APPENDIX B NOTICE OF DEVIATION Virginia Electric and Power *company Surry License Nos. DPR-32

& DPR-37 Based on the results of the U.S.' Nuclear Regulatory Commission inspection conducted on October 1-31, 1979, certain of your activities appear to deviate from your com-mitments to the Commission as indicated 1below:

Tabl,.e E-.3 in Part IV of the Surry Fire Protection Systems Review and revisions t,tates that the specified portable fire extinguishers are installed and main-tained in accordance with NFPA 10, which requires monthly inspections (Section 4-3.1).

Contrary to the above, on October 25, 1979, one of the two portable fire extinguishers in each of the Safeguards valve pit areas for Units 1 aµd 2 were found not inspected. since January 1979 (Fire Extinguishers f/94 and fl13i).