It PS~G Page 1. of 3 S-C-M200-NDM~061Q-0 Date 2/18/88 Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department TITLE: APPENDIX R/BREAKER COORDINATION "AS FOUND" REVIEW (PRE-AUDIT 1987) 1~0 PURPOSE To provide/document the methodology to be used to complete the review of Appendix R/breaker coordination impact for Salem Unit 2 for the design contiguration of September 1987.*

2.0 SCOPE This effort involves a review of the identified associated*

circuits with a common power source, as defined in Generic Letter 81-12. These associated circuits shall be defined in accordance with.the 1987 Salem Unit 2 Safe Shutdown model and a review of the electrical drawings and the Appendix R Area Assessments.

3.0 REFERENCES

3.1 Appendix R to 10CFR50 3.2 Generic Letter 81-12 3.3 1987 Salem Safe Shutdown Model 3.4 Fire Hazards Analysis Salem Nuclear Generating Station Units 1 and 2 3.5 1987 Sal~m Appendix R Area Assessments 3.6 Generic Letter 86-10 3.7 Appendix R Safety Evaluation (S-C-M200-NSE-0709) 3.8 Breaker Coordination Safety Evaluation (S-C-E500-NSE-0675) 3.9 Ebasco Short Circuit Calculation 3.10 Station Loss of Busses (AOP~ELEC-) Operating Procedures 3.11 Fire Area Exemption Requ~sts (NLR-N86005 & NLR-86202) 3.12 Inspection Report No. 50-311/87-29 (Salem 2 ~eptember 1987 Appendix R Audit)

-~.

. UQ..~<;-'=°='(>().-' l c::--**=-*-.c>*-=- 1 o be ~~-

PDR .ADOCK 05000311' 4.~ ~~ ~ U -0*.

___.. SJ.. .. * . DCD * *-----------------------------i Ddm2/ma Tl..,e Energy P8c;_'. *~'

. j

S-C-M200-NDM-061Q-0 Page 2 of 3 Date: . 2/18/88 4.0 DISCUSSION In response to a request by the NRC (reference 3.12), a review of

.the electrical distribution configuration concentrating in the area of breaker coordination will be performed on the basis of an Appendix R postulated exposure fire hazard. The configuration under study will b~ the distribution system in its pre-restart rnodif ication format *.

An engineering evaluation will be issued at the completion of this effort to document all findings.

4.1 Associated Circuit (common power source) Methodology 4.1.1 Utilize 1987 Salem Shutdown Model to review Salem Electr1cal Single Lines and identify safe shutdown and associated circuit loads.

4.1.2 Review the Tenera Unit 2 Appendix R Area Assessments to determine safe shutdown trains that will be utilized to achieve shutdown. This information will serve to identify "associated" safe shut~own cables for analysis.

4.1.3 Once associated circuits are identified, document voltage level, safety ~hannel, cable route and length, fire area, and reference drawings on cable input forms (Attachment A).* Information as to whether the raceway is fire wrapped will aiso be provided.

4.1.4 Define where the breaker becomes coordinated.

  • Define what level of short circuit current/cable length at which the co?rdination occuis.

4.1.5 Should the breaker not be coordinated, review for protection with fire wrap.

  • 4.1.6 Should neither breaker coordination nor fire barriers be acceptable for mitigating the associated ~ircuit's expos~re, review ~he area for exemption request commitments.

4.1.7 Sh6uld neither breaker coordination, noi fire wrap, nor exemption request commitments mitigate exposure fire damage, review for application of AOP-ELEC or EOP-LOPA.

Ddm2/ma

s-c.'.-M200-NDM- 0610:-0 Paqe 3 of 3 Date: 2/18/88 4.1.8 The comment section of the cable input forms shall be utilized to disposition each associated circuit, and provide data for preparation of the final engineering *evaluation.

5.0 ACTION Personnel assigned to*Appendix R/Breaker Coordination Task Force shall utilize the methodology provided in this design memo.

6.0 SCHEDULE In accordance with the commitments established by PSE&G upper management, the effort is scheduled to be completed by March 4, 1988.

7.0 FUNDING AUTHORIZATION To be provided t6 participating members of the task £orce on a need to know basis.

  • 8.0 ATTACHMENTS 8.1 Cable Input Form 8.2 Appendix R/Breaker Coordination Flow Chart 9.0 SIGNATURES

./:* 4>/ .-- .. . ~' /1 *<l'i~<

Originator's Group Head roate Nuclear En ering Sciences Manager

~&;~o:<JJ

_ NucleaEl ctrical

_Engineering Manager m4e Date Manager-Nuclear /

/

C !r:/{;;(,.,d>>w,, /~*A l

u Engineering Speciaf Projects ate

ii* I *.u.t1 - -- -:-- - - ---- JI Wtl - - - - - - -- - *- - ~II LIT f__ l_IlTTD I *I' I I r-r1=i I I I I I EL~J L_IIJ. I_ I t~l-LID [ 0 -,

f_ITf~J=r[J_-_[J. I l!E1 I _l_L_[J~lTI-o 111~J LI I LJIO_( 111 ITEJ

[TilTJ_L ITI_J ~ [=-r=1~~rJ __] __JTI ~J L-1 I I t~I~rJ ~J=rI_] [8]~ .*

I I 1=1~-[J~r-_r _ [_1 ITEJ I IT.J-=:[J~_JJ=1 [~1~J [l I l_-t=]~J~l~J__ l_JJ l!T1J I I DTI=t. LJ J S3 IT_lT[JTI . f~l~I 1_-rr1-r=-t~[~T~-:[_[J]

[iEJ I I LlJ_l~L L_ f__ I Isl 10 [=:t~:r_1--1 11 J l sEl r-_[IJ_-1_- r-1_ I~ L~tJ f~~

LI Ll~J=_E~J h,I I 0 I I I I J-[]~[J L~ I~ I I .ITJ-.. 1_I I. I I_ '_ LJ~] [~-r~l . ~

II I. L_l_J_J ITE1 I I rT--f_JT[J E-Ed LCCl_JJ~[] __ l_TIJ EEi ~

_O I I I I I 03 I I r1-1r1-1TJ EE] ITI I I rn I. I -11 EE] ~

Ll_ II I I I II I I I I 1 0 I I -1 I I I I I I /I0 I I I I I I I I I I I I I EEi t lWMJlWH

___ JlNJOOIS ~\

9NllnOH J18W:J IT LI I I I LJ LI I I ITI ITLITTI_t' LI t"JTI=rJ I MtllnOJ "OYJ *

  • * *
  • 1*

. . r,. ..'.

i,

  • ,*rrn' 1111*111 ,*,,, 1.11111 CI]l rr-B-__ r~ rTTTJ 1 1 ITJ]

LL _ ITJTITLIILD

'9.A9 _ * .,ay n':.i. * ,.., - -,a, "/'7l'iJ *ot1 :J,,,.~

~ 0 I I I I I I I I I I hl'u *'J**a .,,, .Q, D ,,.Q ~.!M.

APPENDIX A/BREAKER COORDINATION

. ..:..s FOUND" FLOWCHART

- SAFETY EVALUATIONS - IDENTIFY AS A

- RESTART DCP's CONCERN

- FIRE WATCH LISTS - VERIFY COMPENSATORY START MEASURES. NOW IN FINISH PLACE

- DOCUMENT VIA ENGIN-EERING EVALUATION WOULD

- S/D MODEL ID ASSOCIATED APPLICATION YES

- DESIGN DRWNG CIRCUITS OF LOSS OF AC DOCUMENT

- GENERIC LETTER (COMMON POWER POWER PROCEDURE ACCEPTABILITY 81-12 SOURCE) BY MITIGATE THE

- AREA ASSESSMENTS FIRE AREA PROBLEM?

EXEMPTION.REQUEST LETTER JAN. 1986 YES

  • DID NO FOR ASSOCIATED FIRE CIRCUITS DEFINE: PROTECTION YES IMPROVEMENT VOLTAG~ ROUTINa - CCR PROGRAM COMMIT TO FIRE ARE~ REF . . * - DESIGN PROTECTING DRAWINGS, CHANNEL DRAWINGS THE CABLE ECO OF POWER SOURCE  ?

2/17/88 FIRE WRAP DRAWINGS CCR - CABLE CONTROL REPORT .

IDENTIFY IS CABLE YES REDUNDANT POWER FIRE WRAPPED SOURCE CHANNELS UNTIL ROUTED IN SAME COORDINATION FIRE AREA OBTAINED?

CLRSTDCP - SHORT CIRCUIT CALCULATION

- RELAY/PROTECTIVE NO DEVICE CURVES

  • YES

POWER CABLES SUBJ.

TO FIRE DAMAGE POWER SOURCE~T.

BY LACK OF COORDIN.

SHUTDOWN COMPONENT AFFECTED IMPACT ON AB SAFELY SHUTDOWN TO 12FA-AB-100A lA 7YF-A lA 230V VITAL AC CC #11 CHILLED WATER NONE-UTILIZE #12 CHILLED PUMP WATER PUMPo 1AADC26-AT NONE NONE 1CCDC24-CT NONE NONE 1ADC22-ET* NONE NONE 2BDC22-ET* NONE NONE 2CCDC24-CT NONE NONE PAGE 1 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF COO AFFECTED SAFELY SHUTDOWN l 2FA-AB-122A lADCl-AT* NONE NONE NONE-ALT. SHUTDOWN PRO-lADCl 7-HT* NONE NONE CEDURES WOULD BE IMPLE-1BDC17-ET* NONE NONE MENTED.

lCDCl 7-ET* NONE NONE 1A7YC-A* lA VITAL AI:R COND. #11 CHILLED WATER CLEAR lB VITAL AIR COND cc PUMP CC. CLOSE IN SWGR BREA-lA 7YD-A* NONE NONE KER TO POWER lB VITAL 1A7YA-A* NONE NONE AIR COND. CC - CLOSE IN 1B7YC-B* lB VITAL AIR COND. #12 CHILLED WATER # 12 CHILLED WATER PUMP.

cc PUMP

!Cl 3YQ-C* lC VITAL VENT CC #12 CHARGING PUMP ROOM COOLER

  1. 11 COMPONENT COOLING PUMP ROOM COOLER
  1. 12 CHARG. PUMP RM 1Cl3YP-C*
  • lC VITAL VENT CC COOLER
  1. 11 COMP CLG PUMP RM COOLER 2A2Y-A* NONE NONE 2ADC1-AT* NONE NONE 2ADC1 7-HT* NONE NONE 2A7Y-A 21 VITAL AIR COND #21 CHILLED WATER cc PUMP 2A 7YF-A 2A VITAL AIR COND #21 CHILLED WATER cc PUMP 2BDC1 7-ET* NONE NONE 2CDC1 7-FT* NONE NONE 2A7YC-A* 2A VITAL AIR COND #21 CHILLED WATER RESET 2A 230V SWGR BRKR cc PUMP AND 2A VITAL AIR COND.

2A7YA-A* 2A VITAL AIR COND #21 CHILLED WATER CC. 2B VITAL AIR COND.

cc PUMP CC AND #22 CHILLED WATER 2B7YC-B* 2B VITAL AIR COND #22 CHILLED WATER PUMP ARE THEN OPERABLE.

cc PUMP 2Cl 3YP-C* 2C VITAL VENT CC #22 CHARGING PUMP ROOM COOLER

  1. 21 COMP. COOLING PUMP ROOM COOLER PAGE 2 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 12FA-AB-122A 2Cl 3YQ-C* #22 CHARG. PUMP RM (CONT'D) COOLER

  1. 21 COMP. COOLING PUMP RM COOLER PAGE 3 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-64Al 2ADC25-AT NONE NONE NONE-UTILIZE TRAINS 2A &

2CDCA-C 2C 125VDC BA'I'.TERY NONE (BATT. CHRGR) 2B.

2CDCB-C 2C 125VDC BATTERY NONE (BATT. CHRGR)

PAGE 4 OF 74

POWER CABLES SUBJ~ POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB "'y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-45A 2BY6BN-B* 2B WEST VALVES CC 2SJ4 NONE -

2SJ12 21-24BF13 ARE NOT 22RH19 REQUIRED. UTILIZE 2B EAST VALVES CC 2RH1 21-24BF19 & 40 VALVES.

21BF13 22BF13 21RH19, 21 RHR PUMP, &

2C3YBN-C* 2C WEST VALVES CC 2SJ1 21 RHR ROOM COOLER ARE 2C EAST VALVES' CC 2SJ5 NOT REQUIRED. UTILIZE 2SJ13 22 RHR FLOWPATH. 22RH19, 23BF13 2RH1, & 2RH2 MUST BE 2 4BF13 MANUALLY OPERATED FOR COLD SHUTDOWN UNLESS VALVE cc*s ARE RESTORED.

21CC16 NOT REQUIRED-UTILIZE 22CC16.

2A7D-A NONE #21 RHR PUMP 2SJ1, 2SJ4, 2SJ5, 2SJ12, 2Al 3YH-A NONE #21 RHR ROOM COOLER & 2SJ13 ARE NOT RE-2A3YBD-A NONE 21CC16 QUIRED. NORMAL CHARG-2A3YBE-A 2A WEST VALVES CC 21CC16 ING, LETDOWN, & BORIC 21RH19 ACID FLOWPATHS ARE 2A EAST VALVE CC 2RH2 AVAILABLE.

2A3YBF-A NONE NONE 2A3YBK-A NONE NONE 2A3YBU-A NONE 21RH19 PAGE 5 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-45B 2C3YBR-C* 2C WEST VALVES CC 2SJ1 NONE -

2C EAST VALVES CC 2SJ5 2l-24BF13 ARE NOT 2SJ13 REQUIRED. UTILIZE 23BF13 21-24BF19 & 40 VALVES.

24BF13 2B3YBN-B* 2B WEST VALVES CC 2SJ4 22RH19, 22 RHR PUMP, &

2SJ12 22 RHR ROOM COOLER ARE 22RH19 NOT REQUIRED. UTILIZE 2B EAST VALVES cc* 2RH1 21 RHR FLOWPATH. 2RH1 21BF13 MUST BE MANUALLY OPER-22BF13 ATED FOR COLD SHUTDOWN 2B3YBR-B* SAME AS 2B3YBN-B SAME AS 2B3YBN-B UNLESS 2B EAST VALVE CC 2C3YBJ-C* NONE NONE IS RESTORED.

2Bl3YH-B NONE #22 RHR ROOM COOLER 2B3YBH-B SAME AS 2B3YBN-B SAME AS 2B3YBN-B 2SJ1, 2SJ4, 2SJ5, 2SJ12, 2B3YBL-B* NONE NONE & 2SJ13 ARE NOT RE-2B3YBT-B* NONE NONE QUIRED. NORMAL CHARG-2B3YBU-B* NONE NONE ING, LETDOWN, & BORIC 2B3YBX-B* NONE NONE ACID FLOWPATHS ARE 2B7D-B NONE 22 RHR PUMP AVAILABLE.

PAGE 6 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-84D 2A3YBS-A* NONE NONE NONE -

2BDD-B(CABLE IS NONE NONE 2A & 2B DIESEL GEN POWER FIRE WRAPPED) TRAINS AVAILABLE FOR 2C3YBW-C* NONE NONE SAFE SHUTDOWN.

2CGN-C 2C DG 2C DG OF 2C TRAIN 2CDD-C 2C DIESEL GEN 2C DIESEL & 2C 2CDDA-C 2C DG DISTRIBUTION SYS 2BDDA-B NONE NONE (PROPOSED FIRE WRAP COMPENSATORY. MEAS-URES IN PLACE)

PAGE 7 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDQWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-84G 2B4YG-B* NONE 22 FUEL OIL TRANS- NONE ~ UTILIZE 21 FUEL FER PUMP OIL TRANSFER PUMP PAGE 8 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB Y TO TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUT 2FA-DG-84H 2A3YBS-A* NONE NONE NONE - UTILIZE 22 FUEL OIL TRANSFER PUMP.

2A4YG-A NONE 21 FUEL OIL TRANS-FER PUMP PAGE 9 OF 74

r.

- POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF C AFFECTED SAFELY SHU 2FA-SB-100 1CCDC24-CT NONE NONE 1DCD24-DT lDDC 125V DIST. CAB NONE-LIMITED TO LOSS OF "D" 125VDC DIST. CAB 2DCD24-DT 2DDC 125V DIST. CAB PAGE 10 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPO~ENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-84F 2A3YBS-A NONE NONE NONE -

2A446-A* NONE NONE 2A I 28, & 2C DIESEL (CABLE WRAP) GEN'S AND SERVICE WATER 2ADD-A* NONE NONE ARE IMPACTED. THE "A" (CABLE WRAP) SW PUMP WOULD BE AVAIL-2Bl5Y-B* 2B 230V SWGR 2B VITAL VENT CC ABLE ONCE POWER IS (230V SWGR TO 282 22 RHR RM COOLER RESTORED VIA THE GAS SERV. WTR CC) 21 CHRG PUMP RM CLR TURBINE. THE RESULT OF 2B8Y-B* 22 CCW RM COOLER THIS IS THAT THE SERVICE (230V SWGR TO 281 WATER SYSTEM AND SERV. WTR CC) 2Bl SW INTAKE CC COOLENT COOLING WATER 22 SW VENT FAN SYSTEMS WOULD OPERATE AS DESIGNED, AND NO 282 SW INTAKE CC ALTERNATE COOLING TO THE 24 SW VENT FAN CHARGING PUMPS WOULD BE 2SW26 NECESSARY.

2B AIR COND CC 22 CHILLED WTR PUMP 2B EAST VALVES CC 2RH1 2PR7 218Fl3 228Fl3 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 2*2 FO XF R PUMP 28- DSL GEN PAGE 11 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUT 2FA-DG-84F 2Bl l 25VDC BATT (CONT'D) CHRGR 2Bl 28VDC BATT CHRGR 2B&2D VITAL INST INVERTER PWR SUPPLY 2B VITAL INST BUS AUTO XFMR 2B 460V SWGR 22 CHILLER 22 CFCU 24 CFCU 2B3D-B* NONE NONE (FIRE WRAP COMMIT.)

2B4YG-B* NONE 22 DG FUEL OIL TRAN SF ER PUMP 2B8D-B NONE NONE (FIRE WRAP COMMIT 2C 3D-C

  • 2C DG 2C DIST SYS LOADS (IF BEING USED) 2C 8Y-C
  • 2C 2 30V SWGR 2C VITAL VENT CC 22 CHRG PUMP RM CLR 21 CCW RM COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 2 4]3Fl 3 PAGE 12 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-84F 2C WEST VALVES CC (CONT'D) 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERTER PWR SUPPLY 2C 460V SWGR 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT SHUTDOWN SYS XFMR 480V PRESSRZR HTRS (ALT SD ONLY)

PAGE 13 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON .AB TO TO FIRE DAMAGE BY LACK OF COO AFFECTED SAFELY SHUTDOWN 2FA-SB-100 1CCDC24-CT NONE NONE NONE 1DCD24-CT lDDC 125V DIST CAB 2DCD24-DT 2DDC 125V DIST CAB PAGE 14 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-TGA-88 2ADC10-FT* NONE NONE NONE -

2ADC12-AT* NONE NONE. 21-24BF13 ARE NOT 2ADC13-AT* NONE NONE REQUIRED. FAIL CLOSE 2BDC10-ET* NONE NONE 21-24-BF19 & 40 VALVES.

2BDC12-BT* NONE NONE 2BDC13-BT* NONE NONE 22RH19 IS NOT REQUIRED, 2BDC15-GT* NONE NONE UTILIZE 21RH19.

(NORM DEENERGIZED) 2B3YAU-B* NONE NONE 2RH1 MUST BE MANUALLY 2B36AV-B* NONE NONE OPERATED FOR COLD SHUT-2C3YAX-C* NONE NONE DOWN UNLESS 2B EAST 2B3YAM-B 2B EAST VALVES CC 2RH1 VALVE CC IS RESTORED.

( 21BF13) 21BF13 2B3YAN-B 22BF13 2SJ1, 2SJ4, 2SJ5, 2SJ12

( 2 2BF13) 2SJ4 & 2SJ13 ARE NOT RE-2B WEST VALVES CC 2SJ12 QUIRED. NORMAL CHARG-22RH19 ING, LETDOWN, & BORIC 2SJ5 ACID FLOWPATHS ARE 2C3YAT-C 2C EAST VALVES CC 2SJ13 AVAILABLE.

( 2 3BF13) 23BF13 24BF13 2C3YAU-C 2C WEST VALVES CC 2SJ1

( 2 4BF13) 2CCDC24-CT NONE NONE (PNEUMATICALLY

( 2lBF19) FAIL SAFE)

. ( 22BF19)

(21BF40)

( 2 2BF40)

PAGE 15 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-100A 2Al 3YK-A* 2A VENT CC 23 CHARGE PMP. RM. NONE-ALT. SHUTDOWN CLR. PROCEDURES WOULD BE

  1. 2 AFW PMP RM. CLR. IMPLEMENTED.
  1. 21 RHR PMP. RM.

CLR.

2A7YD-A* '2A AIR COND CC #21 CHILLED WATER PUMP 2ADC1-AT* NONE NONE 2ADC20-AT (NORMALLY NONE NONE DEENERGIZED) 2Bl 3YM-B* NONE NONE 2B7YD-B* 2B AIR COND. CC 22 CHILLED WATER PUMP 2BDC1 7-ET* NONE NONE 2BDC19-BT (NORMALLY NONE NONE DEENERGIZED) 2BDC21-DT (NORMALLY NONE NONE DEENERGIZED) 2BDC24-BT (NORMALLY NONE NONE DEENERGIZED) 2Cl 3YP-C* 2C VENT cc #22 CHRG. PMP. RM.

CLR.

  1. 21 CCW PMP. RM.

CLR.

2Cl 3YQ-C* 22 VENT CC #22 CHRG. PMP. RM.

CLR.

  1. 21 CCW PMP. RM.

CLR.

2COC11-CT NONE NONE 2COC1 7-FT* NONE NONE 2AADC6-AT 21\ADCS-AT 2AAOC33-AT 2CCDC5-CT 2AADC11-AT 2CCDC30-CT 2CCDC13-CT PAGE 16 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUTD 2F A-AB-lOOA 2A5YA-A NONE (CONT'D) 2A 7YF-A 2A AIR COND. CC #21 CHILLED WATER PUMP 2B5YA-B 2B5YB-B 2B7YF-B 2B AIR co~m. cc #22 CHILLED WATER PUMP 2CllY-C (NORMALLY NONE NONE DEENERGIZED) 2C5YA-C 2C5YB-C 2C6YC-C 2CCDC24-CT (21BF19, 22BF19)

(21BF40, 22BF40) 2CDC21-CT NONE NONE 2AZY-A* NONE NONE 2C ZY-C NONE NONE PAGE 17 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF COO AFFECTED SAFELY SHUTDOWN FA-PP-lOOH 2A3YAV-A NONE NONE NONE 2B3YAB-B NONE NONE 2B3YAC-B NONE NONE 2B3YAZA-B NONE NONE 2C3YAW-C NONE NONE 2C3YAZ-C NONE NONE PAGE 18 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUTD 2FA-EP-100G 2Al3YA-A* 2A VITAL VENT cc #23 CHRG. PUMP RM. NONE -

2Al 3YB-A* C LR. ON LOSS OF 2A & 2C 2Al 3YE-A* #2 AFW PMP. RM. CLR DIESEL GENS RUN AUX 2Al 3YG-A* #21 RHR PMP. RM. FEED TURBINE DRIVEN 2Al 3YH-A {21 RHR RM CLR. PUMP. UTILIZE 2B DIESEL COOLER) GEN. AND GAS TURBINE 2Al 3YF-A { 2 AFW RM. FOR POWER DISTRIBUTION.

COOLER) UTILIZE MOTOR DRIVEN 2Al 3YC-A { 23 CHRG. PUMPS WHEN ON GAS RM. COOLER) TURBINE. MANUALLY 2Al 3YK-A* OPERATE 2RHZ FOR COLD -

2Al3YJ-A* SHUTDOWN.

2A9X-A* 2A 460V SWGR #21 CHILLER

  1. 21 BORIC ACID XFR PMP.
  1. 21 CFCU
  1. 23 CHRG PUMP 2A 230V SWGR 2A VITAL VE~T CC 21 RHR RM COOLER 23 CHRG PUMP RM CLR 2AFP RM COOLER 2A SW INTAKE CC 21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLED WTR PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 PAGE 19 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-EP-100G 21RH19 (CONT'D) 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATT CHRGR 2Al 28VDC BATT CHRGR 2A VITAL INST INVERTER PWR SUPPLY 2Al 3Y-A 2A 230V SWGR SEE ABOVE SINGLE FAILURE FIRE 2A 460V SWGR SEE ABOVE NONE NONE 2B9X-B*

2C9X-C* 2C 460V SWGR 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT SHUTDOWN SYS XFMR 480V PRESSRZR HTRS (ALT. SD ONLY) 2C 230V SWGR 2C VITAL VENT CC 22 CHRG PUMP RM CLR 21 CCW RM COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 PAGE 20 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUT 2FA-EP-100G 2C EAST VALVES CC (CONT'D) 2SJ5 2SJ13 23BF13 24BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERT PWR SUPPLY

-2Al 3YM-A* 2A VENT CC 23 CHRG. RM. COOLER 2 AFP ROOM COOLER 21 RHR RM. COOLER 2A7YD-A* 2A AIR COND. cc 21 CHILLED WATER PUMP 2A7YF-A (21 CHILLED 2A AIR COND. cc 21 CHILLED WATER WATER PUMP) PUMP 2Al 3X-A NONE 21 CHILLER 2B13YF-B 2B VENT cc 22 CCW RM. COOLER 2Bl 3YC-B 21 CHRG. RM. COOLER 2B7YD-B* 2B AIR COND. cc 22 CHILLED WATER PMP.

2B13YA-B* 2B VENT CC 22 CCW RM. COOLER 2B13YD-B* 21 CHRG. RM. CLR.

2B13YE-B* 22 RHR RM. COOLER PAGE 21 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUTD 2FA-EP-100G 2Bl3YB-B*

(CONT'D) 2Bl3YJ-B*

2Bl3YM-B*

2Bl3YN-B* 2B VENT CC 22 CCW RM. COOLER 2Cl 3YQ-C* 21 CHRG. RM. CLR.

2Cl3YP-C* 22 RHR RM. COOLER 2Cl3YK-C*

2Cl 3YJ-C*

2Cl3YG-C*

2Cl3YE-C*

2Cl3YB-C*

2Cl3YA-C*

2Cl3YF-C (21 CCW RM. COOLER) 2Cl3YC-C (22 CHRG.

RM. COOLER) 2Cl3YH-B (22 RHR RM. COOLER) 2Cl3YL-C* 2B VENT CC 22 CCW RM. COOLER 2Cl3YN-C* 21 CHRG. RM. CLR.

2Cl 3YM-C* 22 RHR RM. COOLER 2Cl 4X-C NONE #2 EMERG. CONTROL AIR COMPRESSOR 2Cl 3X-C NONE #23 CHILLER PAGE 22 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-100D 2ADD-A 2A DIST. SYSTe 2A DIESEL GEN. & NONE -

2A DIST. SYST. 2B & 2C DIESEL GEN ASSUMING LOP POWER TRAINS AVAILABLE FOR SAFE SHUTDOWN 2A4YA-A 2A DIESEL GEN. CC 2A DIESEL GEN.

2A4YB-A 2A4YC-A 2A4YJ-A 2A4YH-A 2A4YN-A PAGE 23 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-100Dl** 2A4Y-A 2A 2 30V SWGR

  • 2A VITAL VENT CC NONE -

21 RHR RM COOLER 2B & 2C DIESEL GEN 23 CHRG PUMP RM CLR POWER TRAINS AVAILABLE 2AFP RM COOLER FOR SAFE SHUTDOWN 2A SW INTAKE CC 21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLED WTR PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 2ADSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al l 25VDC BATT CHRGR 2Al 28VDC BATT CHRGR 2A VITAL INST INVERTER PWR SUPPLY 2A 460V SWGR 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23_ CHRG PUMP PAGE 24 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON ABI TY TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-100Dl** 2A4YG-A 2A DIESEL GEN. CC 2A DIESEL GEN.

(CONT'D) 21 FUEL OIL TRANSFER PUMP 2B4Y-B (FIRE NONE NONE WRAPPED) 2C 4 Y-C (FIRE NONE NONE WRAPPED) 2CDC22 (FIRE NONE NONE WRAPPED)

PAGE 25 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO FIRE TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUT 2FA-DG-100E** *2BDD-B 2B DISTRIBUTION SYS 2B DIESEL GEN NONE -

2A & 2C DIESEL GEN 2B4YA-B . 2B DIESEL GEN CC 2B DIESEL .POWER TRAINS AVAILABLE 2B4YB-B 22 FUEL OIL XFR PMP FOR SAFE SHUTDOWN 2B4YC-B 2B4YH-B 2B4YJ-B 2B4YN-B PAGE 26 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-100El** 2B4Y-B 2B .DIESEL GEN NONE -

2B 230V SWGR 2B VITAL VENT CC 2A & 2C DIESEL GEN 22 RHR RM COOLER POWER TRAINS AVAILABLE 21 CHRG PUMP RM FOR SAFE SHUTDOWN COOLER 22 CCW RM COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2B2 SW INTAKE CC 24 SW VENT FAN 25SW26 2B AIR COND CC 22 CHILLED WTR PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl l 25VDC BATT CHRGR PAGE 27 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COO AFFECTED SAFELY SHUTDOWN 2FA-DG-100El** 2Bl 28VDC BATT (CONT'D) CHRGR 2B & 2D VITAL INST INVERTER PWR SUPPLY 28 VITAL INST BUS AUTO XFMR 2B 460V SWGR 22 CHILLER 22 CFCU 24 CFCU 2B4YG-B 22 FUEL OIL XFR PMP 2C4Y-C (FIRE NONE NONE WRAPPED) 2CDC22-CT NONE NONE (FIRE WRAPPED)

PAGE 28 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF COO AFFECTED "' SAFELY SHUTD WN 2FA-DG-100F** 2CDD-C 2C DIST SYST 2C DIESEL GEN NONE -

2C4YA-C 2C DIESEL GEN 2C DIESEL GEN 2A & 2B DIESEL GEN 2C4YB-C 2C DIESEL GEN POWER TRAINS AVAILABLE 2C4YC-C FOR SAFE SHUTDOWN.

2C4YH-C 2C4YJ-C 2C4YN-C PAGE 29 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUTD 2FA-DG-100Fl** 2C4Y-C 2C DIESEL GEN NONE -

2C 230V SWGR 2C VITAL VENT CC 2A & 2B DIESEL GEN 22 CHRG PUMP RM CLR POWER TRAINS AVAILABLE 21 CCW RM COOLER FOR SAFE SHUTDOWN.

2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 2 4BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERT PWR SUPPLY 2C 460V SWGR 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT SHUTDOWN SYS XF~R PAGE 30 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB ~ TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-DG-100F 1 ** 480V PRESSRZR HTRS (CONT'D) (ALT. SD ONLY) 2CDC22-CT NONE NONE PAGE 31 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUTDOWN 2FA-AB-122B 2A3YBP-A* 2A WEST VALVES CC 21CC16 NONE -

2CC30 AFW WILL BE AVAILABLE 21CC3 VIA 21 & 22 AFP BY 21RH19 ALTERNATING THE PUMPS.

THE PUMPS ARE IN AN OPEN 2Al3YK-A* 2A VENT CC #23 CHRG. RM. CORRIDOR WHICH IS COOLER SERVICED BY NORMAL AUX

  1. 2 AFP RM. COOLER BUILDING VENTILATION.
  1. 21 RHR RM. COOLER POWER FOR 2B & 2D VIB WILL BE FROM 2B 125V 2Al2X-A* NONE NONE BATTERY. IF THIS IS DEPLETED, SUFFICIENT 2BllX-B* NONE NONE INSTRUMENTATION WILL BE AVAILABLE FROM 2A &

2Bl2X-B* NONE NONE 2C VIB TO MONITOR PLANT SHUTDOWN.

2B3YBS-B* NONE NONE POWER WILL BE REQUIRED 2B7YC-B 2B AIR COND. cc #22 CHILLED WATER TO 2B 4KV BUS FROM PUMP EITHER 2B DIESEL ON THE GAS TURBINE PRIOR TO 2AVAC10-AT NONE NONE COLD SHUTDOWN TO SUPPORT RHR OPERATION.

2AVAC15-AT NONE NONE 2B7YD-B 2B AI Ro COND. cc 22 CHILLED WATER PUMP 2B7Y-B 2B 230V SWGR 2B VITAL VENT CC 22 RHR RM. COOLER 21 CHRG. PUMP RM.

COOLER 22 CCW RM. COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2Bi SW INTAKE CC 24 SW VENT FAN PAGE 32 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB! TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-122B 2SW26 (CONT'D) 2B AIR COND. CC 22 CHILLED WTR.

PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl 125VDC BATTERY*

CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 2D VITAL INST.

INVERTER POWER SUPPLY 2B VITAL INST. BUS AUTO XFMR 2B 460V SWGR 22 CHILLER 22 CFCU 24 CFCU PAGE 33 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA.:...AB-122B 2B7Y-F 2B AIR COND. CC 22 CHILLED WATER (CONT'D) PUMP 2BVAC10.:...BT NONE NONE 2Cl SX-C NONE NONE 2C3YBP-C 2C WEST VALVES CC 2SJ1 2CV40 2CC31 22SW22 22CC3 2C EAST VALVES CC 23BF13 24BF13 2CVAC10-CT NONE NONE 2DCA16A-HT NONE NONE PAGE 34 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-FH-100 2CVAC21-CT NONE NONE NONE 2BVAC30-BT NONE NONE PAGE 35 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN lFA-TGA-88 2DCD24-DT NOr.:IE 23BF40 NONE -

24BF19 UTILIZE BF19 & 40 VALVES 2DCD41-GT NONE NONE 2DCD7-GT NONE NONE 2DCD32-GT NONE NONE PAGE 36 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 12FA-AB-84A 2DCD14-GT NONE NONE NONE PAGE 37 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-84A 2A4D-A 2A 460V SWGR 21 CHILLER SHUTDOWN IMPACTED DUE 2A9X-A 21 BORIC ACID XFR. TO MISROUTED ALTERNATE 2A7X-A PUMP SHUTDOWN POWER FEED.

2A4X-A 21 CFCU 2A2X-A 23 CHRG PUMP IF ONLY CONSIDERING 2A3YA-A BREAKER COORDINATION, 2A8Y-A 2A 230V SWGR. 2A VITAL VENT CC 2C 125VDC BUS AND 2C 2Al3Y-A 21 RHR RM. COOLER BATTERY COULD BE 2A3YB-A 23 CHRG PUMP RM. RESTORED AND THE PLANT 2A4Da-A COOLER SUBSEQUENTLY PROCEED 2A7Y-A 2AFP RM. COOLER TO SHUTDOWN VIA THE ALTERNATE SHUTDOWN 2A SW INTAKE CC METHOD.

21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLED WTR PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATTERY SINGLE FAILURE FIRE CHARGER PAGE 38 OF 74

1 POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO FIRE TO FIRE DAMAGE BY LACK OF COO AFFECTED SAFELY SHUTDOWN 2FA-AB-84A 2Al 28VDC BATTERY (CONT'D) CHARGER 2A VITAL INST.

INVERTER POWER SUPPLY 2A6X-A* NONE NONE 2Al lX-A NONE NONE 2Al 4Y-A NORMALLY OPEN BACK-UP TO 2B BATT.

CHARGER 2ADC5-AT 2Al BATT CHARGER 2ADC6-AT NORMALLY OPEN 2ADC25-AT NONE NONE 2ADC26-AT NORMALLY OPEN 2ADC30-AT NONE NONE 2ADC35-AT NONE NONE 2Al3X-A 460V SWGR 21 CHILLER 2Al5X-A 2Al 6X-A 2A5X-A 2Al0X-A 2Al 4X-A 2Al2X-A PAGE 39 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED* SAFELY SHUTD 12FA-PT-84 2CVAC15-CT* NONE NONE NONE -

2AVAC22-AT* NONE NONE A FIRE IN THIS AREA HAS 1A3D-A NONE 15SWP AN IMPACT ON SERVICE 1A8D-A NONE 16SWP WATER AND POWER DISTRI-1A8Y-A BUTION. POWER IS 1AADC18-AT NONE lSWVlO RESTORED VIA THE GAS 1FW313-AT NONE LA-1688, LA-5744IB TURBINE. AUX FEEDWATER 1FW314-BT NONE LA-2670, LA-2705IB AVAILABLE FROM AFWST 1A3YBN-A* NONE NONE (8 HR CAPACITY) AND 1A3YBR-A* NONE NONE ALTERNATE AFW SUCTION 1B3YBM-B* NONE NONE FROM 2/500,000) GAL DM 1B3YBZA-B* NONE NONE TANKS. STEAM FROM 1B3YBZB-B* NONE NONE ATMOSPHERIC STEAM 2A3YBN-A* NONE NONE RELIEFS. CHG PUMPS CAN 2A3YBR-A* NONE NONE BE COOLED BY DM WATER 2B3YBZA-B* NONE NONE VIA HOSE HOOKUP. CHG 2B3YBZB-B* NONE NONE MAKEUP FROM RWST. CHG 2B3YBM-B* NONE NONE DISCHARGE VIA ANY FLOW-PATHS IN SYSTEM. CCW 2B8Y-B 2B 230V SWGR 2B VITAL VENT CC CAN BE CROSSED CONNECTED 2Bl5Y-B 22 RHR RM. COOLER WITH HOSES. SW CAN ALSO 21 CHRG PUMP RM. BE CROSSED CONNECTED COOLER WITH HOSES ALLOWING 22 CCW RM. COOLER RESTORATION OF SW LOADS SUCH AS THE DIESEL GENS.

2Bl SW INTAKE CC 22 SW VENT FAN 2B2 SW INTAKE CC 24 SW VENT FAN 25SW26 2B AIR COND CC 22 CHILLED WATER PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 PAGE 40 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 12FA-PT-84 2B WEST VALVES CC (CONT'D) 2 2CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl 125VDC BATTERY CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 2D VITAL INST.

INVERTER POWER SUPPLY 2B VITAL INST. BUS AUTO XFMR 2B 460V SWGR 22 CHILLER 22 CFCU 24 CFCU 2A3D-A .2A DIESEL GENERATOR 2A8D-A 2A8Y-A 2A 230V SWGR 2A VITAL VENT CC 21 RHR RM. COOLER 23 CHRG PUMP RM.

COOLER 2AFP RM. COOLER 2A_ SW INTAKE CC 21SW20 PAGE 41 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 12FA-PT-84 21 SW VENT FAN (CONT'D) 2A AIR COND CC 21 CHILLED WTR.

PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATTERY CHARGER 2Al 28VDC BATTERY CHARGER 2A VITAL INST.

INVERTER POWER SUPPLY 2A 460V SWGR 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23 CHRG PUMP 2AADC18-AT NONE 2SWV1 2SWV2 2SWV5 2SWV7 PAGE 42 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUT 12FA-PT-84 2SWV8 (CONT'D) 2B8D-B 2B DIESEL GEN.

2C3D-C 2C DIESEL GEN.

2C8Y-C 2C 230V SWGR 2C VITAL VENT CC 22 CHRG PUMP RM.

COOLER 21 CCW RM. COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 24BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST.

INVERT. POWER SUPPLY 2C 460V SWGR 23 CHILLER 22 BORIC ACID XFR PUMP PAGE 43 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO

  • FIRE TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUT 12FA-PT-84 23 CFCU (CONT'D) 25 CFCU 2 EMER CONT. AIR COMPRESSOR ALT. SHUTDOWN SYS XFMR .

480V PRESSRZR. HTRS (ALT *. SD ONLY) 2FW313-AT NONE LA-1688, LA-5744IB PAGE 44* OF 7 4

IMPACT ON AB TO POWER CABLES SUBJ.

TO FIRE DAMAGE POWER SOURCE BY LACK OF CO T. SHUTDOWN COMPONENT AFFECTED SAFELY SHUT 12FA-SW-90B 2AVAC22-AT* NONE NONE NONE -

1B8YA-B* NONE NONE UNIT #2 ONLY ONE SW 1C8YA-C* lCSW cc 11SW20 PUMP AVAILABLE DUE TO 1C8YG-C* llSW VENT FAN DIESEL GEN. LIMITATION.

1C8YH-C* TURBINE BLDG MUST BE ISOLATED UTILIZING 2A8YA-A* lA SW cc 21SW20 2SW26. BY RESTORING 2C 2A8YG-A* 21SW VENT FAN 4KV BUS AND BY RESETTING 2A8YH-A* 2C SEC, 26 SWP COULD BE 2A8YHA-A STARTED TO PROVIDE ADEQUATE SERVICE WATER 2B8YA-B* NONE NONE FLOW FOR SAFE SHUTDOWN.

1B3D-B NONE 13 SWP 1C8Y-C NONE lC SW CC UNIT #1 TURBINE BLDG 1B3D-B NONE 13 SWP MUST BE ISOLATED BY lBBYE-B* NONE NONE MANUAL OPERATION OF lSTl 1B8YEA-B* NONE NONE OR 1SW26. TWO SW PUMPS 1B8YQ-B NONE 1SW26 AVAILABLE ON lA & lB 1B8YR-B NONE 12SW VENT FAN DIESEL GEN PROVIDE ADEQUATE SERVICE WATER 1C8YE-C* lC SW cc 11SW20 FLOW FOR SAFE SHUTDOWN.

1C8YEA-C* llSW VENT FAN 1C8YF-C 1C8YJ-C 1C8YJA-C 1C8YK-C*

1C8YR-C*

1C8YS-C 1CCDC8-CT NONE lSWVl 1SWV2 lSWVS 1SWV7 1SWV8 2B8YE-B NONE NONE 2B8YEA-B NONE NONE 2B8YR-B NONE 22 SW VENT FAN 2B8Y-B NONE 2Bl SW CC 22 SW VENT FAN PAGE 45 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO FIRE TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUT 12FA-SW-90B 2A3D-A 2A DIESEL G.EN 21 SWP (CONT'D) 2A8D-A 22 SWP

,2B3D-B 2B DIESEL GEN 23 SWP 24 SWP 1C3D-C NONE 11 SWP 2A8Y-A NONE 2A SW CC 21 SW VENT FAN 21SW20 1B8Y-B NONE !Bl SW CC 12 SW VENT FAN 15SW26 2A8YS-A 2A SW CC 21 SW VENT FAN 2A8YE-A* 21SW20 2A8YE-A*

2A8YJ-A*

2A8YJA-~*

2A8YK-A 2A8YR-A 1C8D-C NONE 12 SWP PAGE 46 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 12FA-SW-90A 1B15Y-B NONE 1B2 SW CC NONE -

14 SW VENT FAN ONLY ONE UNIT #2 SW PUMP AVAILABLE DUE TO 2CVAC15-CT* NONE NONE DIESEL GEN. LIMITATION.

TURBINE BLDG MUST BE 1A8YA-A* lA SW CC 13SW20 ISOLATED UTILIZING 1A8YG-A* 13 SW VENT FAN MANUAL OPERATION OF 2ST1 1A8YH-A* OR 2SW26. BY RESTORING 2A 4KV BUS AND RESETTING 1Bl5YA-B* 1B2 SW CC 14SW VENT FAN 2A SEC, 22 SWP COULD BE 2Bl5YA-B* NONE NONE STARTED TO PROVIDE ADE~UA~E SERVICE WATER 2C8YA-C 2C SW CC 23SW20 FLOW FOR SAFE SHUTDOWN.

2C8YG-C 23 SW VENT FAN 2C8YH-C 1A3D-A NONE 15 SWP 1A8D-A NONE 16 SWP 1A8Y-A NONE IA SW CC 13 SW VENT FAN 1A8YE-A* lA SW CC 13SW20 1A8YEA-A* 13 SW VENT FAN 1A8YF-A 1A8YJ-A*

1A8YJA-A*

1A8YK-A*

1A8YR-A*

1A8YS-A 1AADC18-AT NONE lSWVlO 1SWV4 1SWV3 1SWV9 1SWV6 PAGE 47 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTD 12FA-SW-90A lBlSYE-B* 1B2 SW CC 14 SW VENT FAN (CONT'D) lBlSYEA-B*

lBlSYR-B lBBD-B NONE 14 SWP 2BBD-B 2B DIESEL GEN 2B DIST. SYST.

23 SWP 24 SWP 2B15YE-B NONE NONE 2Bl5YEA-B NONE NONE 2B15YQ-B NONE 2SW26 2Bl5YR-B NONE 24 SW VENT FAN 2C3D-C 2C DIESEL GEN 2C DIST. SYST.

25 SWP 2CBD-C NONE 26 SWP 2C8YE-C* 2C SW cc 23SW20

.2CBYEA-C* 23 SW VENT FAN 2C8YF-C*

2C8YJ-C*

2CBYJA-C*

2C8YK-C 2CBYR-C*

2CBYS-C 2SWV9 2SWV4 2CBYH-C 2C SW CC 2C8YHA-C 2C8Y-C NONE 2C SW CC 23 SW VENT FAN 23SW20 2Bl5Y-B NONE 2B2 SW CC 24_ SW VENT FAN 2SW26 PAGE 48 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-EP-78C 2A2X-A NONE NONE NONE -

2A4X-A 2A & 2C DIVISIONS OF 2Al3Y-A POWER ARE AVAILABLE, 2A9X-A BASED ON EXISTING FIRE 2Al3X-A WRAP AND 20 FT. SEPAR-2A3YAH-A* ATION CRITERIA.

2A3YAR-A*

2A7YF-A 2A7YD-A 2Al3YA-A 2Al3YB-A 2A13YE-A* NONE NONE (WRAPPED/COORD.

>31' )

2A3YAB-A* NONE NONE (WRAPPED/COORD.

)27 I) 2ADC9-HT NONE NONE 2B13X-B NONE 22 CHILLER 2B2X-B NONE 22 CFCU 2B4X-B 2B 460V SWGR 22 CHILLER 2B8X-B 22 CFCU 2Bl3Y-B 24 CFCU 2B 230V SWGR 2B VITAL VENT CC 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22 CCW RM COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2B2 SW INTAKE CC 24 SW VENT FAN PAGE 49 OF 74

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHU 2FA-EP-78C 2SW26 (CONT'D) 2B AIR COND CC 22 CHILLER WATER PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl 125VDC BATTERY CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 20 VITAL INST.

BUS AUTO XFMR 2B6X-B NONE 24 CFCU 2B7YF-B 2B AIR COND CC 22 CHILLER WATER 2B7YD-B PUMP 2Bl3YD-B 2B VENT CC 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22* CCW RM COOLER PAGE 50 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-EP-78C 2Bl3YE-B NONE NONE (CONT'D) 2Bl3YM..,..B 2BDC9-ET 2C9X-C 2B9X-B 2Cl3X-C 2Cl4X-C 2Cl3YE-C*

2Cl3YL-C*

2Cl3YA-C 2Cl3YK-C 2Cl3YJ-C 2CVAC11-CT 2BVAC36-BT 2CVAC11-CT 2DVAC41-DT 2DVAC19-DT 2Al4X-A (NORMALLY DEENERGIZED) 2Cl3Y-C (CABLE WRAP) 2A3YAL-A

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTD FA-MP-7BI 2AVAC25-AT* NONE INST. PNL 827-2A NONE -

21 CFCU MUST FAIL AIR TO OPEN INLET & OUTLET VALVE FOR 2BVAC25-BT* NONE INST. PNL 827-2C

  • ONk CFCW. FUN CFCU IN 24 CFCU LOW SPEED.

2BVAC23-BT* NONE INST. PNL 827-2B MUST MANUALLY OPERATE 22 CFCU 2RH1 & 2RH2 FOR COLD -

SHUTDOWN.

2BVAC30-BT* NONE NONE 2BVAC28-BT*

2CVAC21-CT*

2CVAC20AA~CT*

2CVAC23-CT* NONE 23 CFCU (PANEL 8 27-20) 2CVAC25-CT* NONE PANEL 827-2E (25 CFCU) 2CVAC20A-CT* NONE NONE 2A5X-A* .

2A3YAR-A*

2A3YAB-A*

2A3YAL-A*

2A3YAQ-A*

2A3YAH-A* 2A EAST VALVES CC 2RHZ 2B3YBZE-B* NONE NONE 2B3YBK.;..B*

2B3YAA-B*

2BSX-B 2B3YBE-B 2B WEST VALVES CC 2SJ2 2SJ4 2SJ12 2CV41 PAGE 52 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-MP-78I 22CC16 (CONT'D) 22RH19 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B3YBF-B NONE 2SJ4 2B3YBG-B NONE 2SJ12 2B3YBP-B NONE NONE 2B3YBZC-B NONE NONE 2B3YBZD-B NONE NONE 2C3YAB-C NONE 2SJ5 2C3YAC-C NONE 2SJ13 2C3YAJ-C NONE NONE 2C3YAS-C NONE NONE 2C3YBX-C NONE 22SW22 2C3YAA-C NONE NONE 2C3YAF-C NONE NONE 2C3YAG-C NONE NONE 2C3YAK-C NONE NONE 2C3YAL-C NONE NONE PAGE 53 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-64A 2A5X-A NONE NONE NONE -

2A6X-A 2A & 2C POWER DISTRI-2Al0X-A BUTION ARE IMPACTED.

2Al2X-A UTILIZE 2B DIESEL GEN 2Al5X-A AND GAS TURBINE. WHEN 2Al6X-A GAS TURBINE IS AVAILABLE 2Bl0X-B POWER 2A 4KV BUS TO 2Bl5X-B RECOVER SECOND SW PUMP.

2AllY-A 2B9Y-B 2B2Y-B 2A3YA-A 2A 230V SWGR 2A VITAL VENT CC 2A9Y-A 21 RHR RM COOLER 23 CHRG PUMP RM COOLER 2 AFP RM COOLER 2A SW INTAKE CC 21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLER WATER PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 21RH29 2A DSL GEN CC PAGE 54 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-64A 21 FO XFR PUMP (CONT'D) 2A DSL GEN 2Al 125VDC BATTERY CHARGER 2Al 28VDC BATTERY CHARGER 2A VITAL INST.

INVERTER PWR SUPPLY 2A 460V SWGR 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23 CHRG PUMP 2A3YBW-AT NONE NONE 2ABYE-A 2Bl3YJ-B 2AVAC22-AT 2AVAC17-AT 2AVAC35A-AT 2BDC26-BT 2BDC28-DT 2DCA30-HT 2DCA37-HT PAGE 55 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-PP-92K 2A3YAX-A NONE NONE NON.E 2B3YAU-B 2B3YAV-B 2B3YAZB-B 2C3YAX-C 2C3YAY-C PAGE 56 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTD 2FA-AB-100C 2AllX-A NONE 21 BA XFR PUMP UTILIZE THE GAS TURBING 2Al2X-A NONE NONE TO RESTORE POWER TO THE 2BllX-B NONE NONE VITAL BOSSES. ONCE THE 2Bl2X-B NONE NONE VITAL BOSSES ARE RE-2CllX-C NONE 22 BA XFR PUMP ENERG I ZED THE MOTOR 2Cl5X-C NONE NONE CONTROL CENTERS CAN BE RESET AND THE. AFFECTED 2A7Y-A 2A 230V SWGR 2A VITAL VENT CC SYSTEM RESTORED TO A 2A4Y-A 21 RHR RM COOLER NORMAL SHUTDOWN CONFIGU-23 CHRG PUMP RM RATION. IF PRIMARY COOLER CONCERN IS THE VITAL 2AFP RM.COOLER VENTILATION AND ROOM COOLERS. THE AFFECTED 2A SW INTAKE cc** MOV'S ARE POSITIONED IN 21SW20 THE REQUIRED HSB 21 SW VENT FAN POSITION PREVIOUSLY.

DECAY HEAT REMOVAL WILL 2A AIR COND CC BE AVAILABLE INITIALLY 21 CHILLED WTR BY RUNNING 23 AFP AND PUMP STEAMING VIA THE MSlO's.

2A EAST VALVES CC 2RH2

  • 2PR6
  • 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 21RH29 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATTERY CHARGER PAGE 57 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-100C 2Al 28VDC BATTERY (CONT'D) CHARGER 2A VITAL INST.

INVERTER POWER SUPPLY 2A 460V SWGR 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23 CHRG PUMP 2B7Y-B 2B 230V SWGR 2B VITAL VENT CC 2B4Y-B 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22 CCW RM COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2B2 SW INTAKE CC 24 SW VENT FAN 2SW26 2B AIR COND CC 22 CHILLED WTR PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 PAGE 58 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-100C 2SJ4 (CONT'D) 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B *DSL GEN 2Bl 125VDC BATTERY CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 2D VITAL INST INVERTER POWER SUPPLY 2B VITAL INST BUS AUTO XFMR 2B 460V SWGR 22 CHILLER 22 CFCU 24 CFCU 2C4Y-C 2C 230V SWGR 2C VITAL VENT CC 22 CHRG PUMP RM COOLER 21 CCW RM COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 24BF13 2C WEST VALVES CC PAGE 59 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-100C 2SJ1 (CONT'D) 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERT POWER SUPPLY 2C 460V SWGR 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT. SHUTDOWN SYS XFMR 480V PRESSRZR HTRS (ALT. SD ONLY) 2A7YF-A 2A AIC COND. CC 21 CHILLER WATER 2A7YD-A PUMP 2B7YF-B 2B AIR COND. CC 22 CHILLER WATER 2B7YC-B PUMP 2B7YD-B 2A3YBQ-A 2A WEST VALVES 2CC30 21CC3 21CC16 21RH19 2A3YBP-A 2A EAST VALVES 2RH2 2PR6 PAGE 60 OF 74

~------------------------------------------------------

r ,

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB! TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-100C 2C3YBP-C 2C WEST VALVES 2SJ1 (CONT'D) 22CC3 22CC31 2CV40 22SW22 2C EAST.VALVES 2SJ5 2SJ13 23BF13 24BF13 2B3YBV-B NONE 2CV41 2B3YBS-B NONE NONE 2C3YBM-C NONE NONE 2C3YBK-C NONE 2CV40 2Al3YK-A 2A VENT CC 21 RHR RM COOLER 23 CHRG PUMP RM COOLER 2AFP RM COOLER 2Cl3YQ-C 2C VENT CC 22 CHRG PUMP RM 2Cl3YP-C COOLER 21 CCW RM COOLER 2DVAC14-DT NONE NONE 2DVAC11-DT NONE NONE 2CVAC25-CT NONE PNL 827-2E 25 CFCU 2CVAC20A-CT NONE NONE 2CVAC23-CT NONE PNL 827-20 23 CFCU 2CVAC10-CT NONE NONE 2VAC21-CT 2CVAC30-CT 2BVAC23-BT NONE 24CFCU PAGE 61 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORµIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-100C 2BVAC23-BT 22CFCU (CONT'D) 2BVAC30-BT NONE NONE 2BVAC28-BT 2BVAC10-BT 2AVAC39-AT 2AVAC36-AT 2AVAC25-AT NONE 21CFCU 2AVAC15-AT NONE NONE 2AVAC16-AT 2AVAC10-AT 2CVAC30-CT 2DCA16A-HT 2DCA16-HT 2DCB38-ET 2DCB34-ET 2DCC38-FT 2CDC22-CT 2CDC27-GT PAGE 62 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON ABI TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-64B 2ASX-A NONE NONE NONE -

2Al0X-A UTILIZE RHR FLOWPATH B.

2Al2X-A MUST MANUALLY OPERATE 2C5X-C 2RHZ FOR COLD SHUTDOWN.

2ClOX-C NORMAL CHARGING FLOW-2Cl5X-C PATHS ARE AVAILABLE.

2C3YAS-C 23, 24BF13 VALVES NOT REQUIRED, UTILIZE BF19 2A3YBW-AT 2A WEST VALVES 2CC30 & 40 VALVES.

21CC3 21CC16 21RH19 2A EAST VALVES 2RHR2 2PR6 2C3YBN-C 2C WEST VALVES 2SJ1 22CC3 2CC31 2CV40 22SW22 2C3YBR-C 2C EAST VALVES 2SJ5 2C3YAA-C 2SJ13 2C3YBG-C 23BF13 2C3YBQ-C 24BF13 2AVAC17-AT NONE NONE 2AVAC22-AT

.2CVAC3 9A-CT 2CVAC26-CT PAGE 63 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-84C 2CDD-C 2D DIESEL GEN NONE -

2A & 2B DIESEL GEN'S 2C9D-C NONE 22 CHRG. PUMP AVAILBLE.

2C8D-C 2C DIESEL GEN 2C3D-C 2A3YBZ-A NONE NONE 2A3YBT-A NONE 21CC3 2AVAC14-AT NONE NONE 2AVAC11-DT PAGE 64 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-84B 2Bl4X-B NONE NONE NONE -

2Bl6X-B BOTH CCW PUMP RM COOLERS 2C10X-C ARE IMPACTED. ONE CCW 2C5X-C PUMP CAN RUN ON AN ALTERNATING BASIS WITH 2B3YBM-B 2B WEST VALVE CC 22CC16 THE PUMP ROOM DOOR OPEN.

2B3YBW-B 22RH19 THE AUX BLDG VENT SYSTEM 2SJ2 WILL PROVIDE AIR FLOW 2SJ4 THROUGH THE ROOMS. WHEN 2SJ12 2C VITAL VENT CC IS 2CV41 RESTORED 21 CCW PUMP ROOM COOLER CAN BE 2A3YBR-A 2B EAST VALVES 2RH1 RETURNED.

2B3YBZA-B 2PR7 2B3YBZB-B 21BF13 2B3YBD-B 22BF13 2B3YBS-B 2A3YBN-A 2A WEST VALVES 2CC30 21CC3 21CC16 21RH19 2A EAST VALVES 2RH2 2PR6 2C3YBG-C 2C WEST VALVES 2SJ1 2C3YBQ-C 22CC3 2CC31 2CV40 22SW22 2C EAST VALVES 2SJ5 2SJ13 23BF13 24BF13 PAGE 6-5 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-AB-84B 2Cl3YB-C 2C VENT CC 22 CHRG PUMP RM (CONT'D) COOLER 21 CCW RM COOLER 2Cl3YG-C NONE NONE 2AVAC22-AT 2AVAC17-AT 2AVAC14-AT 2DVAC11-DT 2CVAC39A-CT 2BVAC14-BT PAGE 66 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-TGA-88 2B3YAM-B 2B EAST VALVES CC 2RH1 NONE -

2B3YAN-B 2PR7 MANUALLY OPERATE 2RH1 21BF13 FOR COLD SHUTDOWNe 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2C3YAT-C 2C EAST VALVES CC 2SJ5 2C3YAU-C 2SJ13 23BF13 24BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2B3YAV-B NONE NONE 2DCA14-HT 2DCA29-HT 2ADC10-FT 2ADC12-AT 2ADC13-AT 2BDC10-ET 2BDC12-BT 2BDC13-BT 2BDC15-GT 2CCDC24-CT NONE 21BF19 22BF19 21BF40 22BF40 PAGE 67 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO

  • FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-TGA-88 2DCC9 NONE NONE (CONT'D) 2DCD24-DT NONE 23BF19 24BF19 23BF40 24BF40 2DCD41-GT NONE NONE 2DCD7-GT 2DCD32-GT 2CVAC31-CT 2BVAC31-BT 2AVAC31-AT PAGE 68 OF 74

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTD 2FA-RC-78 2A13YAP-A N/A N/A SUBJECT TO SINGLE TRAIN 2A13YBP-A EXPOSURE FIRE ONLY. A 2A3YAEP-A COMBINATION OF RADIANT 2A3YAMP-A ENERGY SHIELDING, 2A3YAPP-A DISTANCE, LOCALIZED 2A3YACP-A SUPPRESSION, DETECTION, AND REDUCED LOCALIZED AREA FIRE LOADING ACCOUNT FOR THE PROTECTION AFFORDED REDUNDANT CABLING IN THIS FIRE AREA. FIRE DAMAGING TRAIN 2A SHUTDOWN CABLES DOES NOT ADVERSELY IMPACT SHUTDOWN UTILIZING TRAINS 2B AND 2C.

2B13YAP-B N/A N/A SUBJECT TO SINGLE TRAIN 2Bl3YBP-B EXPOSURE FIRE ONLY. A 2B3YAEP-B COMBINATION OF RADIANT 2B3YAGP-B ENERGY SHIELDING, DISTANCE, LOCALIZED SUPPRESSION, DETECTION, AND REDUCED LOCALIZED AREA FIRE LOADING ACCOUNT FOR THE PROTECTION AFFORDED REDUNDANT CABLING IN THIS FIRE AREA. FIRE DAMAGING TRAIN 2B SHUTDOWN CABLES DOES NOT ADVERSELY IMPACT SHUTDOWN UTILIZING TRAINS 2A AND 2C.

PAGE 69* OF 7 4

POWER CABLES SUBJ. POWER SOURCE SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COO AFFECTED

  • SAFELY SHUTD WN 2FA-RC-78 2C13YAP-C N/A N/A SUBJECT TO SINGLE TRAIN (CONT'D) 2C13YEP-C EXPOSURE FIRE ONLY. A 2C13YAEP-C COMBINATION OF RADIANT 2C13YAVP-C ENERGY SHIELDING, DISTANCE, LOCALIZED, SUPPRESSION, DETECTION, AND REDUCED LOCALIZED AREA FIRE LOADING ACCOUNT FOR THE PROTECTION AFFORDED REDUNDANT CABLING IN THIS FIRE AREA. FIRE DAMAGING TRAIN 2C SHUT-DOWN CABLES DOES NOT ADVERSELY IMPACT SHUT-DOWN UTILIZING TRAINS 2A AND 2B.

2A2XP-A NONE 21 CFCU *NONE. POTENTIAL EXISTS FOR LOSS OF POWER TO 2A4XP-A 2A 230V SWGR 2A VITAL VENT CC ALL THREE TRAINS BELOW 21 RHR RM COOLER 4KV WHICH WILL RESULT 23 CHRG PUMP RM IN LOSS OF DIESEL COOLER GENERATORS. TURBINE 2AFP RM COOLER DRIVEN #23 AUX FEED PUMP WILL BE UTILIZED PRIMARY 2A SW INTAKE CC COOLING. GAS TURBINE 21SW20 WILL BE UTILIZED TO 21 SW VENT FAN RESTORE POWER. TO THE 4KV LEVEL. THIS WILL 2A AIR COND CC RESTORE SERVICE WATER 21 CHILLER WATER FUNCTION AND ALONG WITH PUMP RESETTING OF 4KV/230V FEEDER ALLOW OPERABILITY 2A EAST VALVES CC OF D.G.'S NORMAL SHUT-2RH2 DOWN WOULD THEN PROGRESS 2P.R6 AT WHICH TIME AT LEAST ONE CFCU WILL BE PAGE 70 OF 74

POWER CABLES SUBJ. POWER SOURCE CT. SHUTDOWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-RC-78 2A WEST VALVES CC AVAILABLE IN LOW SPEED (CONT'D) 2CC30 TO SUPPORT NECESSARY 21CC3 CONTAINMENT COOLINGo 21CC16 NO OTHER SHUTDOWN SYSTEM 21RH19 IMPACT IS EXPERIENCED.

21RH29 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATTERY CHARGER 2Al 28VDC BATTERY CHARGER 2A VITAL INST INVERTER POWER SUPPLY 2A 460V SWGR 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23 CHRG PUMP 2B2XP-B NONE 22 CFCU 2A4XP-A NONE 24 CFCU 2B4XP-B 2B 230V SWGR 2B VITAL VENT CC 2B8XP-B 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22 CCW RM COOLER 2Bl SW INTAKE CC 22 SW VENT FAN PAGE 71 OF 74

(

POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTD 2FA-RC-78 2B2 SW INTAKE CC (CONT'D) 24 SW VENT FAN 2SW26 2B AIR COND CC 22 CHILLER WATER PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl 125VDC BATTERY CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 2D VITAL INST INVERTER POWER SUPPLY 2B VITAL INST BUS AUTO XFMR PAGE 72 OF 74

r POWER CABLES SUBJ. POWER SOURCE T. SHUTDOWN COMPONENT IMPACT ON AB TO

  • FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-RC-78 2B 460V SWGR 22 CHILLER (CONT'D) 22 CFCU 24 CFCU 2C2XP-C NONE 23 CFCU 2C6XP-C NONE 25 CFCU 2C4XP-C 2C 230V SWGR 2C VITAL VENT CC 2C8XP-C 22 CHRG PUMP RM COOLER 21 CCW RM COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 24BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERT POWER SUPPLY PAGE 7.3 OF 74

1' POWER CABLES SUBJ. POWER SOURCE. T. SHUTDOWN COMPONENT IMPACT ON AB TO r' FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN. AFFECTED SAFELY SHUTDOWN 2FA-RC-78 2C 460V SWGR 23 CHILLER (CONT'D) 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT. SHUTDOWN SYS XFMR 4BOV PRESSRZR HTRS (ALT. SD ONLY)

PAGE 74 OF 74