Notice of Deviation from Insp on 890516-18 & 0509.Deviation Noted:Bus 1C in Switchgear Room 1-C Had Unsealed Opening in Top Cable Penetration
ML18054A832
Person / Time
Site: Palisades 
Issue date: 07/06/1989
From: Cooper R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML18054A831 List:
References
50-255-89-14, NUDOCS 8907120206
Download: ML18054A832 (1)


Text

NOTICE OF DEVIATION Consumers Power Company Docket No. 50-255 Ba seq on the resul.ts of the NRC inspection conducted on May 16-18 and June 9, 1989, certain of your activities appear t6 deviate from your written response to NRC Branch Technical Position APSCB 9.5-1, Appendix A, as indicated below:

Section_D.3(c) of the Appendix A re~ponse, dated March 31, 1977, itates that "The safety-related equipment in the vicinity of automatic sprinklers have all had the top cable entry points in the cabinets sealed to prevent water ingress.

11 Sect1on E.3(a) of the Appendix A response, dated March 31, 1977~ states that "The top cable entry openings of the cabinets of safety related equipment have been sealed closed to prevent water ingress. 11 Section F.5 of the Appendix A response, dated March 31, 1977, states that*

"All switchgear top cable penetrations are sealed with Flammastic.

11 Contrary to the above, during a plant to~r on May 17, 1989, the NRC identified that Bus lC in Switchgear Room 1-C had an unsealed opening in a top cable penetration.

Please provide in writing* within 30 days of th~ date of this Notice:

(1) th~

reasow for the deviation; (2) the corrective actions that have been t~ken and the r:esults achieved_; (3) the corrective actions that will be taken to avoid further deviations; and (4) the date when your corrective actions will be completed.

Consideration may be given to extending the response time for good cause shown.

  • Dated R907120206 890706

~F'[.IR.

ADOCK 05000255 F'DC Q

R. W. Cooper, Chief _

Engineering Branch