Text
!
1-'\\PPENDI X A NOTICE OF VIOLATION Pub 1 i c S.ervice ~l ectri c and Gas Company Salem Gen~~aJing Station, Units 1 and 2 License NQs*:***tiPR.,.70; DPR-75 Docket Nos. 50-272; 50-311
- As a resuit of* the inspection conducted on August 4 through September 14, 1981, and in accordance with the Interim Enforcement Policy, 45 FR 66754 (October 7, 1980),.
the following violations were identified:
A.
Technical Specffication 3.0.4 states, in part, 11Entry into an OPERATION/l.L MODE or other sp~cified condition shall not be made unles$ the* conditions of the Limiting Condition for Operation are met without reliance on provisions con-
- tained* in>the ACTION statements requir~merits."
~
Technical Specification.4.0.3 states, i:Failure to perform a Surveillance Requirement-within the specified time interval shall co~stitute failure to meet.the OPERABILITY requirements for a Limiting Condition for Operation."
Contrary" to the* above~ the fa 11 owing. react.or mode changes were macle wi tho tit
- ver*ification that* Limiting Conditions for Operation had been satisfied, with:-
out re 1 i ante on Action Statements requirements:
~...
On. June 21,* 1981, Unit 1 changed from Mode 4 to Mode 3 with No. ll RHR Pump i:nop.erable due to a shut *isolation valve.
Techni(.:al Specification 3.5.2 requires* two RHR,Pumps in Mode 3 as the Lirnitirig Condftion for Operation. *.Action Statement.3.5.2.a permits inoperability *of.one* RHR Pu111p for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
Both pumps were operable within 12. hours~ This
- event \\~as reported in Licensee Event Report 50-272/8l -62/03L. *
.* On June 2i -22,
- l 9Sl ; *Unit 2 changed from Mode 5 to Mode l without* com- * *
. pletion of the coritainrm~.rit. airl6ck 'surveillance testing required by.
Technical Specification 4*.6. l.3~b after establishing containment it)te-grity *..
Hhen this was discovered on July 1, 1981, an overall airlock test confirmed that the* airlock had been operable. This event was reported *1 n *Licensee E.vent Report 50-311 /8l *53/03L.
1 Sever&l *.ti.mes during the P?riod June* *2:..4~ 1981, Unit.2 changed from Mode : :
3 to ~bde l while the~surveillance test~bf Techriical. Specification 4.3~3.7 relative to C:tccident monitoring instrumentation c;hannels wa$ overdue.
When* this situation was discovered on June 6, 1981
- performance of the survei.llance test confirmed that the instrumentation had been operable.
This event was reported in Licensee Event Report 50-31l/81-3Q/03L. *
- r This is a Severity Level IV Violation (Supplement I) applicabl.i; to Docket Nos. 50-272 and 50~311.
Y.
e11105
~FFICIAL RECORD COPY.
Appendix A 2
B.
Facility Operating License DPR-75 states~ in Section 2.C.(lO)(d),
11By July 31, 1981, PSE&G shall *.* (9) liJrap one of the redundant power cables from the diesel generators located in the fuel oil storage tank room. ii Contrary to the above3 when inspected on September l, 1981, neither power feed to the diesel generators had been wrapped.
This is a Severity Level IV Violation {Supplement I) applicable to Docket No.
50-311.
C.
Technical Specification 4.1.3. l. l requires that the position of each full length rod shall be determined to be within the group demand limit by verifying the individual rod positions at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> except during ti1r~ intervals when the Rod Position Deviation Monitor is inoperable~ then verify the group positions at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. Technical Specification 4.0.2 extends the above interval by 25% to 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.
Contrary to the above, for the following listed 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> intervals, during which the Deviation Monitor was inoperable, no record could be identified to demon-strate that the required determination had been made:
Unit l Unit l Unit 2 Unit 2 September 10, 1981 Septewher 2, 1981 JJ.ugust 29 ~ 1981 September 1, 1981 0800 to 1600 1600 to 2400 1600 to 2400 0800 to 1600 This is a Severity Level VI Violation (Supplement I) applicable to Docket Nos.
50-272 and 50-311.
Pursuant to the provisions of 10 CFR 2.201~ Public Service Electric and Sas Company is hereby required to submit to this office within thirty days of the date of this Notice~ a written statement or explanation in replys including:
(1) the corrective steps which have been taken and the results achieved; (2) corrective steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved.
Under the authority of Section 182 of the Atomic Energy Act of 1954!> as amended, this response shall be submitted under oath or affirmation.
Where good cause is shown, consideration will be given to extending your response time~ The responses directed by this Notice are not subject to the clearance pro-cedures of the Office of Management and Budget as reqtflired by the Papen.oJork Reduc-tion Act of 1980 ~ Pl 96-511.
&;Ei~:W.al Sign§d BYij lWT '
198' IV_ //_
Dated
/t'. ~tc::__~~-_r.-~"-=--=--~~~_,,_~
~
R~ Keimig~ Chief Projects Branch #2~ Divisi~ of Resident and Project Inspection