulting in a conspicuously wider channel. In addition, a change of flow direction occurs after the stream cuts through the diabase dike which crosses the river at that point (represented by Hill Island),

and is directed along N 10E striking vertical joints until it is again restricted and deflected by a second diabase dike just south of Three Mile Island.

Boulders carried by the glacial meltwater or transported downstream by ice rafts were first deposited in this wide-channel, low-velocity section of the river and became the nuclei for subsequent deposition of smaller materials. This gradual accretion of river sediment resulted in the growth of most of the islands in this area. Three Mile Island is made up of two such nuclei which eventually merged. This area between the two nuclei is presently represented by fine-grained deposits which were deposited in a low energy fluvial environment between the two growing depositional islands.

2.7.3.4 Bedrock Geology The site is underlaid by the sedimentary rocks of the Gettysburg shale, a part of the Newark group of Triassic Age. Two easterly trending diabase intrusions cut through the Gettysburg shale, one approximately 1 mile upstream from Three Mile Island and a second one about 0.2 miles downstream from the island. These more erosion resistant diabase dikes and the metamorphosed shales along their edge have caused restrictions in the river at Hill Island, north of the site and at Conewago Falls, downstream of the site.

The bedrock surface at the site is essentially flat and lies at approximately elevation 277 ft.

Lithologic types vary from red to brown, interbedded, fine to medium-grained sandstone, shaley siltstone, and shaley claystone which range from medium-hard to hard, possessing seismic velocities in a range from 8500 to 11,500 ft/sec. There is 1 to 3 ft of weathered rock at the overburden-bedrock interface.

The regional dip of the Gettysburg shale is to the northwest at 10to 50. Near the site, the attitude of these beds as measured in surface outcrop, varies from N 65to 80E with 35to 70northerly dips. This variation in inclination of strata was not apparent from drill cores, as a fairly consistent dip of 37.5to 45was observed in the subsurface of Three Mile Island.

Well developed, near vertical jointing is conspicuous along a N10E trend. Drill hole data substantiated surface observations regarding jointing, and revealed that healing of some joints has occurred, while others were altered by oxidation.

TMI-1 UFSAR CHAPTER 02 2.7-5 REV. 18, APRIL 2006 2.7.3.5 Faulting No evidence of faulting which transects the island was seen in the field from available rock exposures along the east bank of the river, or along the western periphery of the island. Aerial photographs give no suggestion of faulting through the island.

Reference 14 has mapped a hypothetical NE trending fault which they projected through Three Mile Island approximately 0.5 miles south of the site area. The substance for their structural geology was obtained by large scale surface mapping which was completed in 1929. Based on the data collected to date, this hypothetical fault does not exist. Likewise, these studies show no evidence to substantiate the projections of other hypothetical faults across the river immediately north and south of the island. The Triassic depositional basins were subjected to an appreciable degree of diastrophism during the Palisades disturbance. Most significant, however, is the fact that structural features resulting from such diastrophism are as much as 185 million years old, and that area has been extremely stable for the last 10,000 to 1 million years. In addition, rock velocities obtained from the seismic survey are normal to Triassic Gettysburg Formation rock types and indicate that the bedrock is not in a state of stress, thereby eliminating any latent threat of future strain.

A comprehensive evaluation of major tectonic elements in south central Pennsylvania was prepared as in Reference 18. It is concluded that the site is not deleteriously affected by faulting, and further, that regional tectonic elements are inactive and present no threat to the structural integrity of the local geology.

2.7.3.6 Soils The island, as a whole, is composed of fluvially stratified subrounded to rounded sand and gravel containing varying amounts of silt, clay, and occasional lenses of clean sand. Density values range from loose to very dense, as established by Standard Penetration Tests.

Boulders are presented at depth and are mainly confined to the lower portions of the soil zone on the north end of the island. Soil depths vary from approximately 6 ft at the south end of the island to a maximum of 30.0 ft near the axial intersection of the island. Depth of soil is relatively constant at about 20 ft in the vicinity of the plant site.

The overburden is made up primarily of two units. Directly overlying the sedimentary rocks is a layer of coarse sand and gravel which, at the north end of the island, contains numerous boulders and cobbles and ranges from medium dense to very dense.

Above the coarse sand and gravel is a layer of loose to medium dense, fine-grained granular material which varies from a fine silty sand and gravel, north of Station 13 + 00 (north) to a very stiff, clayey silt on the south end of the island.

Local variations do occur, and in some drill holes at the plant site, the amount of fines appeared slightly greater below a depth of about 10.5 ft. This variation is believed to be a function of a mechanical breakdown of individual shale and siltstone pebbles contained in the soil. From one half to one foot of topsoil, composed of sandy silt with much organic material, covers the island.

The island had been cultivated and planted into corn fields in past years.

TMI-1 UFSAR CHAPTER 02 2.7-6 REV. 18, APRIL 2006 2.7.4 GROUNDWATER HYDROLOGY 2.7.4.1 General Three Mile Island Nuclear Station is located on a large island in the Susquehanna River. Purely from the standpoint of geography, its groundwater conditions are unique, but relatively constant, and predictably controlled by the Susquehanna River itself. The drainage area of the Susquehanna River extends from its source at Otsego Lake, Cooperstown, New York, for a distance of 444 miles, across the states of Pennsylvania and Maryland, and terminates in the Chesapeake Bay. This major water course collects surface runoff and groundwater seeps as well as their respective contaminants from a watershed area of approximately 27,000 square miles. Three Mile Island is located in the lower third course of the river and therefore is influenced by the quantity and quality of that portion of the water from the Susquehanna River watershed upstream from the island. Average annual rainfall at the site is 40 inches.

2.7.4.2 Mode Of Occurrence The bedrock underlying the general area is composed of shales, sandstones, and siltstones belonging to the Gettysburg shale of Triassic Age. A wide range in yields occurs within the formation, with the sandstone facies normally being the best aquifers. However, in closely jointed or fractured shales, relatively high yields can occur. The alluvial deposits are not believed to be a major source of groundwater in this area.

2.7.4.3 Site Studies Groundwater was studied at the site by means of:

a.

Standpipes to record elevation and fluctuation of water levels, b.

A pumping-out test to determine permeability of the saturated soil, c.

A falling head permeability test to determine permeability of soil above the water table.

Groundwater at the site occurs under water table conditions. The water table reaches its maximum elevation at the highest topographic point in the center of the island and falls off toward both the east and west shores. A variation of only about 5 ft occurs from either side to the center producing a gradient of approximately 0.6 percent toward the river.

At twenty observation points in and surrounding the plant area, water levels occurred generally at a depth in excess of 15 ft and ranged from 14 to 19 ft. The groundwater level occurred at a maximum of 6.2 ft above the top of rock with less than 1 ft of head existing above the soil-rock interface at one point of observation.

The water level of the Susquehanna River, which normally flows at elevation 277 ft, controls Three Mile Island groundwater levels. A rapid rise in the river in response to a heavy rain and thawing of ice jams during January 1967 was seen to produce significant rises in the water levels of observation wells 200 ft from the water's edge. Since a positive head exists on the island, any movement of groundwater from the plant site would be toward either channel of the river, and would eventually enter the stream. The river would act as a natural boundary, limiting

TMI-1 UFSAR CHAPTER 02 2.7-7 REV. 18, APRIL 2006 the dispersal of groundwater from the island to the river. Two factors are important in considering the possibility of infiltration of groundwater into the underlying Gettysburg shale and transmission to onshore water supplies:

a.

A maximum positive head of 6 ft exists above the impervious (relative to the soils)

Gettysburg formation.

b.

Groundwater levels are higher on either shore of the river, with hydraulic gradients sloping toward the river.

In order for groundwater to move from Three Mile Island to the mainland, it would be necessary to reverse the hydraulic gradient on the mainland, which would necessitate partial dewatering of the Susquehanna River.

Further, it is unlikely that river water would ever significantly infiltrate rocks on either shore, except under sustained high capacity pumping, creating induced infiltration. A natural condition of river water flowing into the ground would not be normal to this climate and geography.

The length of time required for the groundwater to move to the river is problematical. Two types of tests were run, in an attempt to establish permeability of the soils overlying the bedrock. A pumping-out test was run on the eastern side of the island and the results determined indicated the permeability of the saturated soil zone to be on the order of 10-2 cm/sec. A falling head test was run in the center of the island which showed a coefficient of approximately 10-3 cm/sec. These results confirmed those permeabilities estimated from examining the continuous samples from the test borings. Some change in slope of the water table will occur due to the variations of the river level, and temporary minor reversal of groundwater movement will probably result during periods of high water or during periods of extended drought. Any additional impoundment of water in either channel would necessarily have an effect on the direction of groundwater movement and on the slope of the water table, but in any event the final discharge point would still be into the river.

2.7.4.4 Area Water Well Data Most of the data on groundwater wells in the Gettysburg shale came directly from the U.S.

Geologic Survey water supply paper on the groundwater resources of Harrisburg International Airport at Middletown (Reference 13). The airport is located approximately two and one half miles north of Three Mile Island.

The average strike of the formation in this area is N 43E with dips at angles varying from 19 to

38. The rock consists of alternating layers of fine to coarse-grained sandstone, siltstone, and shale.

Groundwater occurs under artesian conditions at the base. In 20 wells ranging from 300 to 800 ft in depth, specific capacities of the aquifers tapped ranged from 0.33 to 15.0 gpm/foot drawdown and transmissibilities varied from 1200 gpd per ft to somewhat less than 50,000 gpd per foot. The pH of wells tested ranged from 6.6 to 8.1, hardness from 137 to 826 ppm and dissolved solids from 200 to 1340 ppm. The Brunswick shale (the name applied to the eastern counterpart of the Gettysburg shale) and the Gettysburg shale were combined and included together in groundwater tabulations (Reference 15). Of 112 wells surveyed, the depths ranged from 18 to 500 feet, with an average depth of 157 feet. Yields ranged from zero to 300 gallons

TMI-1 UFSAR CHAPTER 02 2.7-8 REV. 18, APRIL 2006 per minute with an average yield of 41. Six analyses were included showing the range of total dissolved solids to be between 201 and 786 ppm, hardness from 152 to 499 ppm, and iron from 0.5 to 4.9 ppm. Since these are fairly deep rock aquifer wells where water chemistry is a function of mineralogy of the reservoir rocks, one should not expect the alluvial groundwater to be of similar chemical makeup.

2.7.5 FOUNDATION CONSIDERATIONS As set forth in Section 2.7.3.3, the subsurface of Three Mile Island indicates that it formed first as two islands which were later joined as a result of the fluvial cycle of the Susquehanna River.

Both nuclei have subsurface conditions which are favorable for safe, economic foundation design; however, the larger thickness of the uniformly dense to very dense sand and gravel layer at the north end of the island provides a better opportunity to utilize these dense soils as bearing materials and a greater opportunity to remain above the groundwater table. A plant built on the south end of the island would involve expensive rock excavations and definite dewatering costs. Also, a greater variation in the bedrock surface was detected by the seismic survey on the south end of the island, and inferences of greater variations in intensity of weathering were also noted in this area. The type of foundation, base elevation, and foundation medium for all Class I structures are listed in Table 2.7-1.

2.7.5.1 Soils There is a high degree of uniformity of density and of soil types at the plant location, within the upper silty sand layer and the lower sand and gravel layer.

Both layers are capable of supporting foundation loads which will greatly increase with increasing depth. The actual bearing capacity of each soil layer is dependent upon the depth, size, and spacing of footings, and is greatly influenced by the elevation of the ground water table. The bearing capacity of footings placed in the lower sand and gravel layer can conservatively be permitted within a range of 5 to 8 kips per square foot (ksf), but can be considerably increased depending upon the above variables. For instance, a square footing 10 ft wide at a depth of 10 ft can be considered to safely support 14 ksf if it remains a sufficient distance above the water table, and half of that value at the water table.

Field explorations have established that the top of dense to very dense granular overburden material (in excess of 30 blows per foot (bpf) - Standard Penetration Test (SPT) at the plant site ranges from elevation 284.5 to 289.5 ft, while at the cooling towers the elevation of this horizon varies from 283.0 to 294.0 ft.

The top of the granular material with blow counts in excess of 20 bpf - spt varies from 288.6 to 295.4 ft at the cooling towers and at the plant site from 295.0 to 298.7 ft.

2.7.5.2 Rock The fact that the bedrock surface is differentially weathered necessitates a variation in the surface bearing capacity, and points out the need for assuring that any structure supported by rock be firmly established on sound rock. For preliminary planning and estimating purposes, the sound rock surface was assumed to be represented by the seismic top of rock line, defined by a compressional wave velocity of 10,000 ft/sec, shown on Figure 2.7-3, and the bearing

TMI-1 UFSAR CHAPTER 02 2.7-9 REV. 18, APRIL 2006 capacity of rock to support any given foundation at a constant elevation was assumed to be equal to a maximum of 30 ksf.

Since bedding dips at approximately 45 degrees to the horizontal, the heavily loaded foundations (those in excess of 10 ksf) were not placed up dip from sides of excavations. The shearing strength of rock parallel to unconfined bedding planes is significantly smaller than the compressive strength of the rock perpendicular to bedding planes. Also, due to the combination of vertical jointing and moderately dipping bedding planes which afford potential shear surfaces, the high differentially loaded foundations were not placed at shallow depths.

Under conditions of even loading at constant elevation, the unweathered rock at Three Mile Island is capable of safely sustaining maximum loading of 30 ksf.

At the cooling tower locations, the top of rock elevation varies from 270.5 ft to a maximum elevation of 276.2 ft. At the Reactor Building and other main structures, the top of rock varies from elevation 275.0 to 279.5 ft.

All Class I structures founded on bedrock were excavated to sound rock. Wherever necessary concrete fill was placed on top of the rock to the base elevation listed in Table 2.7-1.

The following test data were obtained on BX core samples which were sealed in cheesecloth and wax to preserve natural water until laboratory tests could be performed.

Five representative samples were tested in unconfined compression and one sample in consolidated, undrained triaxial compression. The triaxial compression test was performed with a cell pressure of 50 psi. All compression test samples, having a diameter of approximately 1.65 +/- 0.02 in were trimmed into lengths of 3.03 +/- 0.02 in by means of a diamond saw prior to testing.

Three unconfined compression tests were carried to failure using a rate of strain of 0.025 in/min. The remaining unconfined compression tests and the triaxial compression test were terminated at a compressive load usually in the order of 100 tons per square foot (tsf).

Unload-reload cycles were carried out in four of the tests with stress excursions below the elastic limit.

The pertinent physical, strength, and elastic property test data are tabulated on the summary of laboratory test results in Table 2.7-2. It is noted that the First Load, Secant Modulus (Ec) of the test specimens averaged 0.6 x 103 ksi and that the Second Load (reload), Secant Modulus (E) averaged 1.35 x 103 ksi, based on five and four tests, respectively. The average unconfined compressive strength of the three test specimens which were loaded to failure was 87.4 tsf.

No significant difference was noted between an unconfined and triaxial test performed on specimens trimmed from the same core sample. This finding is noted to be consistent with the relatively small confining pressure utilized during triaxial testing.

The allowable bearing capacity used for the design of the foundations on rock has been determined based upon the average unconfined compressive strength of the rock.

TMI-1 UFSAR CHAPTER 02 2.7-10 REV. 18, APRIL 2006 The factors of safety used to determine the allowable bearing stress were as follows:

30 ksf, for normal load: F.S. = 6 60 ksf, for factored load: F.S. = 3 90 ksf, for extreme load: F.S. = 2 (airplane impact)

The soils and rock are capable of safely supporting the anticipated design loads at the proposed elevations.

2.7.5.3 Groundwater Groundwater levels were recorded in detail around the plant site and vary from 279.0 to 282.0 feet with elevation and distance from the river. Assuming that the river is maintained at elevation 277 feet, the groundwater levels should vary little from those presently observed.

However, flood studies indicate a mean annual flood at the 286 feet elevation with 5, 10, 25, and 30 year flood predicted at 288.0, 290.0, 291.5, and 292.5 feet, respectively.

Deep excavations were dewatered by pumping from shallow sumps. Hydrostatic pressures were considered in the foundation design.

TMI-1 UFSAR CHAPTER 02 2.7-11 REV. 19, APRIL 2008 TABLE 2.7-1 (Sheet 1 of 2)

FOUNDATIONS FOR CLASS I STRUCTURES Type of Base Foundation Structure Foundation Elevation Medium Reactor Building Mat 270 ft Bedrock Auxiliary Building Mat 278 ft Bedrock Fuel Handling Building Mat 276 ft 6 in Bedrock Control Building Continuous foot-278 ft Bedrock ings under walls.

Square footings under columns.

Diesel Generator Building Mat 303 ft Compacted Backfill Intermediate Continuous 277 ft Bedrock Building footings under walls.

Intake Building Mat 259 ft 6 in Bedrock 262 ft 6 in Heat Exchanger Vault Mat 267 ft 6 in Bedrock Access Tunnel Vault to Auxiliary Mat 279 ft Bedrock Building Air Intake Structure Mat 266 ft Bedrock 278 ft

TMI-1 UFSAR CHAPTER 02 2.7-12 REV. 19, APRIL 2008 TABLE 2.7-1 (Sheet 2 of 2)

FOUNDATIONS FOR CLASS I STRUCTURES Type of Base Foundation Structure Foundation Elevation Medium Foundations for Storage Tanks:

Borated Water Sodium thiosulfate (1)

Mat 300 ft Compacted Sodium hydroxide (1)

Backfill Emergency Feedwater Mat 300 ft 11 in Compacted System Condensate Backfill Underground Diesel Mat 283 ft 6 in Compacted Fuel Backfill (1) - The Sodium Thiosulfate and Sodium Hydroxide Tanks are isolated from the DH and BS Systems.

TMI-1 UFSAR CHAPTER 02 2.7-13 REV. 18, APRIL 2006 TABLE 2.7-2 (Sheet 1 of 1)

SUMMARY

OF LABORATORY TEST RESULTS Comprehensive Boring Sample RB-1BX/1 RB-1BX/2 RB-1BX/3 RB-1BX/2A RB-1BX/3A Sample 30.0-30.7 33.4-34.1 44.6-45.0 33.4-34.1 44.6-45.0 Depth (ft)

Water 0.85 0.82 0.92 0.90 0.94 Content (%)

Dry 168.3 167.9 167.0 166.0 166.1 Density (psf)

Elastic Modulus E(psi) 0.67x106 0.50x106 0.62x106 0.90x106 0.30x106 E(psi) 1.6x106 1.2x106 1.3x106 1.3x106 Strength 90.7 91.6 82.9 (tsf)

Type Chisel-Chisel-Chisel-Failure Shattered Shattered Shattered

TMI-1 UFSAR CHAPTER 02 2.8-1 REV. 18, APRIL 2006 2.8 SEISMOLOGY A seismicity and response spectra was conducted and is represented in Reference 19.

2.8.1 SEISMICITY The seismicity analysis indicated that Pennsylvania is relatively inactive seismically, based upon 200 years of historical data and 40 years of instrumental data. Earthquakes in the greater Pennsylvania area, which have or might have affected the site, were studied and their intensity at the site was determined by attenuation of the earthquake with distance.

Earthquakes which have affected the site were studied in two categories, those within a 50 mile radius of the site, and those beyond this radius. Nearly all the earthquakes considered were felt over very limited areas, which are generally elliptical in shape, and aligned with the general structural trend of the area. The high attenuation of these earthquakes indicates that their foci must have been close to the earth's surface.

An estimate of the maximum expected intensity of an earthquake was predicated on the assumption that the activity which would affect the site would originate along the border fault of the Triassic Lowland, five to six miles north of the site. The highest intensity earthquake to occur on this fault has been modified Mercalli VI. The intensity of such an earthquake at the site would be V, based upon the rapid attenuation of similar earthquakes in the area and along the fault. Consideration was given, however, to the future occurrence of an earthquake at a greater depth in the fault, with a conservative assumption that the resulting intensity at the site could approach the epicentral intensity, and not be rapidly attenuated.

The conservative estimate of the maximum earthquake intensity to be expected at the site is a low intensity VI. Using relationships published in Reference 21, this intensity corresponds to a ground acceleration of 0.04g. The design is conservatively based on a basic ground motion of 0.06g maximum.

2.8.2 ACCELERATION RESPONSE SPECTRA The objective of this study was to establish an acceleration response spectra corresponding to a possible earthquake of low intensity VI (Modified Mercalli), as established by the seismicity analysis.

Figure 2.7-1 indicates the average smooth response spectra derived from the ground motions of the 1957 Golden Gate Park, San Francisco earthquake together with the revised acceleration spectra reflecting the greater response at lower frequencies based upon the 1940 El Centro spectra. The resulting acceleration response spectra (Figure 2.7-1) were developed as described in Subsection 2.7.1.

TMI-1 UFSAR CHAPTER 02 2.9-1 REV. 18, APRIL 2006 2.9 GEOLOGIC GLOSSARY 2.9.1 GENERAL Alluvial Stream transported Aquifer A water producing geologic unit Artesian water Groundwater that rises above the level at which it is encountered Bedrock Rock underlying soil, sand, clay, boulders, etc.

Diastrophism The process of deformation of the earth's crust Dike A tabular body of igneous rock that cuts across the structure of adjacent rocks or cuts massive rocks Decomposition Breakdown and decay of rock to soils condition Dip The angle at which a stratum or any planar feature is inclined from the horizontal Fault A break in rock along which there has been displacement of the two sides relative to one another parallel to the break Fluvial Produced by river action Folds Bends in the strata Footwall Rock below a fault plane Fractures Breaks in rock due to folding or faulting Groundwater Subsurface water in the zone of saturation Hanging wall Rock above a fault plane Ice raft Floating ice which transports rock particles and other materials Intrusion An invasion of older rock by igneous rock Joint A fracture or parting along which little or no movement has occurred parallel to the fracture Lithology Composition and texture of rock NX Core size - 2.155 inches Overburden Soil, sand, gravel, boulders, etc., that overlie bedrock

TMI-1 UFSAR CHAPTER 02 2.9-2 REV. 18, APRIL 2006 Overthrust In faulting, the process of thrusting the hanging wall (relatively) over the footwall Sandstone Sandstones are composed of cemented grains of sand-size material Shale A laminated sediment, composed predominantly of particles of clay size Siltstone A very fine grained clastic rock composed predominantly of particles of silt size Tectonics The study of the structure of the earth in response to earth movements Water table The upper surface of a zone of saturation Weathering Mechanical and chemical action on rocks which eventually reduces them to a soil state 2.9.2 HARDNESS CRITERIA Rock hardness as indicated on the boring logs is a qualitative property determined by field classification, and is used as an aid in analyzing general subsurface conditions. Actual rock hardness is difficult to define; therefore, an arbitrary method of hardness determination was defined by the following criteria:

Very soft Rock disintegrates to touch; exhibits destructive alteration; can be considered as hard to very hard soil.

Soft Rock is coherent but is broken very easily by thumb pressure at sharp edges and crumbles with firm hand pressure. Exhibits partial alteration.

Medium hard Rock appears to be relatively hard, but small pieces can be broken by considerable hand pressure. Usually exhibits high degree of oxidation.

Hard Rock cannot be broken by thumb pressure. May exhibit minor oxidation (i.e., some oxide staining or discoloration, etc.).

Very hard Rock broken with difficulty by hammer. Exhibits no effects from weathering.

TMI-1 UFSAR CHAPTER 02 2.10-1 REV. 22, APRIL 2014 2.10 REFERENCES 1.

Annual Review of Aircraft Accident Data, U.S. Air Carrier Operations, National Transportation Safety Board, calendar years 1978 through 1987.

2.

U.S. Weather Bureau, Office of Climatology, Tornado Listings by Year, 1917-1963, and U.S. Department of Commerce, ESSA, Storm Data, 1966-June 1969.

3.

Thom, H.C.S., "Distributions of Extreme Winds in the United States," ASCE Proceedings, April 1960.

4.

Huss, P.O., "Relation Between Gusts and Average Wind Speeds," Daniel Guggenheim Airstrip Inst., Report No. 140, Akron, Ohio, 1946.

5.

Gifford, F.A., "Consequences of Activity Release," Nuclear Safety, 2 (2), p. 57 (1960).

6.

Pasquill, F., "Estimation of the Dispersion of Windborne Material," Meteorology Magazine 90, (1963) pp. 33-49, February 1961.

7.

Slade, D.H., "Estimates of Dispersion from Pollutant Releases of a Few Seconds to 8 Hours in Duration," Environmental Science Services Administration, Technical Note 39 -

ARL-3, April 1966.

8.

Deleted.

9.

Deleted.

10.

Deleted.

11.

Deleted.

12.

Commonwealth of Pennsylvania, Department of Forests and Waters, Water Resources Bulletin No. 1, Pennsylvania Streamflow Characteristics, Low Flow Frequency and Flow Duration, prepared in cooperation with U.S. Department of Interior, Geological Survey, April 1966.

13.

Meisler, H. and Longwill, S.M., Groundwater Resources of Olmstead Air Force Base, Middletown, Pennsylvania, U.S. Geological Survey Water-Supply Paper 1539-H, 1961, U.S. Government Printing Office, Washington, D.C., 34 pp.

14.

Stose, G.W. and Jonas, A.E., Geology and Mineral Resources of the Middletown Quadrangle, Pennsylvania, U.S. Printing Office, Washington, D.C., 86 pp.

15.

Hall, G.M., Groundwater in Southeastern Pennsylvania, Pennsylvania Geological Survey Bulletin W-2; 1934, 255 pp.

16.

Gray, C., Geologic Map of Pennsylvania, Pennsylvania Geological Survey Map #1, 1960.

TMI-1 UFSAR CHAPTER 02 2.10-2 REV. 22, APRIL 2014 17.

Sexton, T.F., Seismic Survey, Three Mile Island, Pennsylvania, Weston Geophysical Engineers, Inc., Weston, Massachusetts, September 9, 1966; USAEC Docket No.

50-289, Three Mile Island Nuclear Station, Unit 1 Preliminary Safety Analysis Report.

18.

Kauffman, M.E., Geologic Investigation of Three Mile Island and Vicinity, January 14, 1967; USAEC Docket No. 50-289, Three Mile Island Nuclear Station, Unit 1 Preliminary Safety Analysis Report.

19.

Holt, R.J., Seismicity and Response Spectra Analysis, Proposed Nuclear Power Plant, Three Mile Island, Susquehanna River, Pennsylvania, Weston Geophysical Research, Inc., January 19, 1967; USAEC Docket No. 50-289, Three Mile Island Nuclear Station, Unit 1 Preliminary Safety Analysis Report.

20.

Snyder, F.F., "Hydrology of Spillway Design: Large Structures - Adequate Data," Journal of the Hydraulics Division, Proceedings of the ASCE, Volume 90, No. HY3, May 1964, Part I, p. 239.

21.

US Nuclear Regulatory Commission, Nuclear Reactors and Earthquakes, TID 7024 22.

Annual Review of Aircraft Accident Data, U.S. General Aviation, National Transportation Safety Board, calendar years 1986 and 1987.

23.

Jane's, All the Worlds Aircraft, 1967-68 and 1990-91 Editions.

24.

Gilbert/Commonwealth, Inc., Report 2661, Review of Low River Flow Hydraulic Analyses, June 1987.

25.

Gilbert/Commonwealth, Inc., Report 2744, Reevaluation of River Flow Hydraulics, April 1988.

26.

U.S. Army Corps of Engineers (Baltimore District), Emergency Plan for Raystown Lake, Susquehanna River Basin, Raystown Branch Juniata River, September 1986.

27.

Pennsylvania Dept. of Environmental Resources, Water Resources Bulletin, No. 6, December 1970.

28.

USGS Water Resources Data - Pennsylvania, Water Year 1987, Volume 2.

29.

Evacuation Travel Time Estimates for the Three Mile Island Nuclear Generating Station Plume Exposure Pathway Emergency Planning Zone, Final Report February 1994.

30.

Caves, J. L. (Parsons Power Group Inc.), Report 9708, Susquehanna River Hydraulic Study, May 1997.

31.

Caves, J. L. (Parsons Power Group Inc.), Report 9708, Rev. 1, Susquehanna River Hydraulic Study, June 1998.

32.

PLG File No. G98TM-4L, Accident X/Q Values for TMI-1, Keith Woodard to Ken Boughton, dated July 23, 1998.

TMI-1 UFSAR CHAPTER 02 2.10-3 REV. 22, APRIL 2014 33.

GPU Nuclear Calculation C-1101-826-E540-020, Atmospheric Transport X/Qs Using ARCON96 Code - Control Room Habitability.

34.

GPU Nuclear Calculation C-1101-826-E540-025, X/Q @ TMI Ventilation Exhaust Opening.

35.

Three Mile Island Unit 1 Nuclear Generating Station Easement License and Attachment Agreement By and Among Jersey Central Power & Light Co., Metropolitan Edison Co.,

PA Electric Co., as Sellers, and AmerGen Energy Co., LLC, as Buyer, Dated December 20, 1999.

36.

Exelon Nuclear Design Analysis C-1101-826-E410-030, Additional Onsite X/Q Values for Alternate Source Term Application.

37.

Analysis of Three Mile Island Area Hydrographic Survey, TMI Report No. 90-3071 (Parsons E&C Report No. 53753307-CE-DR-1), November, 2005, prepared by: J.L.

Caves, Spotts, Stevens and McCoy, Inc. and approved by C. Ricket, Worley Parsons.

38.

C-1101-122-E410-003, Rev 0, "River stage discharge and discharge frequency analysis."

39.

990*3093, Susquehanna River PMF Sensitivity Evaluation, AMEC Letter 10-14-2011.