Forwards IE Info Notice 79-37, Cracking in Low Pressure Turbine Discs. No Response Required
ML18136A430
Person / Time
Site: Surry, North Anna  
Issue date: 12/28/1979
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Proffitt W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
References
NUDOCS 8001250141
Download: ML18136A430 (9)


Text

,..

  • e UNITED STATES NUCLEAR REGULATORY COMMISSION REGION II Virginia Electric and Power Company Attn:
w. L. Proffitt Senior Vice President, Fower P. 0. Box 26666 Richmond, Virginia 23261 Gentlemen:

This Information Notice is provided as an early notification of a possibly significant matter. It is expected that recipients will review the information for possible applicability to their facilities.

No specific action or response is requested at this time.

If NRC evaluations so indicate, further licensee actions may be requested or required.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

Enclosures:

1.

IE Information Notice No. 79-37

2.

List of Recently Issued IE Information Notices Sincerely, Director 8 0 0 1 25 0 14/

1}0.,

Virginia Electric and Power Company cc w/encl:

W.R. Cartwright, Station Manager Post Office Box 402 Mineral, Virginia 23117 P. G. Perry Senior Resident Engineer Post Office Box 38 Mineral, Virginia 23117 W. L. Stewart, Manager Post Office Box 315 Surry, Virginia 23883 I)

-2~

UNITED 'STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 December 28, 1979 I SINS NO. :

6870 Accession No.:

7910250525 IE Information Notice No. 79-37 CRACKING IN LOW PRESSURE TURBINE DISCS Description of Circumstances:

An anonymous letter was received by the Director of the Office of Inspection and Enforcement, on November 17, 1979 which alleged possible violation o~ Part 10 CFR 50.55e and/or 10 CFR 21 Regulations concerning reportability of recently discovered stress corrosion cracking in Westinghouse 1800 rpm low pressure turbine discs.

Westinghouse had made a presentation on the turbine disc cracking to electric utility executives on October 30, 1979.

Telephone discussions between the NRC staff and Westinghouse's Turbine Division on November 20, 1979 established that cracking, attributed to stress corrosion phenomena, had been found in the keyway areas of several LP turbine discs at operating plants and that inservice inspection techniques (i.e., in situ ultra-sonic examination) for crack detection have been developed and are being imple-mented in the field.

The Office of Inspection and Enforcement was also notified on November 20, 1979 that during the current overhaul of Commonwealth Edison's Zion Unit 1 LP turbine, ultrasonic examination revealed embedded cracks located on the inlet side on the disc bore area where no cracks had been previously observed.

Ultrasonic measurements indicate this disc bore cracking is of greater depth than the keyway cracks found to date.

According to Westinghouse, these bore cracks have been metallurgically examined and preliminary findings show them not to be typical of classical stress corrosion cracking observed in the keyways.

The probable cracking mechanism and impact on disc integrity is being further evaluated by Westinghouse.

A meeting was held on December 17, 1979 between the NRC staff, Westinghouse and utility representatives to discuss the disc cracking problem, repair alter-natives, turbine missile evaluation, inspection techniques and plant inspection priorities.

In response to the staffs' request, Westinghouse provided the staff an updated report on December 21, 1979 regarding the current field inspection program that included a list of nuclear power plants already inspected, recom-mended inspection schedules and pertinent information related to LP turbines where cracks have been observed.

Inspections to date have identified turbine disc cracks at Surry Unit 2, Point Beach Unit 2, Palisades, Indian Point Unit 3 and Zion Unit 1. All units except Point Beach Unit 2 will make repairs before the plants return to power.

Point Beach returned to power on December 23, 1979 with a small crack in the No. 2 disc of LP Turbine No. 2.

An analysis by Westinghouse indicated that the observed crack will not attain critical dimensions during 28 additional months of turbine operation.

The NRC staff is evaluating the turbine inspection results and analysis by Westinghouse.

IE Information Notice No. 79-37 December 28, 1979 Page 2 of 2 Westinghouse also notified the staff that extrapolation of information obtained from Indian Point Unit 3 inspection and analysis indicates that disc cracking could be significant at Indian Point Unit 2 and the turbines should be inspected sooner than the spring outage of 1980.

The NRC staff is currently reviewing Consolidated Edison's plans for prompt evaluation of this potential problem at this unit. lists the PWR plants having Westinghouse 1500/1800 rpm turbines.

The AA category represents those turbines which appear to have the earliest need for inspection.

With the exception of Yankee Rowe, Westinghouse has recommended to utilities that inspection of these machines be completed by the Spring 1980 outage period.

The Rowe unit is uninspectable by the present ultrasonic techniques due to its design.

Westinghouse has recommended the remaining machines of the Category A plants be inspected as their service periods approach five years or in th~ event significant corrosion problems become evident during this time.

The NRC staff is currently reviewing the need for inspection of those PWR plants having other interfacing turbine designs shown in Enclosure 2.

Changes to the forementioned inspection schedules proposed by Westinghouse may be necessary as new technical information becomes available.

From the information available to the NRC staff at this time it appears that cracking may be more generically widespread in turbine discs (e.g., keyways and bore areas) than previously observed.

It is important to note that the UT inspections performed by Westinghouse thus far were essentially limited to the keyways (disc outlet) of selected discs whereas the Zion Unit 1 inspection results indicate that examination of the disc bore section must be taken into account.

Also, Westinghouse is currently re-evaluating their previously estimated turbine missile energies based on recent missile test results from model symmetric and non-symmetric missile impact tests.

Their preliminary findings, although subject to change, now indicate possible higher missile exit energies in some cases than previously expected.

This Information Notice is provided as an early notification of a possibly significant matter, the allegations and the generic safety implications of which are currently undergoing review by the NRC staff. It is expected that recipients will review the information applicable to their facilities. If NRC evaluations so indicate, further licensee actions may be requested or required.

Embedded cracking in keyways and disc bore areas have been observed only in Westinghouse LP turbines thus far.

However, the NRC staff believes that turbines of other manufacturers should be included in consideration of this problem.

. No written response to this Information Notice is required. If you have any questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

Enclosures:

As stated

/

l UTILITY Florida, P&L Consolidated ED.

PASNY Arkansas P&L VEPCO Carolina P&L So. Calif. Ed.

Yankee A.P.

Wisc. Mich. Pwr.

Consumers Pwr.

Commonwealth Ed.

Commonwealth Ed.

Florida P&L Nebraska PPD Wisc. Mich. Pwr.

Maine Yankee Rochester G&E Northern States Wisc. P.S.

CATEGORY AA STATION Turkey Point Indian Point Indian Point Russellville Surry Robinson San Onofre Rowe Point Beach Palisades Zion 1 Zion 2 Turkey Point Cooper Point Beach Bailey Point Ginna Prairie Island Kewaunee e

UNIT 3

2 3

1 1

2 1

1 1

1 1

2 4

1 2

1 1

1 1

  • (Co~tinued)

UTILITY Alabama Power Alabama Power Baltimore G&L Carolina P&L Carolina P&L Carolina P&L Carolina P&L Cincinnati G&E Commonwealth Ed.

Commonwealth Ed.

Commonwealth Ed.

Commonwealth Ed.

Connecticut Yankee Duke Power Duke Power Duquesne Lt.

Duquesne Lt.

Duquesne Lt.

Flordia Power Flordia Power Flordia Power Houston L&P Houston L&P Louisiana P&L Corp.

& Lt.

& Lt.

Metrppolitan Ed.

Northern States Pwr.

Pub. Service E&G Pub. Service E&G Pacific G&E Pacific G&E CATEGORY A STATION Farley Farley Calvert Cliffs Harris Harris Harris Harris Zimmer Byron Byron Braidwood Braidwood Haddam Neck McGuire McGuire Shippingport Beaver Valley Beaver Valley Crystal River St. Lucie St. Lucie So. Texas So. Texas Waterford Three Mile Island Prairie Island Salem Salem Diablo Canyon Diablo Canyon UNIT 1

2 2

1 2

3 4

1 1

2 1

2 1

1 2

1 1

2 3

1 2

1 2

3 2

2 1

2 1

2 Page 2 of 3

e (Continued)

Page 3 of 3 CATEGORY A UTILITY STATION UNIT P.S. Indiana Marble Hill 1

P.S. Indiana Marble Hill 2

Puget Sound P&L Skagit 1

SMUD.

Rancho Seco 1

TVA Sequoyah 1

TVA Sequoyah 2

TVA Watts Bar 1

TVA Watts Bar 2

VEPCO North Anna 1

VEPCO North Anna 2

VEPCO North Anna 3

VEPCO North Anna 4

VEPCO North Anna 2

WPPSS Hanford 2

11 WPPSS WNPS 1

WPPSS WNPS 3

WPPSS WNPS 4

WPPSS WNPS 5

UTILITY Duke Power Co.

Duke Power Co.

Duke Power Co.

OPPD e

Baltimore Electric

& Gas Metropolitan Edison Indiana & Michigan Electric Indiana & Michigan Electric Northeast Utilities Portland General Electric Toledo Edison Arkansas Power &

Light WPPSS STATION Oconee Oconee Oconee Ft. Calhoun Calvert Cliffs Three Mile Island D.C. Cook D.C. Cook Millstone Trojan Davis Besse Arkansas Nuclear Hanford UNIT 1

2 3

1 1

1 1

2 2

1 1

One 2

1

IE Information Notice No. 79-37 December 28, 1979 In.formation Notice No.

79-37 79-36 79-35 79-34 79-33 79-32 79-31 79-30 79-29 79-28 79-27 79-12A RECENTLY ISSUED IE INFORMATION NOTICES Date Subject Issued Cracking in Low PresBure 12/28/79 Turbine Discs Computer Code Defect In 12/31/79 Stress Analysis of Piping Elbow Control of Maintenance and 12/31/79 Essential Equipment Inadequate Design of Safety-12/27/79 Related Heat Exchangers Improper Closure of Primary 12/21/79 Containment Equipment Access Hatches Separation of Electrical 12/21/79 Cables for HPCI and ADS Use of Incorrect Amplified 12/13/79 Response Spectra (ARS)

Reporting of Defects and 12/6/79 Noncompliances, 10 CFR Part 21 Loss of NonSafety-Related 11/16/79 Reactor Coolant System Instrumentation During Operation Overloading of Structural 11/16/79 Elements Due to Pipe Support Loads Steam Generator Tube 11/16/79 Ruptures At Two PWR Facilities Attempted Damage To New 11/9/79 Fuel Assemblies Enclosure Issued To All holders of power reactors OLs and CPs All holders of power reactor OLs and CPs All holders of power reactor OLs and CPs.

All holders of power reactor OLs and CPs All holders of power reactor OLs and CPs All power reactor facilities holding OLs and CPs All power reactor facilities holding OLs and CPs All power reactor facilities holding OLs and CPs and vendors inspected by LCVIP All power reactor facilities holding OLs or CPs All power reactor facilities with an 01 or CP All power reactor facilities holding OLs and CPs All Fuel Facilities, research reactors, and power reactors with an OL or CP