Forwards LERs 80-016/03L-0,80-064/03L-0,80-065/03L-0 & 80-025/03L-0
Date released: 12/10/2018 Download: ML18139A602


LER 80-025/03L-0:on 801003,w/Unit 2 at 100% Power,Periodic Test 27D Revealed That Amperage for Circuit 2A Panel 10 Was Below Acceptance Criteria.Caused by Damaged Heat Tracing Tape.Verified That Redundant Circuit Was Operable
ML18139A755
Person / Time
Site: Surry 
Issue date: 10/16/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A755 (2)
LER 80-065/03L-0:on 800917,w/unit at Refueling Shutdown, MOV-SW-103B Did Not Operate Electrically During Flush of Recirculation Spray Heat Exchangers.Cause Undetermined,But Marine Growth Suspected.Valve Manually Cycled
ML18139A754
Person / Time
Site: Surry 
Issue date: 10/16/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A754 (2)
LER 80-064/03L-0:on 800916,w/Unit 1 at Cold Shutdown & Unit 2 at 100% Power,Auxiliary Bldg Filter Banks Found to Be Less Efficient than Required.Caused by Settling of Charcoal in Filters.Filters Replaced
ML18139A604
Person / Time
Site: Surry 
Issue date: 10/16/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A604 (2)
LER 80-016/03L-0:on 800916,w/unit Operating Steady State at 100% power,TV-SS-201B Would Not Remain Closed When Control Switch Was Released.Cause Undetermined.Inside Trip Valve Closed & Air Secured to TV-SS-201B
ML18139A603
Person / Time
Site: Surry 
Issue date: 10/16/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A603 (2)
Forwards LERs 80-016/03L-0,80-064/03L-0,80-065/03L-0 & 80-025/03L-0
ML18139A601
Person / Time
Site: Surry 
Issue date: 10/16/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A601 (1)