l

  • ~

OCS IGN FEATURES DESIGN PRESSURE AND TEMPERATURE 5.2.2 The reactor containment building is designed and shall be maintained for a maximum internal pressure of 47 psig and an air temperature of 271°F.

5.3 REACTOR CORE FUEL ASSEMBLIES 5.3.1 The reactor core shall contain 193 fuel assemblies with each fuel assembly normally containing 264 fuel rods clad with Ziracloy-4 except that limited substitution of fuel rods by filler rods consisting of Ziracloy-4 or stainless steel or by vacancies may be made if justified by a cycle specific reload analysis.

Each fuel rod shall have a nominal active fuel length of 143.7 inches and contain a maximum total weight of 1766 grams uranium.

The initial core loading shall have a maximum enrichment of 3.35 weight percent U-235.

Reload fuel shall be similar in physical design to the core loading and shall have a maximum enrichment of 4.05 weight percent U-235.

CONTROL ROD ASSEMB LIES 5.3.2 The reactor core shall contain 53 full length and no part length control rod assemblies.

The full length control rod assemblies shall contain a nominal 142 inches of absorber material. The nominal values of absorber material shall be 80 percent silver, 15 percent indium and 5 percent cadmium.

All control rods shall be clad with stainless steel tubing.

5.4 REACTOR COO I.ANT SYSTEM DESIGN FEATURE AND TEMPERATURE 5.4.1 The reactor coolant system is designed and shall be maintained:

SA LEM - UN IT 1 5-4 Amendment No.