ML18092B212

From kanterella
Jump to navigation Jump to search
Forwards Safety Evaluation Supporting Util 860120 Response to 10CFR50.61,pressurized Thermal Shock (PTS) Rule.Projected Assessment of Resistor Temp for PTS Must Be Updated Whenever Changes Affect Projected Values
ML18092B212
Person / Time
Site: Salem 
Issue date: 07/09/1986
From: Fischer D
Office of Nuclear Reactor Regulation
To: Corbin McNeil
Public Service Enterprise Group
Shared Package
ML18092B213 List:
References
REF-GTECI-A-49, REF-GTECI-RV, TASK-A-49, TASK-OR NUDOCS 8607180046
Download: ML18092B212 (2)


Text

July 9, 1986 Docket No. 50-272 Mr. C. A. McNeill, Jr.

Vice President - Nuclear Public Service Electric and Gas Company Post Office Box 236 Hancocks Bridge, New Jersey 08038

Dear Mr. McNeill:

DISTRIBUTION Docket File NRC PDR Local PDR PD#3 Rdg.

T. Novak OELD E.. Jordan B. Grimes J. Partlow N. Thompson D. Fischer C. Vogan ACRS (10)

Tech Branch

SUBJECT:

PROJECTED VALUES OF MATERIAL PROPERTIES FOR FRACTURE TOUGHNESS REQUIREMENTS FOR PROTECTION AGAINST PRESSURIZED THERMAL SHOCK EVENTS We have reviewed your letter dated January 20, 1986 which was submitted in response to the Pressurized Thermal Shock (PTS) Rule, 10 CFR 50.61, for Salem Nuclear Generating Station, Unit 1.

We have found the material properties of reactor vessel beltline materials, the projected fluence at the inner surface of the reactor vessel and the calculated RT T for the end of the current operating license and the 32 EFPY, the plant 8esign lifetime, to be acceptable.

The calculated RTPJS is below the screening criteria of 270°F at 32 EFPY and, therefore, meets tne requirements of the PTS Rule.

The PTS Rule requires that the projected assessment of the RT TS must be updated whenever changes in core loadings, surveillance measu~ements or other information (including changes in capacity factor) indicate a significant change in the projected values.

This ensures that the licensees will track the accumulated fluence for the limiting beltline materials throughout the life of the plant to verify that their assumptions remain valid.

In this regard we request that you submit a re-evaluated of the RT TS and comparison with of the predicted value in any future Pressure-Temperature submittals which are submitted as required by 10 CFR 50, Appendix G.

Our associated Safety Evaluation is enclosed.

Enclosure:

As stated Sinc7}/

Donald C. Fischer, Senior Prject Manager PWR Project Directorate #3 Division of PWR Licensing-A cc:

See next page PD#3 c)

CVogan 11i- /86 PDut,)cf DFischer

~Cj /86 I

8607180046 860709 PDR ADOCK 05000272 P

PDR

Mr. C. A. McNeill Public Service Electric & Gas Company cc:

Mark J. Wetterhahn, Esquire Conner and Wetterhahn Suite 1050 1747 Pennsylvania Avenue, NW Washington, DC 20006 Richard Fryling, Jr.,.. Esquire Assistant General Solicitor Public Service Electric & Gas Company P. 0. Box 570 - Mail Code TSE Newark, New Jersey 07101 Gene Fisher, Bureau of Chief.

Bureau of Radiation Protection 380 Scotch Road Trenton, New Jersey 08628 Mr. John M. Zupko, Jr.

General Manager - Salem Operations Public Service Electric & Gas Company Post Office Box E Hancocks Bridge, New Jersey 08038 Robert Traae, Mayor Lower Alloways Creek Township Municipal Hall Hancocks Bridge, New Jersey 08038 Thomas Kenny, Resident Inspector Salem_Nuclear Generating Station U.S. Nuclear Regulatory Commission Drawer I Hancocks Bridge, New Jersey 08038 Richard F. Engel Deputy Attorney General Department of Law and Public Safety CN-112 State House Annex Trenton, New Jersey 08625 Frank Casolito, Action Chief Bureau of Radiation Protection Department of Environmental Protection 380 Scotch Road Trenton, New Jersey 08628 Salem Nuclear Generating Station Richard B. McGlynn, Commission Department of Public Utilities State of New Jersey 101 Commerce Street Newark, New Jersey 07102 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 Lower Alloways Creek Township c/o Mary 0. Henderson, Clerk Municipal Building, P.O. Box 157 Hancocks Bridge, New Jersey 08038 Mr. Bruce A. Preston, Manager Nuclear Licensing & Regulation Public Service Electric & Gas Company P. 0. Box 236 Hancocks Bridge, New Jersey 08038 Mr. David Wersan Assistant Consumer Advocate Office of Consumer Advocate 1425 Strawberry Square Harrisburg, Pennsylvania 17120