ML18058B888

From kanterella
Jump to navigation Jump to search
Responds to Unresolved Item Re Electrical Distribution Sys Functional Insp 50-255/91-19.C/As:licensee Will Replace Thermal Overload Heaters & Revise Procedure for Testing of Molded Case Circuit Breakers
ML18058B888
Person / Time
Site: Palisades 
Issue date: 06/21/1993
From: Slade G
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9306300117
Download: ML18058B888 (13)


Text

(

I consumers Power POW ERi Nii NllCHlliAN'S PROliRESS

. Palisades Nuclear Plant:

27780 Blue Star Memorial Highway, Covert, Ml 49043

_June 21, 1993 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 GB Slade General Manager DOCKET 50-255 - LICENSE DPR PALISADES PLANT - CHANGE IN COMMITMENT -

ELECTRICAL DISTRIBUTION SYSTEM FUNCTIONAL INSPECTION REPORT COMMITMENTS - NRC INSPECTION REPORT No. 91019 AND RESPONSES TO EDSFI CONCERNS The NRC conducted an Electrical Distribution System Functional Inspection (EDSFI) at the Palisades Plant from November 4, 1991 to December 13, 1991 and.

documented the results in Inspection Report (IR) No. 91019, dated January 31, 1992.

By letter dated March 2, 1992, Consumers Power Company

~CPCo) responded to the violations and deviations identified in IR 91019 and identified corrective action necessary to address the violations.

By letter dated March 31, 1992, CPCo responded to the open items contained in IR 91019 and identified corrective action necessary to address the open items.

On January 14, 1993, NRC Inspection Report No. 92027 identified an unresolved item concerning incorrect information provided to the NRC (unrelated to the EDSFI).

The cause of the unresolved item was an internal miscommunication of the NRC commitment and a miscommunication of a commitment due date requiring NRC notification.

As a result of the corrective actions taken to ensure the NRC is provided with the correct and up-to-date information, we have performed a review of the open NRC commitments that we maintain in our commitment-tracking system.

The review included commitments made to the NRC resulting from the EDSFI.

Our review revealed that changes to the completion dates of the proposed corrective actions for one of the EDSFI violations, and one of the EDSFI open items had been made internally within CPCo without notification

  • to the NRC prior to the expiration of the completion dates.

The changed completion dates and the reasons for the changes are discussed in the attachment to this letter.

In addition, a corrective action which effectively addressed one of the NRC concerns during the EDSFI, has changed slightly and is also discussed in the attachment.

In the attachment to this letter the NRC violation, open item, or concern from the EDSFI (IR 91019) is repeated, followed by the CPCo response and proposed corrective action from our previous correspondence.

The last section under

  • each of the issues is a description and reason for the change in commitment.

9306300117 930621 PDR.

ADOCK 05000255*

1 I.!

I A CMS ENER5Y COMPANY G

PDR

2 As previously stated, a review of all EOSFI issues has been completed.

This review was conducted as part of an EDSFI close out project.

In addition to having reviewed EDSFI commitments which were to come due on or prior to the date of this submittal, we are now reviewing our progress in closing out the remaining EDSFI commitments.

We have grouped the EDSFI commitments and have identified the interdependencies between individual issues to determine which issues must be resolved before resolution of others can commence.

We will reconfirm the resources required to resolve each of the open issues, and establish a schedule for each required resolution activity. The end result of this overall review of open EDSFI commitments is to develop an EDSFL closeout plan which identifies the completion date for closure of each open issue, and reflects our efforts to focus resources toward the resolution of the remaining issues.

Also as part of our review of EDSFI commitments, we have identified several commitments which will require rescheduling.

The new completion dates for these commitments will be included in our EDSFI closeout plan.

Since completion of the EDSFI inspection in November 1991, we have been working toward resolution of the open issues. Significant progress has been made as approximately 45 percent of all EDSFI commitments have now been closed.

Our progress also includes the development of a design to modify the emergency diesel generator control circuitry to add coincidence logic to non-essential diesel generator trips. This modification, anticipated to be installed in the 1994 refueling outage, results from an EDSFI commitment.

The design will undergo an independent third party technical review prior to installation.

Our recent and ongoing efforts to review the status against our EDSFI commitments and to develop a closure plan for the remaining EDSFI open issues has been to place additional emphasis on completing the remaining open issues.

Efforts will be placed on the most significant or prerequisite issues first, enhancing the overall progress toward closing the EDSFI issues.

Following the present 1993 refueling outage, we will be re-assessing the EDSFI resources and adjusting, as necessary, the closure of the EDSFI issues.

Once the re-assessment is complete, we will present the closure plan to the NRC.

Gra~

General Manager

  • CC Administrator, Region III, USNRC NRC Resident Inspector - Palisades

ATTACHMENT Consumers Power Company Palisades Plant Docket 50-255 CHANGED COMMITMENTS ELECTRICAL DISTRIBUTION SYSTEM FUNCTIONAL INSPECTION COMMITMENTS June 21, 1993 10 Pages

Violation No.I. IR 91019 10 CFR 50, Appendix 8, Criterion III, requires that applicable regulatory requirements and the design basis be correctly translated into drawings, procedures and instructions. Criterion III also requires that design changes be subject to design control measures commensurate with the original design.

Contrary to the above, from March 1986 until December 13, 1991, the licensee failed to translate a design change, which re-sized 17 thermal overloads associated with safety related motors, into field instructions for implementing the changes.

Reason for the Violation The reason for the discrepancies found between installed overload heaters and those specified in the setting sheets for motor control centers (MCCs) No. 1 and No. 2 was procedure inadequacy.

System Maintenance and Construction Services (SM&CS), a section of the Consumers Power Company corporate 1 aboratory, 1 aboratory procedure PD-11, "Test Procedure for Mo 1 ded Case Circuit Breakers," Revision 7-1985, used for testing of molded case circuit breakers, did not require SM&CS personnel to compare installed equipment with that specified in the setting sheet.

Breakers within MCCs No. 1 and No. 2 were tested by SM&CS personnel in 1986.

Breaker testing was performed in conjunction with the plant electrical maintenance department's preventive maintenance of the breaker buckets.

1 During the bucket preventive maintenance, the breaker was removed from the bucket by electrical maintenance and given to SM&CS for testing.

Upon completion of testing, the breaker was returned to the plant electrical maintenance department for reinstallation in the bucket.

In 1986, SM&CS personnel were not explicitly required by the SM&CS procedure (PD-11) to verify that the settings of protective devices listed on the setting sheet (e.g., starters, breakers, -0verload heaters, etc.) matched those installed in the bucket.

Based on information provided by SM&CS personnel who performed the breaker testing in 1986, the verification of protective devices listed on the setting sheets was considered an SM&CS responsibility.

However, this verification was apparently not performed in this instance.

Furthermore, System Protection Engineering did not provide the revised setting sheets to the plant.

In 1986, the method by which the plant would have been notified. of an equipment discrepancy was through a deficiency notice generated by SM&CS personnel during breaker testing.

No deficiency notices have been located for MCCs No. 1 and No. 2 from 1986 testing. Thus, plant personnel were not aware of the equipment discrepancies. Absence of the deficiency notices also supports the belief that a comparison between installed and required equipment was not performed.

Additional means now exist to prevent installed equipment from going unnoticed and unchanged from that specified in the setting sheet.

Upon issuance of setting or equipment changes by System Protection Engineering, the plant Systems Engineering Department receives an information copy of the revised

2 setting sheet which notes any changes.

This serves to notify the plant of changes in overload heater sizing and allows for these changes to be made via the work order process prior to SM&CS personnel coming onsite to test the device.

Corrective Actions Taken and Results Achieved

1. Provide walkdown verification of setting sheet specifications for MCCs located inside containment.

For Safety Related MCCs operability determinations will be made for discrepant information.

2. All MCCs located outside of containment have been walked down for component verification. These results will be utilized to implement actions to ensure plant equipment matches the setting sheet specifications.

For Safety Related MCCs operability determinations will be made for discrepant information.

Corrective Action to Avoid Future Non-Compliance The procedure for the testing of molded case circuit breakers, PD-11, "Test Procedure for Molded Case Circuit Breakers," was revised in 1989 to explicitly require SM&CS personnel to verify that installed protective devices (e.g.,

breakers, starters, overload heaters, etc.) match those specified by the setting sheet.

(This requirement exists in the 1991 revision of the procedure.)

The verification requirement should prevent equipment discrepancies from being overlooked during future breaker testing.

Date of Full Compliance Full compliance will be achieved with replacement of thermal overload heaters or when revision to setting sheets has been made.

This is currently scheduled for completion by June 1992.

  • Change in Commitment By letter dated January 14, 1993, the NRC issued Inspection Report 92027 which included an unresolved item relating to incomplete and inaccurate information being supplied to the NRC.

CPCo responded to the unresolved item in IR 92027 on February 16, 1993, pointing out that one of the causes of providing the incomplete and inaccurate information had to do with a discrepancy in the determination of due date versus target date on corrective action associated with commitments made to the NRC.

One of the corrective actions from our February 16, 1993, response was to "... review all open NRC commitments to assure all due dates are identified as such and not as target dates... "

Included in this review was corrective action associated with the EDSFI violations, open items, and concerns.

"Target dates" within the Palisades corrective action system do not require notification of the NRC prior to changing the completion dates; however, a "due date" requires NRC notification.

From the review of the NRC commitments, we determined that the corrective action associated with Violation 1 of the January 31, 1992 NRC letter (IR 91019) had been assigned a target date instead of a due date.

The corrective action related to Violation 1 had been assigned a completion (target) date of November 1992 (via the plant corrective action system) prior to the issuance of IR 91019.

Following the issuance of IR 91019, the corrective action document associated with Violation 1 retained the November 1992 completion (target) date; however, in our March 2, 1992 letter, CPCo committed to verifying the setting sheet data against the installed thermal overload heaters in all safety related MCCs by June 1992.

The June 1992 date was inconsistent with the previously assigned corrective action completion (target) date. A revised completion date and the reasons for the revised completion date are discussed in the following paragraphs.

3 Following completion of the EDSFI, we conducted a verification of the installed thermal overload.heaters in all motor control centers (MCCs) in the plant. Concurrent with the verification, our System Protection Engineering (SPE) staff was in the process of revising the criteria used in sizing thermal overload heaters. Therefore, a decision was made to delay replacement of any discrepant thermal overload heaters until SPE completed revising the sizing criteria and confirming that the thermal overload heaters were sized to the new criteria. During the verification, other discrepancies such as incorrect breaker settings and missing starter data, as well as the discrepancies between the setting sheet data and the installed thermal overload heaters, were identified.

Since the November 1992 corrective action completion date was considered to be a target date versus a due date, the completion date was extended to the 1993 refueling outage without notifying the NRC.

The completion date for the corrective action for Violation 1 was changed in recognition of the need for additional time to comply with the changes in the revised SPE sizing criteria and to resolve the additional discrepancies found between the setting sheet data and the installed thermal overload heaters.

An operability determination had been performed as part of the original 1991 corrective action for this discrepancy, therefore, a*delay in the completion* of this corrective-action does not create any nuclear safety concern.

Some of the thermal overload heaters in question on MCCs 1 and 2 provide overcurrent indication only for the motor operators of safety related motor operated valves (MOVs) and do not interrupt the function of the motor operators of the safety related MOVs.

Verification of the nameplate data for four of eight MOVs located in containment was obtained in the recent forced outage.

Nameplate data on the four remaining MOVs was not obtained during the forced outage because of the inaccessibility of the nameplates or because the nameplate was missing.

Nameplate data on hand at this time has been forwarded to SPE for evaluation. Currently, due to other priorities, engineering resources required to complete the engineering packages to change the thermal overload heaters are not scheduled during the 1993 refueling outage.

Therefore, the changeout of the thermal overload heaters has been deferred to a subsequent outage, possibly as late as the 1994 refueling outage.

Open Item 91019-10 3.1.13 Diesel Generator Trip Logic The team noted that the EOG control scheme employs the following automatic trip mechanisms that do not require two or more independent measurements of the trip parameter:

4

  • Generator trip on underspeed {<600 RPM) through the Field Shutdown Timer.
  • Engine and generator trip on engine underspeed (<120 RPM).
  • Engine and generator trip on jacket water low pressure, start circuit 8 only.

Since these trips do not employ coincident logic, they increase the potential for spurious EOG trips, which could cause loss of a division during an emergency.

In addition, the non-coincident jacket water low pressure signal provides an unintended DG trip mechanism and can result in the engagement of the air start motors while the engine is running.

This could cause equipment damage and deplete the starting air supply.

The licensee had previously identified these conditions and has committed to correct them by the fourth quarter.of 1992.

Pending further NRC preview of the licensee's corrective action, these issues remain open (255/91019-lO(ORS)).

CPCo Response During the development of Design Basis Document DB0-5.06, "Diesel Generator Controls," a Discrepancy Report No. (ORN) F-CG-91-106, entitled "Emergency Non-Coincident/Non-Bypassed Trips," was issued to identify and evaluate the diesel generator automatic shutdown logi~. As many as four process or system conditions can cause automatic diesel generator shutdown under circumstances which are unacceptable according to the NRC's technical criteria (i.e., Branch Technical Position No. ICSB-17; superseded by Regulatory Guide (RG) 1.9).

Because this aspect of the diesel generator control circuit design represented a potential conflict in the plant's licensing bases, a corrective action document, O-PAL-91-160, was initiated to evaluate the issue.

The corrective action which resulted from O-PAL-91-160 was to modify the diesel generator control circuits to meet RG 1.9.

Also, during the development of DB0-5.06, ORN F-CG-91-107 was issued to identify and provide a basis for the process or equipment conditions which can cause automatic shutdown (i.e., low jacket water pressure and engine underspeed [<120 rpm]).

These items were never intended as shutdown signals.

Rather, an apparent (original design) oversight, wherein the diesel generator

5 "engine started" signal was not designed to seal-in, makes the unit susceptible to automatic shutdown from these process signals. This occurs if the "engine started" permissive conditions fall below the sensing instrument settings at any time during operation, following a legitimate start.

Additionally, a related condition was identified where the lack of the seal-in feature can cause the re-engagement of the air start motor, with the engine running, for the duration of the overcrank trip timer setting.

As a result, the potential for air start motor damage or needless starting air depletion, or both, is introduced.

The occurrence of a diesel generator unit trip on "low jacket water pressure" or "engine underspeed" can occur due to non-coincident signals during emergency operation. These trip are not in conformance with the NRC's technical criteria. Modifications to the control circuit described in Deviation Report No. D-PAL-91-160 will resolve this issue.

Corrective Action A modification to correct these diesel generator control circuit deficiencies will be completed during the 1993 refueling outage.

Change in Commitment Facility Change (FC) 940, "Emergency Diesel Generator Breakers and Protective Trip Logic Upgrade," has been developed to implement the commitments made to the NRC regarding this open item.

Although significant progress has been made toward the completion of this modification, the facility change will not be completed during the 1993 refueling outage as previously identified.

FC 940 could not be completed in the 1993 refueling outage for a number of reasons.

Initially, as conceptual engineering developed for the modification, the scope of the project began to increase, thereby increasing the amount of detailed engineering required for the modification.

Secondly, engineering -

documentation for the replacement stored energy breakers was not available to support the 1993 refueling outage date, further delaying the development of the detailed design. Therefore, management decided to continue work on the.

modification package, but did not require the completion of the modification in the 1993 refueling outage as previously committed.

Our underlying concern was the impact of installing the modification on an accelerated schedule during the 1993 refueling outage and the resulting potential negative effect it might have on emergency diesel generator performance.

Detailed design for this modification is expected to be completed by July 1993, followed by an independent third party technical review.

Installation of the FC 940 modification is scheduled for completion in the 1994 refueling outage.

Open Item 91019-22 Inspection Report Paragraph 3.3.1.1 - Fuel Oil Supply System The team identified the following discrepancies in the design documentation associated with the EOG fuel oil storage tanks:

Fuel consumption tests were not documented.

6 The calculations regarding the capacities of the EOG day tanks and belly tanks were inconsistent.

The low level day tank alarm setpoint did not provide an accurate tank inventory.

The UFSAR, TS and various engineering analyses stated different EOG running time capabilities.

The team noted that the day tank emergency supply lines and their external valves OE-115 and 116, were not included in a maintenance and testing program to assure their availability at all times.

The supply lines provide compensation for the fact that storage tank T-10 and its appurtenances are not seismically or tornado qualified.

The team was also concerned that the TS required minimum 16,000 gallons of fuel in storage tank T-10 would not assure 7 days of dedicated EOG fuel supply.

The licensee currently maintains tank levels above the TS minimum to satisfy calculated 7 day fuel supply requirements.

The licensee's responses to the team's concerns committed to evaluate and provide necessary corrective action by the fourth quarter of 1992.

This item remains open pending NRC review of the licensee's corrective action (255/91019-22{0RS)).

CPCo Response During the inspection, the NRC noted a number of discrepancies in the calculations and docume~tation (i.e., FSAR and the technical specifications) associated with the diesel fuel oil storage analyses.

The issue regarding the current Technical Specification 3.7.li limit on diesel generator fuel oil supply was addressed by CPCo in 1989 as a result of the Configuration Control Project.

We determined that the technical specification limit of 16,000 gallons of diesel fuel oil in T-10 would not support 7 days of diesel generator operation. This is documented in LER 89-005, dated March 3, 1989.

Corrective action for that event included performing a calculation to determine the actual diesel fuel oil storage capacity.

As a result, a technical specifications change request was submitted on November 11, 1989 to increase the diesel fuel oil storage capacity requirement.

We are currently awaiting NRC approval of this technical specification change request.

In the interim, the more restrictive diesel fuel oil storage requirements are being administratively controlled via Standing Order 54, Section 3.7.li and will serve to insure an adequate supply of diesel fuel oil is maintained.

The remaining issues concerning diesel fuel oil storage analysis are currently being evaluated.

.e 7

The NRC also identified a weakness in the calculations for the diesel fuel oil storage capacity in. that fuel oil consumption rates utilized in the calculations had not been verified by testing.

CPCo had utilized the original diesel generator fuel consumption rate {obtained by test at the factory) in our calculations. Data obtained during the performance of technical specification surveillance test {TSSP) M0-7A, "Emergency Diesel Generators,"

indicated the existing fuel consumption rates were nearly equal the factory test data. A more formal test needs to be performed.

The NRC team also identified a weakness concerning the emergency fill lines to the diesel generator day tanks in that they are not included in the maintenance and testing programs.

CPCo will develop a maintenance and testing program commensurate with the significance and probability of the failure of the emergency fill lines.

Corrective Action The remaining issues concerning diesel fuel oil storage analysis are currently being evaluated and will be completed by the end of 1992.

Recommended corrective actions resulting from this evaluation will be documented and appropriate completion dates will be assigned.

The formal test to determine the diesel generator fuel oil consumption rate as well as the maintenance and testing program for the emergency fill lines to the diesel generator day tanks will be developed by the end of 1992.

December 22, 1992 Change in Commitment By letter dated December 22, 1992 we notified the NRC of a change in the completion dates of the commitments associated with this open item.

The changed commitments were identified as follows:

1.

The available on-site fuel oil inventories for diesel fuel oil storage tank T-10, day tanks T-25A/B, and diesel generator belly tanks have been verified but require formal technical review.

The evaluation-will be completed in the first quarter of 1993.

2.

The formal test to determine fuel oil consumption rate will be developed in the first quarter of 1993 and is scheduled to be performed in May 1993.

3.

The results of items 1 and 2 above will be coupled with a detailed diesel generator electric load evaluation to finalize the required fuel oil inventory for the analyzed event.

The final comparison between required.fuel oil inventory and the available fuel oil inventory will be completed by October 1993.

The electric load evaluation is presently in progress and is expected to be completed by August 1993 to support the final comparison.

4.

The present emergency fill method for the diesel generator day tanks is being re-evaluated to determine the best alternative. Once the best alternative is determined, a functional test will be conducted.

8 Completion of the functional test is expected by December I993.

It appears that a fjll connection or fill method inside the rooms that contain the diesel generator day tanks will be more dependable and will requtre less effort to maintain.

Change in Commitment Item I is partially complete in that the "usable" on-site diesel fuel oil inventory has been determined.

The "available" on-site diesel fuel oil inventory is dependent upon other fuel oil demands placed on storage tank T-IO.

  • A revised completion date for Item I will be included in the EDSFI closeout plan.

Item 2, fuel oil consumption rate testing for both emergency diesel generators, has been completed and the results are being compiled.

The results of this testing will be incorporated into the remaining emergency diesel generator fuel oil concerns.

Completion dates for the remaining emergency diesel fuel oil concerns will be included in the EDSFI closeout pl an.

The previously identified completion dates for item 3 and item 4 (August, October and December I993) are being re-evaluated.

The priority placed on these items relative to other scheduled work and emergent work is currently being evaluated and will be included in the EDSFI closeout plan.

NRC CONCERN #I7:

LACK OF ELECTRICAL ISOLATION BETWEEN CLASS IE AND NON-IE DESCRIPTION OF CONCERN The J200/5A CT's for Breakers J52-J05 and J06 for 2400 V Class JE Bus JC are connected-to Class JE overcurrent relays J5J and Non-Class JE ammeter and wattmeter located in the control room.

There is no electrical isolation between these two circuits (the same applies to Bus JD).

An earthquake (common mode failure) can cause open circuit in the protective system resulting in a failure of both Class JE protective systems.

Reqt:

Physical and Electrical Isolation shall be provided between Class JE and Non-Class JE Circuits Ref:

IEEE 308 FSAR Section 8.J.

RESPONSE TO CONCERN The design of the current transformer control scheme for the 2400 volt breakers I52-I05 and I52-I06 is as described in the concern description.

The condition. is attributed to the age of the Palisades design and the changes in the "state of the art" which have occurred since the Plant was designed and constructed.

Palisades was designed in the I960's prior to the develcopment of current design standards (eg. IEEE-308) and thus prior to today's definition of Class IE.

Subsequently, electrical equipment classification has been backfit to Palisades to designate equipment as Class IE or non-Class IE.

The use of the term Class IE at Palisades means that the system or component provides an essential function as provided in the IEEE-308 definition of Class IE.

The ammeter and wattmeter do not perform an essential function and thus are classified as non-Class IE.

Although the Plant was originally designed and qualified by analysis to provide safety related functions, original equipment may not meet all of the design and testing criteria of IEEE-308 and other standards incorporated by reference therein.

9 Design criteria for the independence of non-Class IE circuits from Class IE circuits were first provided in IEEE-384.

Again, these requirements post date the Palisades design.

The only commitments which Palisades has with regard to the requirements of IEEE-384 are associated with post TMI modifications made in NUREG-0737.

However, Palisades does attempt to meet the intent of IEEE 308 and IEEE 384 requirements for all recent modifications.

The issue identified by this concern relates to the lack of isolation between the Class IE current transformers on the safety related buses and non-Class IE ammeter and wattmeters located in the control room.

While we agree that isolation meeting the requirements of IEEE-384 is not provided, we do not consider this lack of isolation to be a* significant concern.

To fail both safety related buses, the two current transformer ~ircuits would have to open simultaneously.

We consi~er that opening both of these circuits simultaneously could only occur as a result of a common mode failure during a seismic event.

The issue of seismic qualification of mechanical and electrical equipment for plants of Palisades vintage is being addressed generically as Unresolved Safety Issue {USI-A-46).

To resolve this issue, Palisades intends to use the methodology provided by the Seismic Qualification Utility Group {SQUG) in their Generic Implementation Procedure. This procedure has been reviewed by the NRC and has been found to-be a generally acceptable method for resolving the seismic issue.

Evaluations performed by the Seismic Qualification Utility Group (SQUG) has indicated, that instrumentation of the type represented by the ammeter and wattmeter do not fail during seismic events if the equipment is adequately mounted to a control cabinet which is anchored firmly to the floor. This conclusion was reached by SQUG following their review of the actual damage caused by I9 earthquakes of various magnitudes.

The data base used in this evaluation contained over IOO facilities. A copy of Chapter 20 of EPRI NP-7I49-D, "Summary of the Seismic Adequacy of Twenty Classes of Equipment Required for Safe Shutdown of Nuclear Plants," is included as Attachment I. This chapter provides a summary of the seismic adequacy of instrumentation panels and cabinets and the installed instrumentation.

Page 20-7 of this chapter discusses the earthquake experience at the Pleasant Valley Pumping Plant. This plant contained a large number of ammeters and wattmeters, none of which were significantly damaged during an earthquake with a recorded average peak ground acceleration of 0.56g.

Although we do not consider current transformer isolation to be a significant concern, it has become apparent to us that isolation requirements for

IO Palisades need to be better defined.

To this end, the Configuration Control Project has developed a work activity to define the design basis for isolation. A copy of the position paper describing the scope of this activity is included as Attachment II.

CONCLUSIONS Palisades was designed and constructed prior to the issuance of present day IEEE standards related to isolation of Class IE and non-Class IE circuits.

Although we have subsequently designated portions of the current transformer circuits as non-Class IE, we do not believe that there is a credible event which would operi both of these circuits simultaneously resulting in a loss of both safety buses. This conclusion is based on work performed by SQUG to evaluate equipment damage resulting from actual earthquakes.

Palisades does, however, plan to develop a Design Basis Document related to isolation techniques as part of the Configuration Control Project.

Change in Commitment By letter dated March 30, I993, CPCo provided the NRC with an update of the status of the Configuration Control Project (CCP).

The Attachment to our March 30, I993 letter identified completed design basis documents (DBDs), DBDs currently under development, and DBDs to be developed.

In the category of completed DBDs, we identified a completed report entitled "Electrical I&C Isolation," which effectively addresses the NRC concern described above.

This report has been changed to an engineering aid, EGAD-ELEC-I6, "Electrical Control Panel Isolation Criteria, Practices, and Exceptions."

As such, a design basis document (DBD), as described in our March 30, I993 letter and as committed to during the EDSFI, will not be developed.