Mr. Leon R. Eliason Chief Nuclear Officer & President-Nuclear Business Unit Public Service Electric and Gas Company Pest Office Box 236 Hancocks Bridge, NJ 08038 rTarch 21, 1996 e

SUBJECT:

LICENSING BASIS CHANGE RELATING TO EMERGENCY DIESEL GENERATOR (EDG)

AIR START SYSTEMS, SALEM NUCLEAR GENERATING STATION, UNITS I AND 2 (TAC NOS. M94636 AND M94637)

Dear Mr. Eliason:

By letter dated February 8, 1996, Public Service Electric and Gas Company (the licensee) proposed to change the licensing basis for Salem Nuclear Generating Station, Units 1 and 2.

The proposed change would delete the air dryers in the EDG air start systems.

The air dryers were installed by the licensee as a means of complying with the recommendations of NUREG/CR-0660 and were found acceptable by the staff as stated in Supplement 5 to NUREG-0517, Safety Evaluation Report.

The licensee proposes to delete the air dryers and replace them with system piping and components made of corrosion resistant materials, and has requested that the licensing basis for both units be changed to reflect this alternative approach to compliance with the recommendations of NUREG/CR-0660 as reflected in NUREG-0800, Standard Review Plan.

Enclosed is our Safety Evaluation which concludes that the licensee's proposal is acceptable.

Docket Nos. 50-272/311

Enclosure:

As stated cc w/encl~ See nex~ page DISTRIBUTION:

Docket File

. JStolz

  • PUBLIC MO' Brien PDl-2 Reading LOlshan SVarga
  • .OGC JZwolinski

~CRS Sincerely,

/S/

Leonard N. Olshan, Project Manager Project Directorate 1-2 Division of Reactor Projects - 1/11 Office of Nuclear Reactor Regulation LNicholson, RGN-1 CMcCracken

  • JCalvo ET01~l i nson i

l DATE

/

/96 3 I 7 /96.

3 / /96 J /it"/96

(- ____ 96 g~~I;6-1~8 BE~~-~~;~-P_Y ___

DO_~U_M~_N_T_Nj\\ME: SAM9 636. L TR

'3\\1 ;~

PDR ADOCK 05000272.

p PDR

~ crE~\\rrm Cint?Y l:'fbl I I

' ~p.'R REG(/(

e e

. 'l~**o1)

UNITED STATES I-0

~

0 NUCLEAR REGULATORY COMMISSION to-

~

<II i:

WASHINGTON, D.C. 20555-0001

~

~

~

~o

        • il Mr. Leon R. Eliason Chief Nuclear Officer & President-Nuclear Business Unit
  • Public Service Electric and Gas Company Post Office Box 236 Hancocks Bridge, NJ 08038 March 21, 1996

SUBJECT:

LICENSING BASIS CHANGE RELATING TO EMERGENCY DIESEL GENERATOR (EOG)

AIR START SYSTEMS, SALEM NUCLEAR GENERATING STATION, UNITS 1 AND l (TAC NOS. M94636 AND M94637)

Dear Mr. Eliason:

By letter dated February 8, 1996, Public Service Electric and Gas Company (the licensee) proposed to change the licensing basis for Salem Nuclear Generating Station, Units 1 and 2.

The proposed change would delete the air dryers in the EOG air start systems.

The air dryers were installed by the licensee as a means of complying with the recommendations of NUREG/CR-0660 and were found acceptable by the staff as stated in Supplement 5 to NUREG-0517, Safety Evaluation Report.

The licensee proposes to delete the air dryers and replace them with system piping and components made of corrosion resistant materials, and has requested that the licensing basis for both units be changed to reflect this alternative approach to compliance with the recommendations of NUREG/CR~0660 as reflected in NUREG-0800, Standard Review Plan.

Enclosed is our Safety Evaluation which concludes that the licensee's proposal is acceptable.

Docket Nos. 50-272/311

Enclosure:

Safety Evaluation cc w/encl:

See next page Sincerely,

~'-~

Leonard N. Olshan, Project Manager Project Directorate 1-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

M~. Leon R. Eliason ~

Public Service Electric & Gas Company cc:

Mark J. Wetterhahn, Esquire Winston & Strawn 1400 L Street NW Washington, DC 20005-3502 Richard Fryling, Jr., Esquire Law Department - Tower SE 80 Park Place Newark, NJ 07101 Mr. Clay Warren General Manager - Salem Operations Salem Generating Station P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Louis Storz Sr. Vice President - Nuclear Operations Nuclear Department P.O. Box 236 Hancocks Bridge, New Jersey 08038 Mr. Charles S. Marschall, Senior Resident Inspector Salem Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Maryland Office of People's Counsel 6 St. Paul Street, 21st Floor Suite 2102 Baltimore, Maryland 21202 Ms. R. A. Kankus Joint Owner Affairs PECO Energy Company 965 Chesterbrook Blvd., 63C-5 Wayne, PA 19087 Mr. Elbert Simpson Salem Nuclea~enerating Station, Units 1 and 2 Richard Hartung Electric Service Evaluation Board of Regulatory Commissioners 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Lower Alloways Creek Township c/o Mary 0. Henderson, Clerk Municipal Builoing, P.O. Box 157 Hancocks Bridge, NJ 08038 Mr. Frank X. Thomson, Jr., Manager Licensing and Regulation Nuclear Department P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. David Wersan Assistant Consumer Advocate Office of Consumer Advocate 1425 Strawberry Square Harrisburg, PA 17120 Ms. P. J. Curham MGR. Joint Generation Department*

Atla~tic Electric Company P.O. Box 1500 6801 Black Horse Pike Pleasantville, NJ 08232 Carl D. Schaefer External Operations - Nuclear Delmarva Power & Light Company P.O. Box 231 Wilmington, DE 19899 Public Service Commission of Maryland Engineering Division Chief Engineer 6 St. Paul Centre Baltimore, MD 21202-6806 Senior Vice President - Nuclear Engineering Nuclear Department P.O. Box 236 Hancocks Bridge, ~ew Jersey 08038