consumers Power l'OWERINli MICHlliAN'S l'ROliRESS Palisades Nuclear Plant: 27780 Blue Star Memorial Highway, Covert, Ml 49043 February 2, 1996 US Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 LICENSEE REPORT OF MONTHLY OPERATING DATA DPR-20, DOCKET NO 50-255.
Enclosed is a copy of the Monthly Operating Data and Summary of Operating Experience for the Palisades Nuclear Plant for the month of January 1996..
If you have any questions or concerns,* please feel free to contact me at (616) 764-8913, extension 0113.
Sincerely, AL Williams Reactor Engineering Supervisor CC:
RA Vincent, Palisades Senior Resident Inspector, Palisades DRHahn, Div of Rad Health Services, Lansing, Ml BWJorgensen, Michigan Dept of Labor, Lansing, Ml JPadgett, Michigan Public Service Commission CWMain, Palisades SMMclntyre, P13-121 Region Ill Admin~strator, USNRC Document Control, 950*22*35*1 O/L Cycle 12 ReportJ r-----=96 7 0;;-:;2;;;-;090033 960131 -
PDR ADOCK 05000255 R
PDR, ;
OHOfl03
SUMMARY
OF OPERATING EXPERIENCE FOR JANUARY 1996 The unit began the month operating at 100% power. On January 16 at 0537 hours0.00622 days <br />0.149 hours <br />8.878968e-4 weeks <br />2.043285e-4 months <br />, the 2400 volt AC power automatically transferred from the normal power source (safeguards power) to the backup power source (startup power). At 2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br /> on January 16 a Notification of Unusual Event (NUE) was declared as a result of the shutdown required by Technical Specifications. The unit came offline at 0450 on January 17. Upon investigation a fault was discovered in the power supply cable to the 2400 volt "D" bus which runs in conduit under the Turbine Building between the Safeguards bus and buses *c* and "D".
At 2211 hours0.0256 days <br />0.614 hours <br />0.00366 weeks <br />8.412855e-4 months <br /> on January 30 the unit was brought back online.
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO 50-255.
UNIT Palisades DATE 02/02/96 COMPLETED BY KAKobiata MONTH JANUARY TELEPHONE (616)764-8913 AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe Net)
(MWe Net)
- 1.
781
- 17.
71
- 2.
784
- 18.
0
- 3.
783
- 19.
0
- 4.
781
- 20.
0
- 5.
782.
- 21.
0
- 6.
782
- 22.
0
- 7.
782
- 23.
0
- 8.
781
. 24.
0
- 9.
779
- 25.
0
- 10.
780
- 26.
0
- 11.
780
- 27.
0
- 12.
781
- 28.
0
. 13.
780 29.
0
- 14.
778
- 30.
- 7
- 15.
783
- 31.
407
- 16.
765 INSTRUCTIONS:
On this format, "list the average daily" unit power "level in MWe-NET for each day in the reporting month.
Compute to the nearest whole megawatt.
~'
DOCKH NO 50-255 UNIT Palisades DATE 02/02196 COMPLETED BY KAKoblata REPORT MONTH JANUARY 1996 TELEPHONE 616-764-8913 UNIT SHUTDOWNS AND POWER REDUCTIONS No. Date Type1 Duration Reason2 Method of Licensee System Component Cause & Corrective (Hours)
Shutting Event Code4 Down Reador Report #
1/17/96 F
329.4
.A Code' Action to Prevent Recurrence Fault in the power supply cable to the 2400 volt "D" bus which runs in Conduit under the Turbine Building Between the Safeguards bus and Buses *c* and "D", causing the 2400 volt AC power automatically to transfer from the nonnal power source (Safeguards power) to the backup power Source (startup power).
A.4.l.fl.AAAM4.W.AJ.>>>>A4.W.lJt.>AAAA.!J..W>J>J:A/i.M A.AMl.W.4.lAU..l.!J./1.A>AlJ>>>.l.JAU>>MlAA.AJAAJ.>>>>>AAPJl>>>AAJ..AJ.>>.W>Ml>A'>>>AA
- 1.
F: Forced S: Scheduled
- 2.
Reason A-Equipment Failure (Explain)
B-Maintenance or Test C-Refueling D-Regulatory Restriction E-Operator Training & License Examination F-Administrative G-Operational Error (Explain)
H-Other (Explain)
- 3.
~
- 5.
Method:
. Exhibit G
- Instructions Exhibit I - Same Source 1-Manual for Preparation of Data 2-Manual Scram Entry Sheets for Licensee 3-Automatic Scram Event Report (LER) File 4-0ther (Explain)
OPERATING STATUS:
- 1.
UNIT NAME
- 2.
REPORTING PERIOD:
- 3.
LICENSED THERMAL POWER (MWt)
- 4.
NAMEPLATE RATING (GROSS MWe)
- 5.
DESIGN ELECTRICAL RATING (NET MWe)
MAXIMUM DEPENDABLE CAPACITY (GROSS MWe)
MAXIMUM DEPENDABLE CAPACITY (NET MWe)
OPERATING DATA REPORT Palisades 960101-960131 2530 811. 7 805
- 770
- 730
- 6.
- 7.
- 8.
IF CHANGES OCCUR IN CAPCITY RATINGS (ITEM NUMBERS 3 THROUGH 7AND 7) SINCE LAST REPORT, GIVE REASONS:
- 9.
POWER LEVEL TO WHICH RESTRICTED, IF ANY (lllB'I' MWe):
- 10. REASONS FOR RESTRICTIONS, IF ANY:
- 11. HOURS IN REPORTING PERIOD
- 12. NUMBER OF HOURS REACTOR WAS CRITICAL
- 13. REACTOR RESERVE SHUTDOWN HOURS
- 14. HOURS GENERATOR ON-LINE
- 15. UNIT RESERVE SHUTDOWN HOURS
- 16. GROSS THERMAL ENERGY GENERATED (MWH)
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH)
- 18. NET ELECTRICAL ENERGY'GENERATED (MWH)
- 19. UNIT SERVICE FACTOR
- 20. UNIT AVAILABILITY FACTOR
- 21. UNIT CAPACITY FACTOR (USING MDC NET)
- 22. UNIT CAPACITY FACTOR (USING DER NET)
- 23. UNIT FORCED OUTAGE RATE.
This Month 744.0 423.3 414. 6 1010896.2 327214 311222 55.7\\'
55.7\\'
57.3\\'
52.0t 44.*3\\'*
- 24. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE AND DURATION. OF EACH):
- 25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
'26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION
- Based on condenser backpressure
- Weighted Average (635 MWe used as MDC Net prior to October 1985)
Yr-to-Date 744.0 423.3 414.6 1010896.2 327214 311222 55.7\\'
- 55. 7t 57.3\\'
52.0t 44.*3t Forecast DOCKET NO 50-255 DATE 02-02-96 COMPLETED BY KAKobiata TELEPHONE (616)764-8913 NOTES:
CWnulative 211431. 0 121374. 6 116569.3 255129586.7 80803468 76264641 55.H 55.H 53.2\\'*
44.8\\'
28.8\\'
Achieved