05000311/LER-1980-002, Forwards LER 80-002/03L-0

From kanterella
(Redirected from ML18082A648)
Jump to navigation Jump to search
Forwards LER 80-002/03L-0
ML18082A648
Person / Time
Site: Salem 
Issue date: 06/25/1980
From: Librizzi F
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML18082A649 List:
References
NUDOCS 8006300479
Download: ML18082A648 (3)


LER-1980-002, Forwards LER 80-002/03L-0
Event date:
Report date:
3111980002R00 - NRC Website

text

OPS~G Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 Phone 201/430-7000 Mr. Boyce H. Grier Director of USNRC Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-75 DOCKET NO. 50-311 REPORTABLE OCCURRENCE 80-02/03L June 25, 1980 Pursuant to the requirements of Salem Generating Station Unit No. 2 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 80-02/03L.

This report is required within thirty (30) days of the.occurrence.

Sincerely yours, F. P. Librizz General Manager -

Electric Production CC:

Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control (3 copies) 8006300 I/ 7?

95*2001 (200MI 2-78

.. -* *. -***.L Report Number:

80-02/03L Report Date:

6/25/80 Occurrence Date:

5/26/80 Facility:

Salem Generating Station Unit 2 Public Service Electric & Gas Company Hancock's Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

2B Diesel Inoperable CONDITIONS PRIOR TO OCCURRENCE:

Mode 6 Initial Fuel Load DESCRIPTION OF OCCURRENCE:

While performing routine maintenance on 2A Emergency Diesel and performing surveillance on 2B Emergency Diesel, it was determined the 2B diesel would not increase its load to the required 2600 KW.

Action Statement 3.8.1.2 was entered at 1028 hours0.0119 days <br />0.286 hours <br />0.0017 weeks <br />3.91154e-4 months <br /> which requires with less than two diesel generators operable, suspend all operations involving core alterations or positive reactivity changes until the minimum required electrical power sources are restored to operable status.

The 2A diesel was restored to operable status and dem-onstrated operable at 1215 hours0.0141 days <br />0.338 hours <br />0.00201 weeks <br />4.623075e-4 months <br /> and the Action Statement was terminated.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Three pins for the individual fuel injectors were stuck preventing the loading of the diesel fully.

ANALYSIS OF OCCURRENCE:

When performing the routine surveillance, 2B diesel was only able to load to 2100 KW.

When the 2B diesel was declared inoperable, work on the 2A diesel was stopped.

2A diesel was returned to operable status allowing the Action Statement to be terminated.

CORRECTIVE ACTION

The problem was investigated and it was found three pins were stuck after first replacing the governor.

The pins were made operable.

In addition, the frequency, speed and EGA controls were checked to verify operability.

The 2B diesel was returned to operable status with the surveillance being performed on June 2, 1980.

An inspection order has been issued to ensure proper lubrication of the fuel rack on a monthly basis.

LER 80-02/03L FAILURE DATA:

Alco Diesel Engines Model 521 Prepared By M. J. Murphy SORC Meeting No.

42-80 2 -