05000311/LER-1980-023, Forwards LER 80-023/03L-0

From kanterella
(Redirected from ML18082B097)
Jump to navigation Jump to search
Forwards LER 80-023/03L-0
ML18082B097
Person / Time
Site: Salem 
Issue date: 08/28/1980
From: Librizzi F
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML18082B098 List:
References
NUDOCS 8009090542
Download: ML18082B097 (2)


LER-1980-023, Forwards LER 80-023/03L-0
Event date:
Report date:
3111980023R00 - NRC Website

text

Public Service Electric and Gas Company 80 Park Place Newark. N.J. 07101 Phone 201 '430-7000 Mr. Boyce H. Grier Director of USNRC August 28, 1980 Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-75 DOCKET NO. 50-311

'REPORTABLE OCCURRENCE 80-23/03L Pursuant to the requirements of Salem Generating Station Unit No. 2 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 80-23/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours,

.#~~

F. P. Librizzi General Manager -

Electric Production CC:

Director, Office of Inspection and Enforcement. (30 copies)

Director, Office of Management Information and Program coritrol (3 copies) 95*2001 1200M) 2*78

I

\\.""'"

Report Number:

Report Date:

Occurrence Date:

80--03L 8/28/80 7/31/80 Facility:

Salem Generating Station, Unit 2 Public Service Electric & Gas Company Hancock's Bridge, New Jersey 08038

. IDENTIFICATION OP. OCCURRENCE:

Refueling Water Storage Tank CRWST) Inoperable CONDITIONS :PRI"OR TO OCCURRENCE:

Mode 3 DESCRIPTION OF OCCURRENCE:

A chemical analysis of the RWST revealed the boron concentration to be at 1980 ppm.

This being below the 2000 ppm minimum, Action State-ment 3.l.2.8b and 3.5.5 were entered at 2300 hours0.0266 days <br />0.639 hours <br />0.0038 weeks <br />8.7515e-4 months <br />.

This required the RWST boron concentration to be restored within one hour or be in at least Hot Standby within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in Cold Shutdown within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Personnel Error ANALYSIS OF OCCURRENCE:

At the time of this occurrence, the RWST was being recirculated through a temporary demineralizer to reduce the sodium levels in the tank.

A sample analysis revealed the boron concentration below Technical Specification minimum.

Boron was added to increase the concentration in the tank.

The RWST was re.sampled and the boron concentration increased to 2160 ppm.

It is believed that the analysis of 1980 ppm was incorrect because the amount of boron added would not have increased the concentration by that amount.

CORRECTIVE ACTION

The boron concentration was increased and the Action Statement was terminat;ed at* 0.445 hours0.00515 days <br />0.124 hours <br />7.357804e-4 weeks <br />1.693225e-4 months <br /> on, August 1,, l.980f the procedure for boron analysis was reviewed with the chemical technician.

The sampling frequency was increased while circulating the RWST through this demineralizer.

FAILURE DATA:

Not Applicable Manager -

Salem Generating Station Prepared By

  • R. J. Newman SORC Meeting No.

66-80