ML18093A760

From kanterella
Jump to navigation Jump to search
Appendix R/Breaker Coordination as-Found Review (Pre-Audit 1987)
ML18093A760
Person / Time
Site: Salem 
Issue date: 02/18/1988
From: Adams M
Public Service Enterprise Group
To:
Shared Package
ML18093A759 List:
References
S-C-M200-NDM-06, S-C-M200-NDM-0610-0, S-C-M200-NDM-6, S-C-M200-NDM-610, NUDOCS 8803300215
Download: ML18093A760 (79)


Text

,-.. ----

It PS~G Page S-C-M200-NDM~061Q-0 Date

1. of 3 2/18/88 Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department TITLE:

APPENDIX R/BREAKER COORDINATION "AS FOUND" REVIEW (PRE-AUDIT 1987) 1~0 PURPOSE To provide/document the methodology to be used to complete the review of Appendix R/breaker coordination impact for Salem Unit 2 for the design contiguration of September 1987.*

2.0 SCOPE This effort involves a review of the identified associated*

circuits with a common power source, as defined in Generic Letter 81-12.

These associated circuits shall be defined in accordance with.the 1987 Salem Unit 2 Safe Shutdown model and a review of the electrical drawings and the Appendix R Area Assessments.

3.0 REFERENCES

3.1 Appendix R to 10CFR50 3.2 Generic Letter 81-12 3.3 1987 Salem Safe Shutdown Model 3.4 Fire Hazards Analysis Salem Nuclear Generating Station Units 1 and 2 3.5 1987 Sal~m Appendix R Area Assessments 3.6 Generic Letter 86-10 3.7 Appendix R Safety Evaluation (S-C-M200-NSE-0709) 3.8 Breaker Coordination Safety Evaluation (S-C-E500-NSE-0675) 3.9 Ebasco Short Circuit Calculation 3.10 Station Loss of Busses (AOP~ELEC-) Operating Procedures 3.11 Fire Area Exemption Requ~sts (NLR-N86005 & NLR-86202) 3.12 Inspection Report No. 50-311/87-29 (Salem 2 ~eptember 1987 Appendix R Audit)

-~. be.. ~<;-'=°='(>().-' l c::--**=-*-.c>*-=- 1 o -0*.

UQ

~~-

4.~ ~~ ~ U PDR.ADOCK 05000311'

___.. SJ....

DCD *

  • -----------------------------i Ddm2/ma Tl..,e Energy P8c;_'.
  • ~'

. j

S-C-M200-NDM-061Q-0 Page 2 of 3 Date:. 2/18/88 4.0 DISCUSSION In response to a request by the NRC (reference 3.12), a review of

.the electrical distribution configuration concentrating in the area of breaker coordination will be performed on the basis of an Appendix R postulated exposure fire hazard.

The configuration under study will b~ the distribution system in its pre-restart rnodif ication format *.

Ddm2/ma An engineering evaluation will be issued at the completion of this effort to document all findings.

4.1 Associated Circuit (common power source) Methodology 4.1.1 Utilize 1987 Salem Shutdown Model to review Salem Electr1cal Single Lines and identify safe shutdown and associated circuit loads.

4.1.2 Review the Tenera Unit 2 Appendix R Area Assessments to determine safe shutdown trains that will be utilized to achieve shutdown.

This information will serve to identify "associated" safe shut~own cables for analysis.

4.1.3 Once associated circuits are identified, document voltage level, safety ~hannel, cable route and length, fire area, and reference drawings on cable input forms (Attachment A).*

Information as to whether the raceway is fire wrapped will aiso be provided.

4.1.4 Define where the breaker becomes coordinated.

  • Define what level of short circuit current/cable length at which the co?rdination occuis.

4.1.5 Should the breaker not be coordinated, review for protection with fire wrap.

  • 4.1.6 Should neither breaker coordination nor fire barriers be acceptable for mitigating the associated ~ircuit's expos~re, review ~he area for exemption request commitments.

4.1.7 Sh6uld neither breaker coordination, noi fire wrap, nor exemption request commitments mitigate exposure fire damage, review for application of AOP-ELEC or EOP-LOPA.

s-c.'.-M200-NDM- 0610:-0 Paqe 3 of 3 Date:

2/18/88 4.1.8 The comment section of the cable input forms shall be utilized to disposition each associated circuit, and provide data for preparation of the final engineering *evaluation.

5.0 ACTION Personnel assigned to*Appendix R/Breaker Coordination Task Force shall utilize the methodology provided in this design memo.

6.0 SCHEDULE In accordance with the commitments established by PSE&G upper management, the effort is scheduled to be completed by March 4, 1988.

7.0 FUNDING AUTHORIZATION To be provided t6 participating members of the task £orce on a need to know basis.

  • 8.0 ATTACHMENTS 8.1 Cable Input Form 8.2 Appendix R/Breaker Coordination Flow Chart 9.0 SIGNATURES

./:* 4>/.--...

~' /1 *<l'i~<

Originator's Group Head roate Nuclear En ering Sciences Manager

/

~&;~o:<JJ

_ NucleaEl ctrical

_Engineering Manager C !r:/{;;(,.,d>>w,, /~*A u Manager-Nuclear

/

l ate Engineering Speciaf Projects m4e Date

ii*

I

  • .u.t1

- ---- JI Wtl ------ -- - *- -

~II LIT f __ l_IlTTD I *I' I I

r-r1=i I I I I I EL~J L_IIJ. I_ I t~l-LID [0 f_ITf~J=r[J_-_[J. I l!E1 I

_l_L_[J~lTI-o 111~J LI I LJIO_( 111 ITEJ

[TilTJ_L ITI_J ~

[=-r=1~~rJ __ ] __ JTI ~J L-1 I I t~I~rJ ~J=rI_] [8]~

I I 1=1~-[J~r-_r __ [_1 ITEJ I IT.J-=:[J~_JJ=1 [~1~J [l I l_-t=]~J~l~J __ l_JJ l!T1J I I DTI=t.. LJ J S3 IT_lT[JTI f~l~I 1_-rr1-r=-t~[~T~-:[_[J] [iEJ I I LlJ_l~L L_ f __ I Isl 0 1

[=:t~:r_1--1 11 J l sEl r-_[IJ_-1_- r-1_ I~ L~tJ f~~

LI Ll~J=_E~J h,I 0 I I

I I I J-[]~[J L~ I~ I I. ITJ-.. 1 _ I I. I I __ '_ LJ~] [~-r~l. ~

I I I. L_l_J_J ITE1 I

I rT--f_JT[J E-Ed LCCl_JJ~[] __ l_TIJ EEi

~

_O I I I I I 03 I I r1-1r1-1TJ EE] ITI I I rn I. I -11 EE] ~

Ll_

I I I I I I 1 I 0 I I I I I I -1 I I I I I I / I 0 I I I I I I I I I I I I I EEi t lWMJlWH JlNJOOIS 9NllnOH J18W:J IT LI I I I LJ LI I I ITI ITLITTI_t' LI t"JTI=rJ I

MtllnOJ "OYJ *

  • * *
  • 1* *
  • rr-B-__ r~ rTTTJ 1 1 ITJ]
  • ,*rrn' 1111*111,*,,, 1.11111 CI]l LL _ ITJTITLIILD r,... '. i, *.

'9.A9 _

.,ay n':.i.

,.., - -,a,

"/'7l'iJ

  • ot1
J,,,.~

~

0 I I I I I I I I I I hl'u

  • 'J**a.,,,

.Q, D,,.Q

~.!M.

~\\

- S/D MODEL

- DESIGN DRWNG

- GENERIC LETTER 81-12

- AREA ASSESSMENTS ECO 2/17/88 CLRSTDCP APPENDIX A/BREAKER COORDINATION

...:..s FOUND" FLOWCHART START ID ASSOCIATED CIRCUITS (COMMON POWER SOURCE) BY FIRE AREA FOR ASSOCIATED CIRCUITS DEFINE:

VOLTAG~ ROUTINa

- CCR FIRE ARE~ REF.. * - DESIGN DRAWINGS, CHANNEL DRAWINGS OF POWER SOURCE IDENTIFY REDUNDANT POWER SOURCE CHANNELS ROUTED IN SAME FIRE AREA

- SAFETY EVALUATIONS

- RESTART DCP's

- FIRE WATCH LISTS

- IDENTIFY AS A CONCERN

- VERIFY COMPENSATORY MEASURES. NOW IN PLACE

- DOCUMENT VIA ENGIN-EERING EVALUATION WOULD APPLICATION YES OF LOSS OF AC POWER PROCEDURE MITIGATE THE PROBLEM?

EXEMPTION.REQUEST LETTER JAN. 1986 NO DID FIRE YES PROTECTION YES IMPROVEMENT PROGRAM COMMIT TO PROTECTING FIRE WRAP DRAWINGS CCR - CABLE CONTROL REPORT.

THE CABLE

?

IS CABLE YES

- SHORT CIRCUIT CALCULATION

- RELAY/PROTECTIVE DEVICE CURVES FIRE WRAPPED UNTIL COORDINATION OBTAINED?

NO YES FINISH DOCUMENT ACCEPTABILITY

12FA-AB-100A POWER CABLES SUBJ.

TO FIRE DAMAGE lA 7YF-A 1AADC26-AT 1CCDC24-CT 1ADC22-ET*

2BDC22-ET*

2CCDC24-CT POWER SOURCE~T.

BY LACK OF COORDIN.

lA 230V VITAL AC CC NONE NONE NONE NONE NONE SHUTDOWN COMPONENT AFFECTED

  1. 11 CHILLED WATER PUMP NONE NONE NONE NONE NONE PAGE 1 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE-UTILIZE #12 CHILLED WATER PUMPo

l 2FA-AB-122A POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COO lADCl-AT*

lADCl 7-HT*

1BDC17-ET*

lCDCl 7-ET*

1A7YC-A*

lA 7YD-A*

1A7YA-A*

1B7YC-B*

!Cl 3YQ-C*

1Cl3YP-C*

2A2Y-A*

2ADC1-AT*

2ADC1 7-HT*

2A7Y-A 2A 7YF-A 2BDC1 7-ET*

2CDC1 7-FT*

2A7YC-A*

2A7YA-A*

2B7YC-B*

2Cl 3YP-C*

NONE NONE NONE NONE lA VITAL AI:R COND.

cc NONE NONE lB VITAL AIR COND.

cc lC VITAL VENT CC

  • lC VITAL VENT CC NONE NONE NONE 21 VITAL AIR COND cc 2A VITAL AIR COND cc NONE NONE 2A VITAL AIR COND cc 2A VITAL AIR COND cc 2B VITAL AIR COND cc 2C VITAL VENT CC NONE NONE NONE NONE AFFECTED
  1. 11 CHILLED WATER PUMP NONE NONE
  1. 12 CHILLED WATER PUMP
  1. 12 CHARGING PUMP ROOM COOLER
  1. 11 COMPONENT COOLING PUMP ROOM COOLER
  1. 12 CHARG. PUMP RM COOLER
  1. 11 COMP CLG PUMP RM COOLER NONE NONE NONE
  1. 21 CHILLED WATER PUMP
  1. 21 CHILLED WATER PUMP NONE NONE
  1. 21 CHILLED WATER PUMP
  1. 21 CHILLED WATER PUMP
  1. 22 CHILLED WATER PUMP
  1. 22 CHARGING PUMP ROOM COOLER
  1. 21 COMP. COOLING PUMP ROOM COOLER PAGE 2 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE-ALT. SHUTDOWN PRO-CEDURES WOULD BE IMPLE-MENTED.

CLEAR lB VITAL AIR COND CC.

CLOSE IN SWGR BREA-KER TO POWER lB VITAL AIR COND. CC -

CLOSE IN

  1. 12 CHILLED WATER PUMP.

RESET 2A 230V SWGR BRKR AND 2A VITAL AIR COND.

CC.

2B VITAL AIR COND.

CC AND #22 CHILLED WATER PUMP ARE THEN OPERABLE.

FIRE AREA 12FA-AB-122A (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2Cl 3YQ-C*

  1. 22 CHARG. PUMP RM COOLER
  1. 21 COMP. COOLING PUMP RM COOLER PAGE 3 OF 74 IMPACT ON AB Y TO SAFELY SHUTDOWN

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT IMPACT ON AB y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED SAFELY SHUTDOWN 2FA-AB-64Al 2ADC25-AT NONE NONE NONE-UTILIZE TRAINS 2A 2CDCA-C 2C 125VDC BA'I'.TERY NONE (BATT. CHRGR) 2B.

2CDCB-C 2C 125VDC BATTERY NONE (BATT. CHRGR)

PAGE 4 OF 74

FIRE AREA 2FA-AB-45A POWER CABLES SUBJ~

TO FIRE DAMAGE 2BY6BN-B*

2C3YBN-C*

2A7D-A 2Al 3YH-A 2A3YBD-A 2A3YBE-A 2A3YBF-A 2A3YBK-A 2A3YBU-A POWER SOURCE CT.

BY LACK OF COORDIN.

2B WEST VALVES CC 2B EAST VALVES CC 2C WEST VALVES CC 2C EAST VALVES' CC NONE NONE NONE 2A WEST 2A EAST NONE NONE NONE VALVES CC VALVE CC SHUTDOWN COMPONENT AFFECTED IMPACT ON AB

"'y TO SAFELY SHUTDOWN 2SJ4 2SJ12 22RH19 2RH1 21BF13 22BF13 2SJ1 2SJ5 2SJ13 23BF13 2 4BF13

  1. 21 RHR
  1. 21 RHR 21CC16 21CC16 21RH19 2RH2 NONE NONE 21RH19 NONE -

21-24BF13 ARE NOT REQUIRED.

UTILIZE 21-24BF19 & 40 VALVES.

21RH19, 21 RHR PUMP, &

21 RHR ROOM COOLER ARE NOT REQUIRED.

UTILIZE 22 RHR FLOWPATH. 22RH19, 2RH1, & 2RH2 MUST BE MANUALLY OPERATED FOR COLD SHUTDOWN UNLESS VALVE cc*s ARE RESTORED.

21CC16 NOT REQUIRED-UTILIZE 22CC16.

PUMP 2SJ1, 2SJ4, 2SJ5, 2SJ12, ROOM COOLER & 2SJ13 ARE NOT RE-QUIRED.

NORMAL CHARG-ING, LETDOWN, & BORIC ACID FLOWPATHS ARE AVAILABLE.

PAGE 5 OF 74

FIRE AREA 2FA-AB-45B POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2C3YBR-C*

2B3YBN-B*

2B3YBR-B*

2C3YBJ-C*

2Bl3YH-B 2B3YBH-B 2B3YBL-B*

2B3YBT-B*

2B3YBU-B*

2B3YBX-B*

2B7D-B 2C WEST VALVES CC 2C EAST VALVES CC 2B WEST VALVES CC 2B EAST VALVES cc*

SAME AS 2B3YBN-B NONE NONE SAME AS 2B3YBN-B NONE NONE NONE NONE NONE 2SJ1 2SJ5 2SJ13 23BF13 24BF13 2SJ4 2SJ12 22RH19 2RH1 21BF13 22BF13 SAME AS 2B3YBN-B NONE

  1. 22 RHR ROOM COOLER SAME AS 2B3YBN-B NONE NONE NONE NONE 22 RHR PUMP PAGE 6 OF 74 IMPACT ON AB Y TO SAFELY SHUTDOWN NONE -

2l-24BF13 REQUIRED.

21-24BF19 ARE NOT UTILIZE

& 40 VALVES.

22RH19, 22 RHR PUMP, &

22 RHR ROOM COOLER ARE NOT REQUIRED.

UTILIZE 21 RHR FLOWPATH.

2RH1 MUST BE MANUALLY OPER-ATED FOR COLD SHUTDOWN UNLESS 2B EAST VALVE CC IS RESTORED.

2SJ1, 2SJ4, 2SJ5, 2SJ12,

& 2SJ13 ARE NOT RE-QUIRED.

NORMAL CHARG-ING, LETDOWN, & BORIC ACID FLOWPATHS ARE AVAILABLE.

FIRE AREA 2FA-DG-84D POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2A3YBS-A*

2BDD-B(CABLE IS FIRE WRAPPED) 2C3YBW-C*

2CGN-C 2CDD-C 2CDDA-C 2BDDA-B (PROPOSED FIRE WRAP COMPENSATORY. MEAS-URES IN PLACE)

NONE NONE NONE 2C DG 2C DIESEL 2C DG NONE GEN NONE NONE NONE 2C DG OF 2C TRAIN 2C DIESEL & 2C DISTRIBUTION SYS NONE PAGE 7 OF 74 IMPACT ON AB Y TO SAFELY SHUTDOWN NONE -

2A & 2B DIESEL GEN POWER TRAINS AVAILABLE FOR SAFE SHUTDOWN.

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDQWN COMPONENT IMPACT ON AB Y TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED SAFELY SHUTDOWN 2FA-DG-84G 2B4YG-B*

NONE 22 FUEL OIL TRANS-NONE

~ UTILIZE 21 FUEL FER PUMP OIL TRANSFER PUMP PAGE 8 OF 74

2FA-DG-84H POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO 2A3YBS-A*

NONE 2A4YG-A NONE SHUTDOWN COMPONENT AFFECTED NONE 21 FUEL OIL TRANS-FER PUMP PAGE 9 OF 74 IMPACT ON AB SAFELY SHUT Y TO NONE -

UTILIZE 22 FUEL OIL TRANSFER PUMP.

2FA-SB-100

r.

- POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF C 1CCDC24-CT 1DCD24-DT 2DCD24-DT NONE NONE lDDC 125V DIST. CAB 2DDC 125V DIST. CAB PAGE 10 OF 74 AFFECTED IMPACT ON AB SAFELY SHU TO NONE-LIMITED TO LOSS OF "D" 125VDC DIST. CAB

FIRE AREA 2FA-DG-84F POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPO~ENT IMPACT ON AB Y TO TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED SAFELY SHUTDOWN 2A3YBS-A NONE 2A446-A*

NONE (CABLE WRAP) 2ADD-A*

NONE (CABLE WRAP) 2Bl5Y-B*

2B 230V SWGR (230V SWGR TO 282 SERV. WTR CC) 2B8Y-B*

(230V SWGR TO 281 SERV. WTR CC)

NONE NONE NONE NONE -

2A I 28, & 2C DIESEL GEN'S AND SERVICE WATER ARE IMPACTED.

THE "A" SW PUMP WOULD BE AVAIL-2B VITAL VENT CC ABLE ONCE POWER IS 22 RHR RM COOLER RESTORED VIA THE GAS 21 CHRG PUMP RM CLR TURBINE.

THE RESULT OF 22 CCW RM COOLER THIS IS THAT THE SERVICE 2Bl SW INTAKE CC 22 SW VENT FAN 282 SW INTAKE CC 24 SW VENT FAN 2SW26 2B AIR COND CC 22 CHILLED WTR PUMP 2B EAST VALVES CC 2RH1 2PR7 218Fl3 228Fl3 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 2*2 FO XF R PUMP 28-DSL GEN WATER SYSTEM AND COOLENT COOLING WATER SYSTEMS WOULD OPERATE AS DESIGNED, AND NO ALTERNATE COOLING TO THE CHARGING PUMPS WOULD BE NECESSARY.

PAGE 11 OF 74

FIRE AREA 2FA-DG-84F (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO 2B 460V SWGR 2B3D-B*

NONE (FIRE WRAP COMMIT.)

2B4YG-B*

NONE 2B8D-B NONE (FIRE WRAP COMMIT 2C 3D-C

(IF BEING USED) 2C3YBW-C*

NONE 2C 8D-C

  • 2C 2 30V SWGR SHUTDOWN COMPONENT AFFECTED 2Bl l 25VDC BATT CHRGR 2Bl 28VDC BATT CHRGR 2B&2D VITAL INST INVERTER PWR SUPPLY 2B VITAL INST BUS AUTO XFMR 22 CHILLER 22 CFCU 24 CFCU NONE 22 DG FUEL OIL TRAN SF ER PUMP NONE 2C DIST SYS LOADS NONE 2C DIST SYS LOADS 2C VITAL VENT CC 22 CHRG PUMP RM CLR 21 CCW RM COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 2 4]3Fl 3 PAGE 12 OF 74 IMPACT ON AB SAFELY SHUT TO

FIRE AREA 2FA-DG-84F (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2C 460V SWGR 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERTER PWR SUPPLY 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT SHUTDOWN SYS XFMR 480V PRESSRZR HTRS (ALT SD ONLY)

PAGE 13 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

2FA-SB-100 POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COO 1CCDC24-CT 1DCD24-CT 2DCD24-DT NONE NONE lDDC 125V DIST CAB 2DDC 125V DIST CAB PAGE 14 OF 74 AFFECTED IMPACT ON.AB TO SAFELY SHUTDOWN NONE

FIRE AREA 2FA-TGA-88 POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2ADC10-FT*

2ADC12-AT*

2ADC13-AT*

2BDC10-ET*

2BDC12-BT*

2BDC13-BT*

2BDC15-GT*

(NORM DEENERGIZED) 2B3YAU-B*

2B36AV-B*

2C3YAX-C*

2B3YAM-B

( 21BF13) 2B3YAN-B

( 2 2BF13) 2C3YAT-C

( 2 3BF13) 2C3YAU-C

( 2 4BF13) 2CCDC24-CT

( 2lBF19)

. ( 22BF19)

(21BF40)

( 2 2BF40)

NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE 2B EAST VALVES CC 2B WEST VALVES CC 2C EAST VALVES CC 2C WEST VALVES CC NONE NONE NONE.

NONE NONE NONE NONE NONE NONE NONE NONE 2RH1 21BF13 22BF13 2SJ4 2SJ12 22RH19 2SJ5 2SJ13 23BF13 24BF13 2SJ1 NONE (PNEUMATICALLY FAIL SAFE)

PAGE 15 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

21-24BF13 ARE NOT REQUIRED.

FAIL CLOSE 21-24-BF19 & 40 VALVES.

22RH19 IS NOT REQUIRED, UTILIZE 21RH19.

2RH1 MUST BE MANUALLY OPERATED FOR COLD SHUT-DOWN UNLESS 2B EAST VALVE CC IS RESTORED.

2SJ1, 2SJ4, 2SJ5, 2SJ12

& 2SJ13 ARE NOT RE-QUIRED.

NORMAL CHARG-ING, LETDOWN, & BORIC ACID FLOWPATHS ARE AVAILABLE.

FIRE AREA 2FA-AB-100A POWER CABLES SUBJ.

TO FIRE DAMAGE 2Al 3YK-A*

2A7YD-A*

2ADC1-AT*

2ADC20-AT (NORMALLY DEENERGIZED) 2Bl 3YM-B*

2B7YD-B*

2BDC1 7-ET*

2BDC19-BT (NORMALLY DEENERGIZED) 2BDC21-DT (NORMALLY DEENERGIZED) 2BDC24-BT (NORMALLY DEENERGIZED) 2Cl 3YP-C*

2Cl 3YQ-C*

2COC11-CT 2COC1 7-FT*

2AADC6-AT 21\\ADCS-AT 2AAOC33-AT 2CCDC5-CT 2AADC11-AT 2CCDC30-CT 2CCDC13-CT POWER SOURCE CT.

BY LACK OF COORDIN.

2A VENT CC

'2A AIR COND CC NONE NONE NONE 2B AIR COND. CC NONE NONE NONE NONE 2C VENT cc 22 VENT CC NONE NONE SHUTDOWN COMPONENT AFFECTED 23 CHARGE PMP. RM.

CLR.

  1. 2 AFW PMP RM. CLR.
  1. 21 RHR PMP. RM.

CLR.

  1. 21 CHILLED WATER PUMP NONE NONE NONE 22 CHILLED WATER PUMP NONE NONE NONE NONE
  1. 22 CHRG. PMP. RM.

CLR.

  1. 21 CCW PMP. RM.

CLR.

  1. 22 CHRG. PMP. RM.

CLR.

  1. 21 CCW PMP. RM.

CLR.

NONE NONE PAGE 16 OF 74 IMPACT ON AB Y TO SAFELY SHUTDOWN NONE-ALT. SHUTDOWN PROCEDURES WOULD BE IMPLEMENTED.

2F A-AB-lOOA (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO 2A5YA-A 2A 7YF-A 2B5YA-B 2B5YB-B 2B7YF-B 2CllY-C (NORMALLY DEENERGIZED) 2C5YA-C 2C5YB-C 2C6YC-C 2CCDC24-CT (21BF19, 22BF19)

(21BF40, 22BF40) 2CDC21-CT 2AZY-A*

2C ZY-C NONE 2A AIR COND. CC 2B AIR co~m. cc NONE NONE NONE NONE SHUTDOWN COMPONENT AFFECTED

  1. 21 CHILLED WATER PUMP
  1. 22 CHILLED WATER PUMP NONE NONE NONE NONE PAGE 17 OF 74 IMPACT ON AB SAFELY SHUTD TO

FA-PP-lOOH POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF COO 2A3YAV-A 2B3YAB-B 2B3YAC-B 2B3YAZA-B 2C3YAW-C 2C3YAZ-C NONE NONE NONE NONE NONE NONE T.

SHUTDOWN COMPONENT NONE NONE NONE NONE NONE NONE AFFECTED PAGE 18 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE

POWER CABLES SUBJ.

FIRE TO FIRE DAMAGE 2FA-EP-100G 2Al3YA-A*

2Al 3YB-A*

2Al 3YE-A*

2Al 3YG-A*

2Al 3YH-A {21 RHR RM COOLER) 2Al 3YF-A { 2 AFW RM.

COOLER) 2Al 3YC-A { 23 CHRG.

RM. COOLER) 2Al 3YK-A*

2Al3YJ-A*

2A9X-A*

POWER SOURCE T.

BY LACK OF CO 2A VITAL VENT cc 2A 460V SWGR 2A 230V SWGR SHUTDOWN COMPONENT AFFECTED IMPACT ON AB SAFELY SHUTD

  1. 23 CHRG. PUMP RM.

NONE -

C LR.

ON LOSS OF 2A & 2C

  1. 2 AFW PMP. RM. CLR DIESEL GENS RUN AUX
  1. 21 RHR PMP. RM.

FEED TURBINE DRIVEN TO CLR.

PUMP.

UTILIZE 2B DIESEL GEN. AND GAS TURBINE FOR POWER DISTRIBUTION.

UTILIZE MOTOR DRIVEN PUMPS WHEN ON GAS TURBINE.

MANUALLY OPERATE 2RHZ FOR COLD -

SHUTDOWN.

  1. 21 CHILLER
  1. 21 BORIC ACID XFR PMP.
  1. 21 CFCU
  1. 23 CHRG PUMP 2A VITAL VE~T CC 21 RHR RM COOLER 23 CHRG PUMP RM CLR 2AFP RM COOLER 2A SW INTAKE CC 21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLED WTR PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 PAGE 19 OF 74

FIRE AREA 2FA-EP-100G (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 21RH19 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATT CHRGR 2Al 28VDC BATT CHRGR 2A VITAL INST INVERTER PWR SUPPLY IMPACT ON AB Y TO SAFELY SHUTDOWN 2Al 3Y-A 2A 230V SWGR 2A 460V SWGR NONE SEE ABOVE SINGLE FAILURE FIRE 2B9X-B*

2C9X-C*

2C 460V SWGR 2C 230V SWGR SEE ABOVE NONE 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT SHUTDOWN SYS XFMR 480V PRESSRZR HTRS (ALT. SD ONLY) 2C VITAL VENT CC 22 CHRG PUMP RM CLR 21 CCW RM COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 PAGE 20 OF 74

2FA-EP-100G (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO

-2Al 3YM-A*

2A VENT CC 2A7YD-A*

2A AIR COND. cc 2A7YF-A (21 CHILLED 2A AIR COND. cc WATER PUMP) 2Al 3X-A NONE 2B13YF-B 2B VENT cc 2Bl 3YC-B 2B7YD-B*

2B AIR COND. cc 2B13YA-B*

2B VENT CC 2B13YD-B*

2B13YE-B*

T.

SHUTDOWN COMPONENT AFFECTED 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 24BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERT PWR SUPPLY 23 CHRG. RM. COOLER 2 AFP ROOM COOLER 21 RHR RM. COOLER 21 CHILLED WATER PUMP 21 CHILLED WATER PUMP 21 CHILLER 22 CCW RM. COOLER 21 CHRG. RM. COOLER 22 CHILLED WATER PMP.

22 CCW RM. COOLER 21 CHRG. RM. CLR.

22 RHR RM. COOLER PAGE 21 OF 74 IMPACT ON AB SAFELY SHUT TO

2FA-EP-100G (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO 2Bl3YB-B*

2Bl3YJ-B*

2Bl3YM-B*

2Bl3YN-B*

2B VENT CC 2Cl 3YQ-C*

2Cl3YP-C*

2Cl3YK-C*

2Cl 3YJ-C*

2Cl3YG-C*

2Cl3YE-C*

2Cl3YB-C*

2Cl3YA-C*

2Cl3YF-C (21 CCW RM. COOLER) 2Cl3YC-C (22 CHRG.

RM. COOLER) 2Cl3YH-B (22 RHR RM. COOLER) 2Cl3YL-C*

2B VENT CC 2Cl3YN-C*

2Cl 3YM-C*

2Cl 4X-C NONE 2Cl 3X-C NONE SHUTDOWN COMPONENT AFFECTED 22 CCW RM. COOLER 21 CHRG. RM. CLR.

22 RHR RM. COOLER 22 CCW RM. COOLER 21 CHRG. RM. CLR.

22 RHR RM. COOLER

  1. 2 EMERG. CONTROL AIR COMPRESSOR
  1. 23 CHILLER PAGE 22 OF 74 IMPACT ON AB SAFELY SHUTD TO

FIRE AREA 2FA-DG-100D POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2ADD-A 2A4YA-A 2A4YB-A 2A4YC-A 2A4YJ-A 2A4YH-A 2A4YN-A 2A DIST. SYSTe 2A DIESEL GEN. CC 2A DIESEL GEN. &

2A DIST. SYST.

ASSUMING LOP 2A DIESEL GEN.

PAGE 23 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

2B & 2C DIESEL GEN POWER TRAINS AVAILABLE FOR SAFE SHUTDOWN

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2FA-DG-100Dl** 2A4Y-A 2A 2 30V SWGR

  • 2A VITAL VENT CC 21 RHR RM COOLER 2A 460V SWGR 23 CHRG PUMP RM CLR 2AFP RM COOLER 2A SW INTAKE CC 21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLED WTR PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 2ADSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al l 25VDC BATT CHRGR 2Al 28VDC BATT CHRGR 2A VITAL INST INVERTER PWR SUPPLY 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23_ CHRG PUMP PAGE 24 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

2B & 2C DIESEL GEN POWER TRAINS AVAILABLE FOR SAFE SHUTDOWN

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2FA-DG-100Dl** 2A4YG-A (CONT'D) 2B4Y-B (FIRE WRAPPED) 2C 4 Y-C (FIRE WRAPPED) 2CDC22 (FIRE WRAPPED) 2A DIESEL GEN. CC NONE NONE NONE 2A DIESEL GEN.

21 FUEL OIL TRANSFER PUMP NONE NONE NONE PAGE 25 OF 74 IMPACT ON ABI TY TO SAFELY SHUTDOWN

POWER CABLES SUBJ.

POWER SOURCE FIRE TO FIRE DAMAGE BY LACK OF CO SHUTDOWN COMPONENT AFFECTED 2FA-DG-100E**

  • 2BDD-B 2B DISTRIBUTION SYS 2B DIESEL GEN 2B4YA-B.

2B4YB-B 2B4YC-B 2B4YH-B 2B4YJ-B 2B4YN-B 2B DIESEL GEN CC 2B DIESEL 22 FUEL OIL XFR PMP PAGE 26 OF 74 IMPACT ON AB SAFELY SHUT NONE -

TO 2A & 2C DIESEL GEN

.POWER TRAINS AVAILABLE FOR SAFE SHUTDOWN

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2FA-DG-100El** 2B4Y-B 2B.DIESEL GEN 2B 230V SWGR 2B VITAL VENT CC 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22 CCW RM COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2B2 SW INTAKE CC 24 SW VENT FAN 25SW26 2B AIR COND CC 22 CHILLED WTR PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl l 25VDC BATT CHRGR PAGE 27 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

2A & 2C DIESEL GEN POWER TRAINS AVAILABLE FOR SAFE SHUTDOWN

FIRE AREA 2FA-DG-100El**

(CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF COO 2B4YG-B 2C4Y-C (FIRE WRAPPED) 2CDC22-CT (FIRE WRAPPED) 2B 460V SWGR 22 FUEL OIL XFR PMP NONE NONE SHUTDOWN COMPONENT AFFECTED 2Bl 28VDC BATT CHRGR 2B & 2D VITAL INST INVERTER PWR SUPPLY 28 VITAL INST BUS AUTO XFMR 22 CHILLER 22 CFCU 24 CFCU NONE NONE PAGE 28 OF 74 IMPACT ON AB Y TO SAFELY SHUTDOWN

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF COO 2FA-DG-100F**

2CDD-C 2C4YA-C 2C4YB-C 2C4YC-C 2C4YH-C 2C4YJ-C 2C4YN-C 2C DIST SYST 2C DIESEL GEN 2C DIESEL GEN SHUTDOWN COMPONENT AFFECTED 2C DIESEL GEN 2C DIESEL GEN PAGE 29 OF 74 IMPACT ON AB TO SAFELY SHUTD WN NONE -

2A & 2B DIESEL GEN POWER TRAINS AVAILABLE FOR SAFE SHUTDOWN.

POWER CABLES SUBJ.

POWER SOURCE FIRE TO FIRE DAMAGE BY LACK OF CO 2FA-DG-100Fl** 2C4Y-C 2C DIESEL GEN 2C 230V SWGR 2C 460V SWGR T.

SHUTDOWN COMPONENT AFFECTED IMPACT ON AB SAFELY SHUTD NONE -

2C VITAL VENT CC 2A & 2B DIESEL GEN TO 22 CHRG PUMP RM CLR POWER TRAINS AVAILABLE 21 CCW RM COOLER FOR SAFE SHUTDOWN.

2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 2 4BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERT PWR SUPPLY 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT SHUTDOWN SYS XF~R PAGE 30 OF 74

FIRE AREA 2FA-DG-100F 1 **

(CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2CDC22-CT NONE 480V PRESSRZR HTRS (ALT. SD ONLY)

NONE PAGE 31 OF 74 IMPACT ON AB

~ TO SAFELY SHUTDOWN

2FA-AB-122B POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO 2A3YBP-A*

2A WEST VALVES CC 2Al3YK-A*

2A VENT CC 2Al2X-A*

NONE 2BllX-B*

NONE 2Bl2X-B*

NONE 2B3YBS-B*

NONE 2B7YC-B 2B AIR COND. cc 2AVAC10-AT NONE 2AVAC15-AT NONE 2B7YD-B 2B AI Ro COND. cc 2B7Y-B 2B 230V SWGR SHUTDOWN COMPONENT AFFECTED 21CC16 2CC30 21CC3 21RH19

  1. 23 CHRG. RM.

COOLER

  1. 2 AFP RM. COOLER
  1. 21 RHR RM. COOLER NONE NONE NONE NONE
  1. 22 CHILLED WATER PUMP NONE NONE 22 CHILLED WATER PUMP 2B VITAL VENT CC 22 RHR RM. COOLER 21 CHRG. PUMP RM.

COOLER 22 CCW RM. COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2Bi SW INTAKE CC 24 SW VENT FAN PAGE 32 OF 74

~-------

IMPACT ON AB TO SAFELY SHUTDOWN NONE -

AFW WILL BE AVAILABLE VIA 21 & 22 AFP BY ALTERNATING THE PUMPS.

THE PUMPS ARE IN AN OPEN CORRIDOR WHICH IS SERVICED BY NORMAL AUX BUILDING VENTILATION.

POWER FOR 2B & 2D VIB WILL BE FROM 2B 125V BATTERY.

IF THIS IS DEPLETED, SUFFICIENT INSTRUMENTATION WILL BE AVAILABLE FROM 2A &

2C VIB TO MONITOR PLANT SHUTDOWN.

POWER WILL BE REQUIRED TO 2B 4KV BUS FROM EITHER 2B DIESEL ON THE GAS TURBINE PRIOR TO COLD SHUTDOWN TO SUPPORT RHR OPERATION.

FIRE AREA 2FA-AB-122B (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2B 460V SWGR 2SW26 2B AIR COND. CC 22 CHILLED WTR.

PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl 125VDC BATTERY*

CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 2D VITAL INST.

INVERTER POWER SUPPLY 2B VITAL INST. BUS AUTO XFMR 22 CHILLER 22 CFCU 24 CFCU PAGE 33 OF 74 IMPACT ON AB!

TO SAFELY SHUTDOWN

FIRE AREA 2FA.:...AB-122B (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2B7Y-F 2BVAC10.:...BT 2Cl SX-C 2C3YBP-C 2CVAC10-CT 2DCA16A-HT 2B AIR COND. CC NONE NONE 2C WEST VALVES CC 2C EAST VALVES CC NONE NONE 22 CHILLED WATER PUMP NONE NONE 2SJ1 2CV40 2CC31 22SW22 22CC3 23BF13 24BF13 NONE NONE PAGE 34 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 2FA-FH-100 POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2CVAC21-CT 2BVAC30-BT NONE NONE NONE NONE PAGE 35 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE

FIRE AREA lFA-TGA-88 POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2DCD24-DT 2DCD41-GT 2DCD7-GT 2DCD32-GT NOr.:IE NONE NONE NONE 23BF40 24BF19 NONE NONE NONE PAGE 36 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

UTILIZE BF19 & 40 VALVES

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT IMPACT ON AB TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED SAFELY SHUTDOWN 12FA-AB-84A 2DCD14-GT NONE NONE NONE PAGE 37 OF 74

FIRE AREA 2FA-AB-84A POWER CABLES SUBJ.

TO FIRE DAMAGE 2A4D-A 2A9X-A 2A7X-A 2A4X-A 2A2X-A 2A3YA-A 2A8Y-A 2Al3Y-A 2A3YB-A 2A4Da-A 2A7Y-A POWER SOURCE T.

BY LACK OF COORDIN.

2A 460V SWGR 2A 230V SWGR.

SHUTDOWN COMPONENT AFFECTED 21 CHILLER 21 BORIC ACID XFR.

PUMP 21 CFCU 23 CHRG PUMP 2A VITAL VENT CC 21 RHR RM. COOLER 23 CHRG PUMP RM.

COOLER 2AFP RM. COOLER 2A SW INTAKE CC 21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLED WTR PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN IMPACT ON AB Y TO SAFELY SHUTDOWN SHUTDOWN IMPACTED DUE TO MISROUTED ALTERNATE SHUTDOWN POWER FEED.

IF ONLY CONSIDERING BREAKER COORDINATION, 2C 125VDC BUS AND 2C BATTERY COULD BE RESTORED AND THE PLANT SUBSEQUENTLY PROCEED TO SHUTDOWN VIA THE ALTERNATE SHUTDOWN METHOD.

2Al 125VDC BATTERY SINGLE FAILURE FIRE CHARGER PAGE 38 OF 74

FIRE 2FA-AB-84A (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF COO 2A6X-A*

NONE 2Al lX-A NONE 2Al 4Y-A NORMALLY OPEN 2ADC5-AT 2Al BATT CHARGER 2ADC6-AT NORMALLY OPEN 2ADC25-AT NONE 2ADC26-AT NORMALLY OPEN 2ADC30-AT NONE 2ADC35-AT NONE 2Al3X-A 460V SWGR 2Al5X-A 2Al 6X-A 2A5X-A 2Al0X-A 2Al 4X-A 2Al2X-A SHUTDOWN COMPONENT AFFECTED 2Al 28VDC BATTERY CHARGER 2A VITAL INST.

INVERTER POWER SUPPLY NONE NONE BACK-UP TO 2B BATT.

CHARGER NONE NONE NONE 21 CHILLER PAGE 39 OF 74 1

IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 12FA-PT-84 POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED*

2CVAC15-CT*

2AVAC22-AT*

1A3D-A 1A8D-A 1A8Y-A 1AADC18-AT 1FW313-AT 1FW314-BT 1A3YBN-A*

1A3YBR-A*

1B3YBM-B*

1B3YBZA-B*

1B3YBZB-B*

2A3YBN-A*

2A3YBR-A*

2B3YBZA-B*

2B3YBZB-B*

2B3YBM-B*

2B8Y-B 2Bl5Y-B NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE 2B 230V SWGR NONE NONE 15SWP 16SWP lSWVlO LA-1688, LA-5744IB LA-2670, LA-2705IB NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE 2B VITAL VENT CC 22 RHR RM. COOLER 21 CHRG PUMP RM.

COOLER 22 CCW RM. COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2B2 SW INTAKE CC 24 SW VENT FAN 25SW26 2B AIR COND CC 22 CHILLED WATER PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 PAGE 40 OF 74 IMPACT ON AB SAFELY SHUTD NONE -

TO A FIRE IN THIS AREA HAS AN IMPACT ON SERVICE WATER AND POWER DISTRI-BUTION.

POWER IS RESTORED VIA THE GAS TURBINE.

AUX FEEDWATER AVAILABLE FROM AFWST (8 HR CAPACITY) AND ALTERNATE AFW SUCTION FROM 2/500,000) GAL DM TANKS.

STEAM FROM ATMOSPHERIC STEAM RELIEFS. CHG PUMPS CAN BE COOLED BY DM WATER VIA HOSE HOOKUP.

CHG MAKEUP FROM RWST. CHG DISCHARGE VIA ANY FLOW-PATHS IN SYSTEM.

CCW CAN BE CROSSED CONNECTED WITH HOSES.

SW CAN ALSO BE CROSSED CONNECTED WITH HOSES ALLOWING RESTORATION OF SW LOADS SUCH AS THE DIESEL GENS.

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 12FA-PT-84 (CONT'D) 2A3D-A 2A8D-A 2A8Y-A 2B 460V SWGR

.2A DIESEL GENERATOR 2A 230V SWGR 2B WEST VALVES CC 2 2CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl 125VDC BATTERY CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 2D VITAL INST.

INVERTER POWER SUPPLY 2B VITAL INST. BUS AUTO XFMR 22 CHILLER 22 CFCU 24 CFCU 2A VITAL VENT CC 21 RHR RM. COOLER 23 CHRG PUMP RM.

COOLER 2AFP RM. COOLER 2A_ SW INTAKE CC 21SW20 PAGE 41 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 12FA-PT-84 (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2AADC18-AT 2A 460V SWGR NONE 21 SW VENT FAN 2A AIR COND CC 21 CHILLED WTR.

PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATTERY CHARGER 2Al 28VDC BATTERY CHARGER 2A VITAL INST.

INVERTER POWER SUPPLY 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23 CHRG PUMP 2SWV1 2SWV2 2SWV5 2SWV7 PAGE 42 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

FIRE 12FA-PT-84 (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO 2B8D-B 2B DIESEL GEN.

2C3D-C 2C DIESEL GEN.

2C8Y-C 2C 230V SWGR 2C 460V SWGR T.

SHUTDOWN COMPONENT AFFECTED 2SWV8 2C VITAL VENT CC 22 CHRG PUMP RM.

COOLER 21 CCW RM. COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 24BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST.

INVERT. POWER SUPPLY 23 CHILLER 22 BORIC ACID XFR PUMP PAGE 43 OF 74 IMPACT ON AB SAFELY SHUT TO

FIRE 12FA-PT-84 (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO 2FW313-AT NONE SHUTDOWN COMPONENT AFFECTED 23 CFCU 25 CFCU 2 EMER CONT. AIR COMPRESSOR ALT. SHUTDOWN SYS XFMR 480V PRESSRZR. HTRS (ALT *. SD ONLY)

LA-1688, LA-5744IB PAGE 44* OF 7 4 IMPACT ON AB SAFELY SHUT TO

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT IMPACT ON AB TO TO FIRE DAMAGE BY LACK OF CO AFFECTED SAFELY SHUT 12FA-SW-90B 2AVAC22-AT*

NONE NONE NONE -

1B8YA-B*

NONE NONE UNIT #2 ONLY ONE SW 1C8YA-C*

lCSW cc 11SW20 PUMP AVAILABLE DUE TO 1C8YG-C*

llSW VENT FAN DIESEL GEN. LIMITATION.

1C8YH-C*

TURBINE BLDG MUST BE ISOLATED UTILIZING 2A8YA-A*

lA SW cc 21SW20 2SW26.

BY RESTORING 2C 2A8YG-A*

21SW VENT FAN 4KV BUS AND BY RESETTING 2A8YH-A*

2C SEC, 26 SWP COULD BE 2A8YHA-A STARTED TO PROVIDE ADEQUATE SERVICE WATER 2B8YA-B*

NONE NONE FLOW FOR SAFE SHUTDOWN.

1B3D-B NONE 13 SWP 1C8Y-C NONE lC SW CC UNIT #1 TURBINE BLDG 1B3D-B NONE 13 SWP MUST BE ISOLATED BY lBBYE-B*

NONE NONE MANUAL OPERATION OF lSTl 1B8YEA-B*

NONE NONE OR 1SW26.

TWO SW PUMPS 1B8YQ-B NONE 1SW26 AVAILABLE ON lA & lB 1B8YR-B NONE 12SW VENT FAN DIESEL GEN PROVIDE ADEQUATE SERVICE WATER 1C8YE-C*

lC SW cc 11SW20 FLOW FOR SAFE SHUTDOWN.

1C8YEA-C*

llSW VENT FAN 1C8YF-C 1C8YJ-C 1C8YJA-C 1C8YK-C*

1C8YR-C*

1C8YS-C 1CCDC8-CT NONE lSWVl 1SWV2 lSWVS 1SWV7 1SWV8 2B8YE-B NONE NONE 2B8YEA-B NONE NONE 2B8YR-B NONE 22 SW VENT FAN 2B8Y-B NONE 2Bl SW CC 22 SW VENT FAN PAGE 45 OF 74

FIRE 12FA-SW-90B (CONT'D)

POWER CABLES SUBJ.

TO FIRE DAMAGE 2A3D-A 2A8D-A

,2B3D-B 1C3D-C 2A8Y-A 1B8Y-B 2A8YS-A 2A8YE-A*

2A8YE-A*

2A8YJ-A*

2A8YJA-~*

2A8YK-A 2A8YR-A 1C8D-C POWER SOURCE BY LACK OF CO 2A DIESEL G.EN 2B DIESEL GEN NONE NONE NONE 2A SW CC NONE SHUTDOWN COMPONENT AFFECTED 21 SWP 22 SWP 23 SWP 24 SWP 11 SWP 2A SW CC 21 SW VENT FAN 21SW20

!Bl SW CC 12 SW VENT FAN 15SW26 21 SW VENT FAN 21SW20 12 SWP PAGE 46 OF 74 IMPACT ON AB SAFELY SHUT TO

FIRE AREA 12FA-SW-90A POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 1B15Y-B 2CVAC15-CT*

1A8YA-A*

1A8YG-A*

1A8YH-A*

1Bl5YA-B*

2Bl5YA-B*

2C8YA-C 2C8YG-C 2C8YH-C 1A3D-A 1A8D-A 1A8Y-A 1A8YE-A*

1A8YEA-A*

1A8YF-A 1A8YJ-A*

1A8YJA-A*

1A8YK-A*

1A8YR-A*

1A8YS-A 1AADC18-AT NONE NONE lA SW CC 1B2 SW CC NONE 2C SW CC NONE NONE NONE lA SW CC NONE 1B2 SW CC 14 SW VENT FAN NONE 13SW20 13 SW VENT 14SW VENT NONE 23SW20 23 SW VENT 15 SWP 16 SWP IA SW CC 13 SW VENT 13SW20 13 SW VENT lSWVlO 1SWV4 1SWV3 1SWV9 1SWV6 PAGE 47 OF 74 FAN FAN FAN FAN FAN IMPACT ON AB TO SAFELY SHUTDOWN NONE -

ONLY ONE UNIT #2 SW PUMP AVAILABLE DUE TO DIESEL GEN. LIMITATION.

TURBINE BLDG MUST BE ISOLATED UTILIZING MANUAL OPERATION OF 2ST1 OR 2SW26.

BY RESTORING 2A 4KV BUS AND RESETTING 2A SEC, 22 SWP COULD BE STARTED TO PROVIDE ADE~UA~E SERVICE WATER FLOW FOR SAFE SHUTDOWN.

FIRE AREA 12FA-SW-90A (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED lBlSYE-B*

lBlSYEA-B*

lBlSYR-B lBBD-B 2BBD-B 2B15YE-B 2Bl5YEA-B 2B15YQ-B 2Bl5YR-B 2C3D-C 2CBD-C 2C8YE-C*

.2CBYEA-C*

2C8YF-C*

2C8YJ-C*

2CBYJA-C*

2C8YK-C 2CBYR-C*

2CBYS-C 2CBYH-C 2C8YHA-C 2C8Y-C 2Bl5Y-B 1B2 SW CC NONE 2B DIESEL NONE NONE NONE NONE 2C DIESEL NONE 2C SW cc 2C SW CC NONE NONE GEN GEN 14 SW VENT FAN 14 SWP 2B DIST. SYST.

23 SWP 24 SWP NONE NONE 2SW26 24 SW VENT FAN 2C DIST. SYST.

25 SWP 26 SWP 23SW20 23 SW VENT FAN 2SWV9 2SWV4 2C SW CC 23 SW VENT FAN 23SW20 2B2 SW CC 24_ SW VENT FAN 2SW26 PAGE 48 OF 74 IMPACT ON AB SAFELY SHUTD TO

FIRE AREA 2FA-EP-78C POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2A2X-A 2A4X-A 2Al3Y-A 2A9X-A 2Al3X-A 2A3YAH-A*

2A3YAR-A*

2A7YF-A 2A7YD-A 2Al3YA-A 2Al3YB-A 2A13YE-A*

(WRAPPED/COORD.

>31' )

2A3YAB-A*

(WRAPPED/COORD.

)27 I) 2ADC9-HT 2B13X-B 2B2X-B 2B4X-B 2B8X-B 2Bl3Y-B NONE NONE NONE NONE NONE NONE 2B 460V SWGR 2B 230V SWGR NONE NONE NONE NONE 22 CHILLER 22 CFCU 22 CHILLER 22 CFCU 24 CFCU 2B VITAL VENT CC 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22 CCW RM COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2B2 SW INTAKE CC 24 SW VENT FAN PAGE 49 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

2A & 2C DIVISIONS OF POWER ARE AVAILABLE, BASED ON EXISTING FIRE WRAP AND 20 FT. SEPAR-ATION CRITERIA.

2FA-EP-78C (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF CO 2B6X-B 2B7YF-B 2B7YD-B 2Bl3YD-B NONE 2B AIR COND CC 2B VENT CC SHUTDOWN COMPONENT AFFECTED 2SW26 2B AIR COND CC 22 CHILLER WATER PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl 125VDC BATTERY CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 20 VITAL INST.

BUS AUTO XFMR 24 CFCU 22 CHILLER WATER PUMP 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22* CCW RM COOLER PAGE 50 OF 74 IMPACT ON AB SAFELY SHU TO

FIRE AREA 2FA-EP-78C (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2Bl3YE-B 2Bl3YM..,..B 2BDC9-ET 2C9X-C 2B9X-B 2Cl3X-C 2Cl4X-C 2Cl3YE-C*

2Cl3YL-C*

2Cl3YA-C 2Cl3YK-C 2Cl3YJ-C 2CVAC11-CT 2BVAC36-BT 2CVAC11-CT 2DVAC41-DT 2DVAC19-DT 2Al4X-A (NORMALLY DEENERGIZED) 2Cl3Y-C (CABLE WRAP) 2A3YAL-A

FIRE AREA FA-MP-7BI POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT IMPACT ON AB SAFELY SHUTD TO TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2AVAC25-AT*

2BVAC25-BT*

2BVAC23-BT*

2BVAC30-BT*

2BVAC28-BT*

2CVAC21-CT*

2CVAC20AA~CT*

2CVAC23-CT*

2CVAC25-CT*

2CVAC20A-CT*

2A5X-A*

2A3YAR-A*

2A3YAB-A*

2A3YAL-A*

2A3YAQ-A*

2A3YAH-A*

2B3YBZE-B*

2B3YBK.;..B*

2B3YAA-B*

2BSX-B 2B3YBE-B NONE NONE NONE NONE NONE NONE NONE 2A EAST VALVES CC NONE 2B WEST VALVES CC INST. PNL 827-2A NONE -

21 CFCU MUST FAIL AIR TO OPEN INLET & OUTLET VALVE FOR INST. PNL 827-2C

  • ONk CFCW.

FUN CFCU IN 24 CFCU LOW SPEED.

INST. PNL 827-2B 22 CFCU NONE 23 CFCU (PANEL 8 27-20)

PANEL 827-2E (25 CFCU)

NONE 2RHZ NONE 2SJ2 2SJ4 2SJ12 2CV41 MUST MANUALLY OPERATE 2RH1 & 2RH2 FOR COLD -

SHUTDOWN.

PAGE 52 OF 74

FIRE AREA 2FA-MP-78I (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2B3YBF-B NONE 2B3YBG-B NONE 2B3YBP-B NONE 2B3YBZC-B NONE 2B3YBZD-B NONE 2C3YAB-C NONE 2C3YAC-C NONE 2C3YAJ-C NONE 2C3YAS-C NONE 2C3YBX-C NONE 2C3YAA-C NONE 2C3YAF-C NONE 2C3YAG-C NONE 2C3YAK-C NONE 2C3YAL-C NONE 22CC16 22RH19 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2SJ4 2SJ12 NONE NONE NONE 2SJ5 2SJ13 NONE NONE 22SW22 NONE NONE NONE NONE NONE PAGE 53 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 2FA-AB-64A POWER CABLES SUBJ.

TO FIRE DAMAGE 2A5X-A 2A6X-A 2Al0X-A 2Al2X-A 2Al5X-A 2Al6X-A 2Bl0X-B 2Bl5X-B 2AllY-A 2B9Y-B 2B2Y-B 2A3YA-A 2A9Y-A POWER SOURCE CT.

SHUTDOWN COMPONENT IMPACT ON AB Y TO BY LACK OF COORDIN.

AFFECTED SAFELY SHUTDOWN NONE NONE NONE -

2A 230V SWGR 2A VITAL VENT CC 21 RHR RM COOLER 23 CHRG PUMP RM COOLER 2 AFP RM COOLER 2A SW INTAKE CC 21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLER WATER PUMP 2A EAST VALVES CC 2RH2 2PR6 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 21RH29 2A DSL GEN CC PAGE 54 OF 74 2A & 2C POWER DISTRI-BUTION ARE IMPACTED.

UTILIZE 2B DIESEL GEN AND GAS TURBINE.

WHEN GAS TURBINE IS AVAILABLE POWER 2A 4KV BUS TO RECOVER SECOND SW PUMP.

FIRE AREA 2FA-AB-64A (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2A3YBW-AT 2ABYE-A 2Bl3YJ-B 2AVAC22-AT 2AVAC17-AT 2AVAC35A-AT 2BDC26-BT 2BDC28-DT 2DCA30-HT 2DCA37-HT 2A 460V SWGR NONE 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATTERY CHARGER 2Al 28VDC BATTERY CHARGER 2A VITAL INST.

INVERTER PWR SUPPLY 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23 CHRG PUMP NONE PAGE 55 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 2FA-PP-92K POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2A3YAX-A 2B3YAU-B 2B3YAV-B 2B3YAZB-B 2C3YAX-C 2C3YAY-C NONE NONE PAGE 56 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NON.E

FIRE AREA 2FA-AB-100C POWER CABLES SUBJ.

TO FIRE DAMAGE 2AllX-A 2Al2X-A 2BllX-B 2Bl2X-B 2CllX-C 2Cl5X-C 2A7Y-A 2A4Y-A POWER SOURCE T.

BY LACK OF COORDIN.

NONE NONE NONE NONE NONE NONE 2A 230V SWGR SHUTDOWN COMPONENT AFFECTED 21 BA XFR PUMP NONE NONE NONE 22 BA XFR PUMP NONE 2A VITAL VENT CC 21 RHR RM COOLER 23 CHRG PUMP RM COOLER 2AFP RM.COOLER 2A SW INTAKE cc**

21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLED WTR PUMP 2A EAST VALVES CC 2RH2

  • 2PR6
  • 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 21RH29 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATTERY CHARGER PAGE 57 OF 74 IMPACT ON AB SAFELY SHUTD UTILIZE THE GAS TURBING TO RESTORE POWER TO THE VITAL BOSSES.

ONCE THE VITAL BOSSES ARE RE-ENERG I ZED THE MOTOR CONTROL CENTERS CAN BE RESET AND THE. AFFECTED SYSTEM RESTORED TO A NORMAL SHUTDOWN CONFIGU-RATION.

IF PRIMARY CONCERN IS THE VITAL VENTILATION AND ROOM COOLERS.

THE AFFECTED MOV'S ARE POSITIONED IN THE REQUIRED HSB POSITION PREVIOUSLY.

DECAY HEAT REMOVAL WILL BE AVAILABLE INITIALLY BY RUNNING 23 AFP AND STEAMING VIA THE MSlO's.

FIRE AREA 2FA-AB-100C (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2A 460V SWGR 2B7Y-B 2B4Y-B 2B 230V SWGR 2Al 28VDC BATTERY CHARGER 2A VITAL INST.

INVERTER POWER SUPPLY 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23 CHRG PUMP 2B VITAL VENT CC 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22 CCW RM COOLER 2Bl SW INTAKE CC 22 SW VENT FAN 2B2 SW INTAKE CC 24 SW VENT FAN 2SW26 2B AIR COND CC 22 CHILLED WTR PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 PAGE 58 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 2FA-AB-100C (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2C4Y-C 2B 460V SWGR 2C 230V SWGR 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B *DSL GEN 2Bl 125VDC BATTERY CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 2D VITAL INST INVERTER POWER SUPPLY 2B VITAL INST BUS AUTO XFMR 22 CHILLER 22 CFCU 24 CFCU 2C VITAL VENT CC 22 CHRG PUMP RM COOLER 21 CCW RM COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 24BF13 2C WEST VALVES CC PAGE 59 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 2FA-AB-100C (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2A7YF-A 2A7YD-A 2B7YF-B 2B7YC-B 2B7YD-B 2A3YBQ-A 2A3YBP-A 2C 460V SWGR 2A AIC COND. CC 2B AIR COND. CC 2A WEST VALVES 2A EAST VALVES 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERT POWER SUPPLY 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT. SHUTDOWN SYS XFMR 480V PRESSRZR HTRS (ALT. SD ONLY) 21 CHILLER WATER PUMP 22 CHILLER WATER PUMP 2CC30 21CC3 21CC16 21RH19 2RH2 2PR6 PAGE 60 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

~------------------------------------------------------

FIRE AREA 2FA-AB-100C (CONT'D) r,

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2C3YBP-C 2B3YBV-B 2B3YBS-B 2C3YBM-C 2C3YBK-C 2Al3YK-A 2Cl3YQ-C 2Cl3YP-C 2DVAC14-DT 2DVAC11-DT 2CVAC25-CT 2CVAC20A-CT 2CVAC23-CT 2CVAC10-CT 2VAC21-CT 2CVAC30-CT 2BVAC23-BT 2C WEST VALVES 2C EAST.VALVES NONE NONE NONE NONE 2A VENT CC 2C VENT CC NONE NONE NONE NONE NONE NONE NONE 2SJ1 22CC3 22CC31 2CV40 22SW22 2SJ5 2SJ13 23BF13 24BF13 2CV41 NONE NONE 2CV40 21 RHR RM COOLER 23 CHRG PUMP RM COOLER 2AFP RM COOLER 22 CHRG PUMP RM COOLER 21 CCW RM COOLER NONE NONE PNL 827-2E 25 CFCU NONE PNL 827-20 23 CFCU NONE 24CFCU PAGE 61 OF 74 IMPACT ON AB!

TO SAFELY SHUTDOWN

FIRE AREA 2FA-AB-100C (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORµIN.

AFFECTED 2BVAC23-BT 2BVAC30-BT 2BVAC28-BT 2BVAC10-BT 2AVAC39-AT 2AVAC36-AT 2AVAC25-AT 2AVAC15-AT 2AVAC16-AT 2AVAC10-AT 2CVAC30-CT 2DCA16A-HT 2DCA16-HT 2DCB38-ET 2DCB34-ET 2DCC38-FT 2CDC22-CT 2CDC27-GT 22CFCU NONE NONE NONE NONE 21CFCU NONE PAGE 62 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT IMPACT ON ABI TO FIRE AREA TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED SAFELY SHUTDOWN 2FA-AB-64B 2ASX-A NONE NONE NONE -

2Al0X-A UTILIZE RHR FLOWPATH B.

2Al2X-A MUST MANUALLY OPERATE 2C5X-C 2RHZ FOR COLD SHUTDOWN.

2ClOX-C NORMAL CHARGING FLOW-2Cl5X-C PATHS ARE AVAILABLE.

2C3YAS-C 23, 24BF13 VALVES NOT REQUIRED, UTILIZE BF19 2A3YBW-AT 2A WEST VALVES 2CC30

& 40 VALVES.

21CC3 21CC16 21RH19 2A EAST VALVES 2RHR2 2PR6 2C3YBN-C 2C WEST VALVES 2SJ1 22CC3 2CC31 2CV40 22SW22 2C3YBR-C 2C EAST VALVES 2SJ5 2C3YAA-C 2SJ13 2C3YBG-C 23BF13 2C3YBQ-C 24BF13 2AVAC17-AT NONE NONE 2AVAC22-AT

.2CVAC3 9A-CT 2CVAC26-CT PAGE 63 OF 74

POWER CABLES SUBJ.

FIRE AREA TO FIRE DAMAGE 2FA-AB-84C 2CDD-C 2C9D-C 2C8D-C 2C3D-C 2A3YBZ-A 2A3YBT-A 2AVAC14-AT 2AVAC11-DT POWER SOURCE CT.

BY LACK OF COORDIN.

2D DIESEL GEN NONE 2C DIESEL GEN NONE NONE NONE SHUTDOWN COMPONENT AFFECTED 22 CHRG. PUMP NONE 21CC3 NONE PAGE 64 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

2A & 2B DIESEL GEN'S AVAILBLE.

FIRE AREA 2FA-AB-84B POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2Bl4X-B 2Bl6X-B 2C10X-C 2C5X-C 2B3YBM-B 2B3YBW-B 2A3YBR-A 2B3YBZA-B 2B3YBZB-B 2B3YBD-B 2B3YBS-B 2A3YBN-A 2C3YBG-C 2C3YBQ-C NONE 2B WEST VALVE CC 2B EAST VALVES 2A WEST VALVES NONE 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2RH1 2PR7 21BF13 22BF13 2CC30 21CC3 21CC16 21RH19 2A EAST VALVES 2RH2 2C WEST VALVES 2C EAST VALVES 2PR6 2SJ1 22CC3 2CC31 2CV40 22SW22 2SJ5 2SJ13 23BF13 24BF13 PAGE 6-5 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

BOTH CCW PUMP RM COOLERS ARE IMPACTED.

ONE CCW PUMP CAN RUN ON AN ALTERNATING BASIS WITH THE PUMP ROOM DOOR OPEN.

THE AUX BLDG VENT SYSTEM WILL PROVIDE AIR FLOW THROUGH THE ROOMS.

WHEN 2C VITAL VENT CC IS RESTORED 21 CCW PUMP ROOM COOLER CAN BE RETURNED.

FIRE AREA 2FA-AB-84B (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2Cl3YB-C 2Cl3YG-C 2AVAC22-AT 2AVAC17-AT 2AVAC14-AT 2DVAC11-DT 2CVAC39A-CT 2BVAC14-BT 2C VENT CC NONE 22 CHRG PUMP RM COOLER 21 CCW RM COOLER NONE PAGE 66 OF 74 IMPACT ON AB Y TO SAFELY SHUTDOWN

FIRE AREA 2FA-TGA-88 POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2B3YAM-B 2B3YAN-B 2C3YAT-C 2C3YAU-C 2B3YAV-B 2DCA14-HT 2DCA29-HT 2ADC10-FT 2ADC12-AT 2ADC13-AT 2BDC10-ET 2BDC12-BT 2BDC13-BT 2BDC15-GT 2CCDC24-CT 2B EAST VALVES CC 2B WEST VALVES CC 2C EAST VALVES CC 2C WEST VALVES CC NONE NONE 2RH1 2PR7 21BF13 22BF13 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2SJ5 2SJ13 23BF13 24BF13 2SJ1 22CC3 2CC31 2CV40 22SW22 NONE 21BF19 22BF19 21BF40 22BF40 PAGE 67 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN NONE -

MANUALLY OPERATE 2RH1 FOR COLD SHUTDOWNe

FIRE AREA 2FA-TGA-88 (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2DCC9 2DCD24-DT 2DCD41-GT 2DCD7-GT 2DCD32-GT 2CVAC31-CT 2BVAC31-BT 2AVAC31-AT NONE NONE NONE NONE 23BF19 24BF19 23BF40 24BF40 NONE PAGE 68 OF 74 IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 2FA-RC-78 POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2A13YAP-A 2A13YBP-A 2A3YAEP-A 2A3YAMP-A 2A3YAPP-A 2A3YACP-A 2B13YAP-B 2Bl3YBP-B 2B3YAEP-B 2B3YAGP-B N/A N/A N/A N/A PAGE 69* OF 7 4 IMPACT ON AB SAFELY SHUTD TO SUBJECT TO SINGLE TRAIN EXPOSURE FIRE ONLY.

A COMBINATION OF RADIANT ENERGY SHIELDING, DISTANCE, LOCALIZED SUPPRESSION, DETECTION, AND REDUCED LOCALIZED AREA FIRE LOADING ACCOUNT FOR THE PROTECTION AFFORDED REDUNDANT CABLING IN THIS FIRE AREA.

FIRE DAMAGING TRAIN 2A SHUTDOWN CABLES DOES NOT ADVERSELY IMPACT SHUTDOWN UTILIZING TRAINS 2B AND 2C.

SUBJECT TO SINGLE TRAIN EXPOSURE FIRE ONLY.

A COMBINATION OF RADIANT ENERGY SHIELDING, DISTANCE, LOCALIZED SUPPRESSION, DETECTION, AND REDUCED LOCALIZED AREA FIRE LOADING ACCOUNT FOR THE PROTECTION AFFORDED REDUNDANT CABLING IN THIS FIRE AREA.

FIRE DAMAGING TRAIN 2B SHUTDOWN CABLES DOES NOT ADVERSELY IMPACT SHUTDOWN UTILIZING TRAINS 2A AND 2C.

FIRE AREA 2FA-RC-78 (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE TO FIRE DAMAGE BY LACK OF COO 2C13YAP-C 2C13YEP-C 2C13YAEP-C 2C13YAVP-C 2A2XP-A 2A4XP-A N/A NONE 2A 230V SWGR SHUTDOWN COMPONENT AFFECTED

  • N/A 21 CFCU 2A VITAL VENT CC 21 RHR RM COOLER 23 CHRG PUMP RM COOLER 2AFP RM COOLER 2A SW INTAKE CC 21SW20 21 SW VENT FAN 2A AIR COND CC 21 CHILLER WATER PUMP 2A EAST VALVES CC 2RH2 2P.R6 PAGE 70 OF 74 IMPACT ON AB TO SAFELY SHUTD WN SUBJECT TO SINGLE TRAIN EXPOSURE FIRE ONLY.

A COMBINATION OF RADIANT ENERGY SHIELDING, DISTANCE, LOCALIZED, SUPPRESSION, DETECTION, AND REDUCED LOCALIZED AREA FIRE LOADING ACCOUNT FOR THE PROTECTION AFFORDED REDUNDANT CABLING IN THIS FIRE AREA.

FIRE DAMAGING TRAIN 2C SHUT-DOWN CABLES DOES NOT ADVERSELY IMPACT SHUT-DOWN UTILIZING TRAINS 2A AND 2B.

  • NONE.

POTENTIAL EXISTS FOR LOSS OF POWER TO ALL THREE TRAINS BELOW 4KV WHICH WILL RESULT IN LOSS OF DIESEL GENERATORS.

TURBINE DRIVEN #23 AUX FEED PUMP WILL BE UTILIZED PRIMARY COOLING.

GAS TURBINE WILL BE UTILIZED TO RESTORE POWER. TO THE 4KV LEVEL.

THIS WILL RESTORE SERVICE WATER FUNCTION AND ALONG WITH RESETTING OF 4KV/230V FEEDER ALLOW OPERABILITY OF D.G.'S NORMAL SHUT-DOWN WOULD THEN PROGRESS AT WHICH TIME AT LEAST ONE CFCU WILL BE

FIRE AREA 2FA-RC-78 (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE CT.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2B2XP-B 2A4XP-A 2B4XP-B 2B8XP-B 2A 460V SWGR NONE NONE 2B 230V SWGR 2A WEST VALVES CC 2CC30 21CC3 21CC16 21RH19 21RH29 2A DSL GEN CC 21 FO XFR PUMP 2A DSL GEN 2Al 125VDC BATTERY CHARGER 2Al 28VDC BATTERY CHARGER 2A VITAL INST INVERTER POWER SUPPLY 21 CHILLER 21 BORIC ACID XFR PUMP 21 CFCU 23 CHRG PUMP 22 CFCU 24 CFCU 2B VITAL VENT CC 22 RHR RM COOLER 21 CHRG PUMP RM COOLER 22 CCW RM COOLER 2Bl SW INTAKE CC 22 SW VENT FAN PAGE 71 OF 74 IMPACT ON AB Y TO SAFELY SHUTDOWN AVAILABLE IN LOW SPEED TO SUPPORT NECESSARY CONTAINMENT COOLINGo NO OTHER SHUTDOWN SYSTEM IMPACT IS EXPERIENCED.

FIRE AREA 2FA-RC-78 (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2B2 SW INTAKE CC 24 SW VENT FAN 2SW26 2B AIR COND CC 22 CHILLER WATER PUMP 2B EAST VALVES CC 2RH1 2PR7 21BF13 22BF13 2B WEST VALVES CC 22CC16 22RH19 2SJ2 2SJ4 2SJ12 2CV41 2B DSL GEN CC 22 FO XFR PUMP 2B DSL GEN 2Bl 125VDC BATTERY CHARGER 2Bl 28VDC BATTERY CHARGER 2B & 2D VITAL INST INVERTER POWER SUPPLY 2B VITAL INST BUS AUTO XFMR PAGE 72 OF 74 IMPACT ON AB SAFELY SHUTD TO

(

POWER CABLES SUBJ.

POWER SOURCE T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2C2XP-C 2C6XP-C 2C4XP-C 2C8XP-C 2B 460V SWGR NONE NONE 2C 230V SWGR 22 CHILLER 22 CFCU 24 CFCU 23 CFCU 25 CFCU 2C VITAL VENT CC 22 CHRG PUMP RM COOLER 21 CCW RM COOLER 2C SW INTAKE CC 23 SW VENT FAN 23SW20 2C EAST VALVES CC 2SJ5 2SJ13 23BF13 24BF13 2C WEST VALVES CC 2SJ1 22CC3 2CC31 2CV40 22SW22 2C DSL GEN CC 2C DSL GEN 2C VITAL INST INVERT POWER SUPPLY PAGE 7.3 OF 74 r

IMPACT ON AB TO SAFELY SHUTDOWN

FIRE AREA 2FA-RC-78 (CONT'D)

POWER CABLES SUBJ.

POWER SOURCE.

T.

SHUTDOWN COMPONENT TO FIRE DAMAGE BY LACK OF COORDIN.

AFFECTED 2C 460V SWGR 23 CHILLER 22 BORIC ACID XFR PUMP 23 CFCU 25 CFCU 2 EMER CONT AIR COMPRESSOR ALT. SHUTDOWN SYS XFMR 4BOV PRESSRZR HTRS (ALT. SD ONLY)

PAGE 74 OF 74

.1'*

' 1 IMPACT ON AB TO SAFELY SHUTDOWN r'

-