ML18058B075

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Aug 1992 for PNPP
ML18058B075
Person / Time
Site: Palisades Entergy icon.png
Issue date: 08/31/1992
From: Handlovits S, Mlynarek M
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9209150323
Download: ML18058B075 (5)


Text

  • ,

consumers Power l'OWERINli NllCHlliAN'S l'RDliRESS Palisades Nuclear Plant: 27780 Blue Star Memorial Highway, Covert, Ml 49043

.September 4~ 1992 US Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 LICENSEE REPORT OF MONTHLY OPERATING DATA DPR-20, DOCKET NO 50-255 Enclosed is a copy of the Monthly Operating Data and Summary of Op_erating Experience for-the Palisades Nuclear Plant for the month of August, 1992.

l.f you have any questions or concerns, please. feel free to contact me at (616) 764-8913, e~tension 0113~*

Sincerely, 111 (;,.,,,,~

MG Mlynarek

  • Reactor Engineer CC:

DPHoffman, P26-ll 7B ABDavis, USNRC JLKu~min, Palisades Resid~nt Inspector, Paiisades DRHahn, Div of Rad Health Se~vices, Lansing, MI BWJorgensen, Michigan Dept of Labor, Lansing, MI JPadgett, Michigan Public Service Commission Records Center, INPO, Atlanta, GA RWTaylor, CE, Palisades AAAlatalo, Palisades.

SMMclntyre, Pl3-121 Administrator, USNRC Documerit Control, 950*22*35*10/L SMH92*24

~~~~~~~-~-)-~20831 :

l PDR.

ADOCK 0500025-5 g

Pn~

, Li.

ACM5ENERGYCOMPANY

OPERATING STATUS:

1.

UNIT NAME

2.

REPORTING PERIOD:

OPERATING DATA REPORT Palisades 920801-920831

3.

LICENSED THERMAL POWER (MWt) 2530.0

4.

NAMEPLATE RATING (GROSS MWe) 811.7

5.

DESIGN ELECTRICAL RATING (NET MWe) 805.0

6.

MAXIMUM DEPENDABLE CAPACITY (GROSS MWe)

    • 770
7.

MAXIMUM DEPENDABLE CAPACITY (NET MWe)

    • 730
8.

IF CHANGES OCCUR IN CAPCITY RATINGS (ITEM NUMBERS 3 AND 7} SINCE LAST REPORT, GIVE REASONS:

9.

POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe):

10. REASONS FOR RESTRICTIONS, IF ANY:
11. HOURS IN REPORTING PERIOD
12. NUMBER OF HOURS REACTOR WAS CRITICAL
13. REACTOR RESERVE SHUTDOWN HOURS
14. HOURS GENERATOR ON-LINE
15. UNIT RESERVE SHUTDOWN HOURS
16. GROSS THERMAL ENERGY GENERATED (MWH)
17. GROSS ELECTRICAL ENERGY GENERATED (MWH)
18. NET ELECTRICAL ENERGY GENERATED (MWH)
19. UNIT SERVICE FACTOR
20. UNIT AVAILABILITY FACTOR
21. UNIT CAPACITY FACTOR (USING MDC NET)
22. UNIT CAPACITY FACTOR (USING DER NET)
23. UNIT FORCED OUTAGE RATE This Month Yr-to-Date 744.0 5855.0 638.3 3973.3 597.5 3807.6 1459272.0 9394944.0 471820.0 3082498.0 446967.0

. 2929038.0 B0.3%

65.0%

80.3%

65.0%

82.3%

68.5%

74.6%

62.1%

19.7%

8.1%

24. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE AND DURATION OF EACH):
25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):

Forecast INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

    • Based on condenser backpressure
  • Weighted Average (635 MWe used as MDC Net prior to October 1985)

DOCKET NO DATE 50-255 8-31-92 COMPLETED BY SMHandlovits TELEPHONE (616)764-8913 NOTES:

Cumulative 181478.0 10i019.9 96719.1 206049557.0 64861223.0 61101046.0 53.3%

53.3%

50.5%*

41.8%

30.7%

Achieved

._/

AVERAGE DAILY UNIT POWER LEVEL MONTH AUGUST 1992 DAY AVERAGE DAILY POWER LEVEL (MWe Net)

1.

778

2.

775

3.

777

4.

778

5.

782

6.

779

7.

775

8.

771

9.

767

10.

761

. 11.

776

12.

780

13.

782

14.

0

15.

0

16.

0 INSTRUCT IONS:

DAY

17.
18.
19.
20.
21.
22.
23.

24.,

25.
26.
27.
28.
29.
30.
31.
  • DOCKET NO 50-255 UNIT Palisades DATE 09/02/92 COMPLETED BY SMHandlovits TELEPHONE (616)764-8913 AVERAGE DAILY POWER LEVEL (MWe Net) 0 509 775 780 780 774 768 768 389 0

374 776 777 778 780 On this format, list the average daily unit power level in MWe-NET for each day in the reporting month.

Compute to the nearest whole megawatt.

REPORT MONTH ~A~U~G~US~T_l~9~9~2 -----

No.

Date Type 1 03 920814 F

04 920825 F

1.
2.

F:

Forced S:

Scheduled Duration Reason2 (Hours) 95.7 A

50.8 A

Reason:

A-Equipment Failure (Explain)

B-Maintenance or Test C-Refue ling D-Regulatory Restriction E-Operator Training & License Examination F-Administrative G-Operational Error (Explain)

H-Other (Explain)

UNIT SHUTDOWNS AND POWER REDUCTIONS Method of Licensee Shutting Event Down Reactor3 Report #

3 LER 92036 3

LER 92037

3.

Method:

!-Manual 2-Manual Scram 3-Automatic Scram 4-0ther (Explain)

4.

System Component Code4 Code5 Exhibit G - Instructions for Preparation of Data Entry Sheets for Licensee Event Report (LER) File (NUREG-0161)

Cause & Corrective Action to Prevent Recurrence DOCKET NO UNIT DATE COMPLETED BY TELEPHONE Failed air line to Feedwater Regulating Valve Failed solenoid in Y-20 Preferred AC Bus

5.

Exhibit I - Same Source 50-255 Palisades 9/02/92 SMHandlovits (616)764-8913

SUMMARY

OF OPERATING EXPERIENCE FOR AUGUST 1992 The unit began the month at full power but tripped on August 14 at 0017 hours1.967593e-4 days <br />0.00472 hours <br />2.810847e-5 weeks <br />6.4685e-6 months <br />.

The reactor went critical August 16 at 1330 hours0.0154 days <br />0.369 hours <br />0.0022 weeks <br />5.06065e-4 months <br /> and was on-line August 17 at 1749 hours0.0202 days <br />0.486 hours <br />0.00289 weeks <br />6.654945e-4 months <br /> but then came off-1 ine at 2017 hours0.0233 days <br />0.56 hours <br />0.00333 weeks <br />7.674685e-4 months <br /> and remained critical.

The unit was placed on-line again August 18 at 0230 hour0.00266 days <br />0.0639 hours <br />3.80291e-4 weeks <br />8.7515e-5 months <br />s~ Full power was reached August 19 at 0423 hours0.0049 days <br />0.118 hours <br />6.994048e-4 weeks <br />1.609515e-4 months <br /> and continued at 100% power until August 25 when the plant tripped at 0129 hours0.00149 days <br />0.0358 hours <br />2.132936e-4 weeks <br />4.90845e-5 months <br />. Criticality was achieved August 26 at 2200 hours0.0255 days <br />0.611 hours <br />0.00364 weeks <br />8.371e-4 months <br /> and went on-1 i ne August 27 at 0417 hours0.00483 days <br />0.116 hours <br />6.894841e-4 weeks <br />1.586685e-4 months <br />.

Full power was reached August 28 by 0800 hours0.00926 days <br />0.222 hours <br />0.00132 weeks <br />3.044e-4 months <br /> and continued until the end of the month.