ML18093B183

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Aug 1988 for Salem Unit 1
ML18093B183
Person / Time
Site: Salem 
Issue date: 08/31/1988
From: Jackson J, Miller L, White P
Public Service Enterprise Group
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
NUDOCS 8810040148
Download: ML18093B183 (11)


Text

AVERAGE DAILY UNIT POWER LEVEL Completed by Pel l White Month AUGUST 1988 Day Average Daily Power Level (MWe-NET) 1 1068 2

10 67 3

1062 4

1071 5

10 54 6

1055 7

1058 8

1063 9

1065 10 1068 11 10 56 12 1066 13 10 64 14 1061 15 10 42 16 1088 P. 8.1-7 Rl 881004(>148 :39():3:31 -- -

RPDR AD01_-:i**.*

)i::-

\\

p,

( *-100027:2 PDC Day Docket No.

~5~0~-~2~7~2:...,,....--~~~~

Unit Name Salem # 1 Date

~9~-~8_-~8~8~~--~~-

Tel ephone 609-935-6000 Extension 4451


'"~~~~~~~-

Average Daily Power Level (MWe-NET) 17 1067 18 1067 19 1060 20 864 21 1053 22 1096 23 1086 24 1078 25 1044 26 1087 27 1066 28 1077 29 1054 30 1102 31 214

OPERATING DATA REPORT Docket No.50-272

-'--~-7-:=--~~~~-

D ate: 9-8-88 Telephone: 935-6000

""-"-----~~~~~~-

Completed by Pell White Extension: 4451

~---~~~~~~-

Operating Status

1.

Unit Name Salem No. 1 Notes

2.

Reporting Period August 1988

3.

Licensed Thermal Power (MWt) 3411

4.

Nameplate Rating (Gross MWe) 1170

5.

Design Electrical Rating (Net MWe) 1115

6.

Maximum Dependable Capacity(Gross MWe)1149

7.

Maximum Dependable Capacity (Net MWe) 1106

8.

If Changes Occur in Capacity Ratings (items 3 through 7) since Last Report, Give Reason~~N~/_A~~~~~~~~~~~~~~~~~~~~~~~~~~

9.

Power Level to Which Restricted, if any (Net MWe) ~~~N-'-/_A~~~~~~~

10. Reasons for Restrictions, if any N/A

~---'-~~~~~~~~~~~~~~~~~~~

This Month Year to Date Cumulative

11. Hours in Reporting Period 744 5855 97944 1 2. No. of Hrs. Reactor was Critical 725.2 4157.5 61852.6 1 3. Reactor Reserve Shutdown Hrs.

0 0

0

14. Hours Generator On-Line 725.2 4074.4 59866.2 1 5. Unit Reserve Shutdown Hours 0

0 0

16. Gross The rma 1 Energy Generated (MWH) 2453464.8 13746307.6 186015316.4 1 7. Gross Elec. Energy Generated (MWH) 802660 4581500 61775990 1 8. Net Elec. Energy Generated (MWH) 768558 4369741 58765950 19. Unit Service Factor 97.5 69.6 61.1
20. Unit Availability Factor 97.5 69.6
61. 1
21. Unit Capacity Factor (using MDC Net)
93. 4 67.5 54.2
22. Unit Capacity Factor (using DER Net)
92. 6 66.9 5 3. 8 2 3. Unit Forced Outage Rate 2.5
1. 4 23.0
24. Shutdowns scheduled over next 6 months (type, date and duration of each)

N/A

25. If shutdown at end of Report Period, Estimated Date of Startup:

Unit returned to service on August 7, 1988 at 1516.

8-1-7.R2

UNIT SHUTDOWN AND POWER REDUCTIONS REPORT MONTH AUGUST 1988 Docket No. 50-272

~~~~~~~~

Unit Name Salem No.I Completed by Pell White No.

OI49 OI64 Date Type I

8-20-88 F

8-31-88 F

Duration Hours

1. 70 I8.80 Reason 2

A A

Method of Shutting Down Reactor 5

3 License Event Report 1

2 Reason F: Forced S: Scheduled A-Equipment Failure-ex~lain B-Maintenance or Test C-Refuel Ing D-Regulatory Restriction E-Operator Training & Licensing Exam F-Administrative G-Operatlonal Error-explain H-Other-explain Date 9-8-88

..,,--~~~~~~~

Telephone 609-935-6000 Extension 445I System Code 4 CB HA 3 Method I-Manual Component Code 5 PUMP XX TURBIN 2-Manual Scram.

3-Automatic Scram.

4-Contlnuation of Previous Outage 5-Load Reduction 9-0ther

~~~~~~~~

Cause and Corrective Action to Prevent Recurrence No. I2 Charging Pump Turbine Trip Inst and Controls 4 Exhibit G Instructions for Prepara-tion of Data Entry Sheets for Licensee Event Report CLER) File (NUREG OI6I) 5 Exhibit 1 Salem as Source

WO NO 871129034 880111174 880616072 880629087 880719092 PSE&G SALEM GENERATING STATION SAFETY RELATED WORK ORDER LOG SALEM UNIT 1 UNIT EQUIPMENT IDENTIFICATION 1

12SW132 FAILURE DESCRIPTION:

LEAK AT INLET PIPING, MARK M-93.

REPLACE PIPING.

1 14SJ93 REPACK FAILURE DESCRIPTION:

14SJ93 REPACK XA-51 PACKING IS LEAKING.

1 11 BAT PUMP FAILURE DESCRIPTION:

MECH SEAL LEAKS/REPLACE SEAL.

1 HOLE IN PIPING BY 1SW911 FAILURE DESCRIPTION:

HOLE IN PIPING BY VALVE 1SW911/REPAIR.

1 1EP6X FAILURE DESCRIPTION:

TRIPS FREQUENTLY/TROUBLESHOOT AND REWORK.

WO NO 880720101 880726173 880728136 880801133 880803084 SALEM UNIT 1 UNIT EQUIPMENT IDENTIFICATION 1

1BR74 1

FAILURE DESCRIPTION:

BONNET LEAK/REPLACE DIAPHRAGM/:MK # M-63.

  1. 12 SERVICE WATER PUMP FAILURE DESCRIPTION:
  1. 12 SERVICE WATER PUMP HAS.EXCESSIVE PACKING LEAKAGE.

1 11 eves MIXED BED DM FAILURE DESCRIPTION:

DEPELETED/SLUICE & FLUSH OUT THE RESIN.

1 WASTE GAS ANALYZER ALARM ANN FAILURE DESCRIPTION:

INOPERABLE/TROUBLESHOOT.

1 1CS58 FAILURE DESCRIPTION:

lCS58-DRN. VLV LEAK THRU-BORON BUILD-UP.

I

SALEM UNIT 1 I

WO NO UNIT EQUIPMENT IDENTIFICATION 880812049 1

11 CA SUP FAN FAILURE DESCRIPTION:

11 CONTROL AREA SUP FAN/STOP IND NOT WORKING/TROUBLESHOOT.

880815124 1

15 SW PUMP FAILURE DESCRIPTION:

INTERMITTENT FALSE START IN AUTO MODE/TROUBLESHOOT.

880817046 1

12 CHG. PMP FAILURE DESCRIPTION:

THE GEAR BOX OIL COOLER ON 12 CHG. PUMP HAS A POSSIBLE S.W. LEAK.

880822122 1

1CVE21 FAILURE DESCRIPTION:

LUBE OIL COOLER TUBE LEAK/REPLACE TUBE.

MAJOR PLANT MODIFICATIONS REPORT MONTH AUGUST 1988

  • DCR NO.

lSM-0580 PRINCIPAL SYSTEM Safety Injection

Design Change Request DOCKET NO.:

50-272 UNIT NAME~

Salem 1 1988 DATE:

September 10, COMPLETED BY: J. Jackson TELEPHONE:

~6=0=9~/=3=3=9--~4~4=5=5------

DESCRIPTION This design change added weep holes.in the valve disk on the upstream side of Valves SJ12 and SJ13.

This provides a thermal expansion path for fluid trapped between the disks and prevents hydraulic locking of the valve.

MAJOR PLANT MODIFICATIONS REPORT MONTH AUGUST 1988 DOCKET NO.:

50-272 UNIT NAME:

Salem 1

  • DCR lSM-0580 DATE:

September 10, 1988 COMPLETED BY: J. Jackson TELEPHONE:

--=6~0~9~/~3~3~9--~4~4~5~5,__ ____ _

SAFETY EVALUATION 10 CFR 50.59 As a result of the weep hole addition and relief line removal, the valve configuration for the safety injection system will be altered to allow the SJ4 and SJ5 Valves to remain open.

This line up will ensure the BIT is always full and will reduce the number of valves required to open on a safety injection signal.

This modification did not alter any plant process or discharge or affect the environmental impact of the plant.

No unreviewed safety or environmental questions are involved.

DCR - Design Change Request

SALEM UNIT NO. 1 SALEM GENERATING STATION MONTHLY OPERATING

SUMMARY

UNIT NO. 1 AUGUST 1988 The Unit began the period operating at 100% power and continued to operate at that level until August 20, 1988, when a Unit shutdown was commenced.

The shutdown was initiated due to repairs to No. 12 Charging Pump not being completed within the Technical Specification time limit.

Later the same day, the charging pump was restored to operable status and the shutdown terminated at 38% power.

The Unit was restored to full power on August 21, 1988, and continued to operate at that level until August 31, 1988, when a turbine/reactor trip occurred due to a malfun.ction of the turbine hydraulic system during a surveillance test of the vacuum trip function.

The Unit remained shutdown for the rest of the period.

t REFUELING INFORMATION DOCKET NO.:

50-272 COMPLETED BY:

J. Jackson UNIT NAME:

Salem 1 DATE:

TELEPHONE:

EXTENSION:

September 10, 1988 609/935-6000 4497 Month AUGUST 1988

1.

Refueling information has changed from last month:

YES NO X

2.

Scheduled date for next refueling:

April 15, 1989

3.

Scheduled date for restart following refueling: May 30, 1989

4.

A)

B)

Will Technical Specification changes or other license amendments be required?

YES NO NOT DETERMINED TO DATE X

Has the reload fuel design been reviewed by the Station Operating Review Committee?

YES NO X

If no, when is it scheduled?

February 1989

5.

Scheduled date(s} for submitting proposed licensing action:

February if required

6.

Important licensing considerations associated with refueling:

7.
8.
9.

NONE Number of Fuel Assemblies:

A)

Inc ore B)

In Spent Fuel Storage Present licensed spent fuel storage capacity:

Future spent fuel storage capacity:

Date of last refueling that can be discharged to spent fuel pool assuming the present licensed capacity:

8-1-7.R4 19 3 464 1170 1170 September 2001

PS~G Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

Dear Sir:

MONTHLY OPERATING REPORT SALEM NO. 1 DOCKET NO. 50-272 September 10, 1988 In compliance with Section 6.9.1.6, Reporting Requirements for the Salem Technical Specifications, the original copy of the monthly operating reports for the month of August 1988 are being sent to you.

Average Daily Unit Power Level Operating Data Report Unit Shutdowns and Power Reductions Safety Related Maintenance Major Plant Modification Operating Summary Refueling Information Sincerely yours,

~:~!~l!t:

General Manager -

Salem Operations RH:sl cc:

Mr. William T. Russell Regional Administrator USNRC Region I 631 Park Avenue King of Prussia, PA 19406 Enclosures 8-l-7.R4 The Energy People 95-2168 (100M) 12-84