  • General Offices: 1945 West Parnall Road, Jackson, Ml 49201 * (517) 788-0550 June 27, 1989 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -

EMERGENCY RESPONSE DATA SYSTEM (ERDS) SURVEY RESPONSE (TAC No. 73444)

By letter dated April 5, 1989, the NRC forwarded a survey requesting Consumers Power Company to provide the hardware, communications, data point and administr-ative information necessary for the NRC to design the Emergency Response Data System (ERDS) system interface and data base for our Palisades Plant. The requested information and points of contact are provided in the attachment.

As noted in the attachment under item II.B.iv., Exceptions, we are not sure the requested 15 second data transmission rate can be maintained without affecting performance of the system during a plant transient. Consumers Power Company will use a 60 second transmission rate.

Consumers Power Company also would like to reiterate that our Big Rock Point Plant can not support the ERDS program without extensive modification because the plant does not utilize a plant data computer in the design of the plant.

Analyst CC Administrator, Region III, USNRC NRC Resident Inspector - Palisades JRJolicoeur, NRC, Washington DC TPLaRosa, EI International, Inc., Idaho Falls, ID Attachment OC0689-0006-NL02 A 0"115 E:IVERGY COMPANY

'.\

ATTACHMENT Consumers Power Company Palisades Plant Docket 50-255 EMERGENCY RESPONSE DATA SYSTEM SURVEY RESPONSE

  • June 27, 1989
  • OC0689-0006-NL02 56 Pages

ENCLOSURE 1

  • ERQS COMMUNICATIONS DESCRIPTION ANO SURVEY QUESTIONNAIRE The following is a questionnaire pertaining to the Nuclear Regulatory Commission's (NRC) Emergency Response Data ~1stem (EROS}. It consists of a series of questions concerning plant I/O points~ software protocols, data formats, transmission frequencies, and other plant computer specific information to be used in the EROS computer database files. Also, included here are descriptions and examples of data streams that the NRC is expecting to see transmitted over the commun1cation line.

The purpose of coll~cting this data is to develop a plant specific database that will be retrieved_intci the EROS once the system is activated by a utility. It will also be used to design and implement EROS software that can receive the utility's data transmission. In essence, this information will provide the basis for building a profile of the plant in the EROS database.

In some cases, the 1/0 point data may b~ distributed over several computers .

  • The EROS considers this situation a multi-feeder site and section IV must be filled out for each feeder .

I. CONTACTS Note: Please provide name, title, mailing.address, and phone number.

A. Survey Coordinator (i.e., contact for later clarification of question-naire answers):

Robert Hamm Consumers Power Company 27780 Blue Star Highway Covert, MI 49043 (616) 764-8913

8. Computer Hardware Specialist(s):

Andrew Zillins Consumers Power Company 27780 Blue Star Highway Covert, ~11 49043 (616) 764-8913 C. Systems Software Specialist(s):

Andrew Zillins D. Application-level Software Specialist(s):

Andrew Zillins E. Telephone Systems Specialist(s):

Robert Cowell Consumers Power Company Room P-14-109 1945 W Parnall Road Jackson, MI 49201 (517) 788-8952 II. EROS COMMUNICATIONS DESCRIPTION .

A. Hardnare The following hardware will be supplied:

-for a single feeder site:

Codex 2234 modem - V.22 2400 bps, asynchronous, autodialing, auto answer, error correcting, using the AT command set,

-for a multiple feeder site:

Cod~x 6015 multiplexer, Codex 2260 modem - V.32 9600 bps, asynchronous, autodialing, auto answer, error correcting, using the AT command set.

B. Software i~ Data T~ansmission

a. Site will initiate a link request in ASCII using:

-three character site designator

-the work LINK

-local site time and date in the format MM/00/YY/HH:MM:SS.

b. EROS will respond in ASCII with:

-three character site designator

-the word ACCEPTED or DENIED.

c. Upon being accepted, the plant begins transmission of data at a fifteen second rate. The data string consists_of:

-header that identifies the site and date and time

-data packet sequenced with point identifier, value, and quality tag

-trailer containing the checksum value of the data packet.

ii. Data Format Two delimiters have been identified as follo~s:

-field delimiter(*)

-Data Set delimiter(\)

a. Link request will be in ASCII as described in II.B.i.a. with each field separated by a field del i_miter and the request terminated with a data s~t delimiter. Example, PAl*LINK*Ol/12/89/11:48:50\.
b. EROS response will be in ASCII as described in II.B.i.b. with each field separated by a field delimiter and the response terminated with a data set delimiter. Example, PAl*ACCEPTEO\.
c. Data stream will be in ASCII and will consist of three parts, header, data, and trailer, as described in lI.B. i .c. with each field separated by a field delimiter and each of the three parts separated by a data set del'imiter. Example, Header: Pal*Ol/12/89/11:50:30\

Data: B21CP004*-0.J234E+00*3* ..... (for each parameter)\

Trailer: 56000\.

d. The following quality tags will be accepted by the EROS:

-Good

  • O value is within range tolerance for discreet points, or input points are within to*l erance for composed points.

-Off-Scan

  • 1 point is currently out-of-service.

-Suspect

  • 2 value is not bad yet should not be considered good. This quality will occur primarily on composed values, when enough of the inputs are good to make the calculation yet a bad quality on other inputs may make *the result quHtionable.

-Bad = 3 valoe is n6t within tolerance fof discreet points, or calculation of a composed point may not be made due to the qualities of its input.:;.

-Unknown = 4 no quality indicator available

-Operator Entered 5 value has been manually entered, overriding the discreet or composed value.

iii. Protocol

a. EROS will use XON/XOFF to stop, resume, or suspend data transmission for the site.
b. Communication parameters:

-eight data bits

-1 stop bit

-no special parity .

iv. Exceptions Please note any exceptions which must be taken to section II and explain why.

II.B.i.c - " . transmission of data at a fifteen second rate."

We are not sure that 15 second rate can be maintained quring a plant transient without affecting performance of critical function monitoring tasks.

Consumers Power will use 60 seconds for its transmission rate .

III. SELECTION OF DATA FEEDERS

  • A. How many data feeders are there? (six maximum}

One data feeder.

B. Identify the selected data feeders and provide the following for each:

(1) a short description of the categories of data points it will provide (e.g., met, rad, or plant data points, by unit) and (2) the rationale for selecting it if another system can also provide its categories of data points.

Critical Function Monitoring System (CFMS)

(1) All data points requested are available on CFMS and (2) only system containing. all categories of data points.

C. Which data feeder is the site time determining feeder? This should be -

the feeder which is providing the majority of the data points.

Critical Function Monitoring System (CFMS)

IV. DATA FEEDER INFORMATION Note: A new Section IV must be filled out for each feeder system selected.

A. General Questions

i. Identification of data feeder
a. What is the name in local parlance given to this data feeder (e.g.,

Emergency Response Information System)? Please give both the acronym and th~ words that form it.

Critical Function Monitoring System (CFMS)

b. Is this the site time determining feeder?

Ye.s

c. What is the update frequency of this feeder (in seconds)?

One second for all points except meteorological (15 minutes) and rod positions (1 to 2 seconds).

ii. Hardware/software environment*

a. Identify the manufacturer and model number of the data feeder hardware:

Perkin-Elmer, Model 3220 (Now Concurrent Computer Corporation)

b. Identify the operating system.

OS/32

c. What method of time-keeping is *implemented on this feeder system (Day-1ight Savings, Standard, Greenwich)7 Daylight Savings
d. In what time zone is this feeder located?

Eastern iii. Data communication details

a. Can this data feeder provide asynchronous serial data communication (RS232C) with full modem co1;trol?

In general., yes. Not sure if all possible modern control features are supported.

b. Will this feeder transmit in ASCII or EBCDIC?

ASCII

c. Can this feeder transmit at a serial baud rate of 2400 bps? If no*t, at what baud rate can it transmit?

Yes, it can transmit at 2400 baud.

d. Does the operating system support XON/XOFF fl ow contra l?

Yes I. Are there any proble~s foreseen in the NRC using XON/XOFF to control transmission of data?

No

e. If it is not feasible to reconfigure a serial port for the EROS linkup (i.e., change the baud rate, parity, etc.}, please explain why.

NA

f. Can the serial port dedicated to EROS be configured so that the NRC need not emulate a specific brand of terminal (i;e., can it be con-figured to be a "vanilla" terminal)?

Yes

g. Do any ports currently exist for the EROS linkup?

Yes, there are several spare parts.

1. If not, is it possible to add additional ports?
2. If yes, will the port be used solely by EROS or shared with other non-emergency-time users? Give details.

Used for ERDS only.

iv. Data feeder physical environment and management

a. Where is the data feeder located in terms of the TSC, EOF, and control -

room?

In trailer on turbine deck within 100 feet of Control Room/TSC .

b. Is the data feeder protected from loss of supply of electricity?

UPS will supply CFMS for greater than 60 minutes following loss of offsite power. For 30 minutes following loss of UPS, CFMS is capable pf .P.ower-f~il restart.

c. is there a numan operator for this data feeder?

No

1. If so, how many hours a day is the feeder attended?

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: .Power Range Safety Channel A GENERIC/COND DESC: Nuclear Instruments, Power Range ANALOG/DIGITAL:  :.:;A_ _ __

ENGR UNITS/DIG STATES:

I ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: """0_ _ __

MAXIMUM INSTR RANGE: ..;..1_25_ _ __

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: .; ;.l_ _ __

HOW PROCESSED: N/A SENSOR LOCATIONS: Adjacent to Reactor Vessel ALARM/TRIP SET POINTS: ""T_r1.....* p~R...e_..a.....c.....to-..r__.@._1.-.0.....

6.....5...%....__ _ _ _ _ _ _ __

UNIQUE SYSTEM DESC:

  • LIB REF-TC07 l
  • DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A NRC ERDS PARAMETER:  ; .;.N-.I_.I=N;. . ;.T. ; ;.E-.R.....RAN=...;;.G=E------------

POINT ID: NI003

..-,..;...;..;------------------~

PLANT SPEC POINT DESC: *wide Range Power NI003 GENERIC/COND DESC: Nuclear Instruments, Intermediate Range ANALOG/DIGITAL: A

=-----

ENGR UNITS/DIG STATES:  %

I I

=-----

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: l.OE-8 MAXIMUM INSTR RANGE: l.OE2 ZE.RO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: s NUMBER OF SENSORS: 1 HOW PROCESSED: N/A SENSOR LOCATIONS: Adjacent to Reactor Vessel ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC:

  • LIB REF-TC07 2

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: *Start Up Count Rate X NIOOl GENERIC/COND DESC: Nuclear Instruments, Source Range ANALOG/DIGITAL: .A ENGR UNITS/DIG STATES: CPS

/

ENGR UNITS CONVERSION:

  • MINIMuM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

l.OEO 3.0E5 REFERENCE POINT NOTES:

PROC OR SENS: s NUMBER OF SENSORS: 1 HOW PROCESSED: N/A SENSOR LOCATIONS: Adjacent to Reactor Vessel ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Source range instrument turned off above l.OE-5% on intermediate range nuclear instruments

  • LIB REF-TC07 3
  • DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A NRC EROS PARAMETER: REAC VES LEV POINT ID: LRXVSL PLANT SPEC POINT DESC: Reactor Vessel Level GENERIC/COND DESC: Reactor Vessel Water Level ANALOG/DIGITAL: A ENGR UNITS/DIG STATES:  %

I ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

0 100 .

TAF REFERENCE POINT NOTES: 0% 11 In Above TAF, 100% - Top of Head PROC OR SENS: p NUMBER OF SENSORS: 16 HOW PROCESSED: Complex SENSOR LOCATIONS: Inside Reactor Vessel ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Reactor vessel level monitored by heated junction thermocouples (HJT) at eight discreet axial locations.

Status of each HJT is monitored (covered/uncovered) and status is converted to relative level in %.

LIB REF-TC07 4

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 DATA FEEDER: _N./A NRC ERDS PARAMETER: TEMP CORE EX


"""""-'_..;;.;~--------------------------

POINT ID: TCETAVG -

PLANT SPEC POINT DESC: *cET Average Temperature GENERIC/COND DESC: Highest Temperature at the Core Exit ANALOG/DIGITAL:

  • A

~----

ENGR UNITS/DIG STATES: F I

ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

0 2400 REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 16 HOW PROCESSED: Average SENSOR LOCATIONS: Inside Reactor Vessel ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Plant procedures use average core exit thermocouple reading rather than highest reading *

  • LIB REF-TC07 5

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOa UNIT: PAl DATA FEEDER: N/A NRC EROS PARAMETER: SUB MARGIN POINT ID: TCETMAR PLANT SPEC POINT DESC: CET Subcooled Margin GENERIC/COND DESC: Saturation Temperature - Highest CET ANALOG/DIGITAL: A ENGR UNITS/DIG I .

STATES: F I

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: _-.-35.___ __

MAXIMUM INSTR RANGE: _2.....

00.___ __

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: _P_ _ __

NUMBER OF SENSORS:

17 HOW PROCESSED: Complez SENSOR LOCATIONS:

Inside Containment ALARM/TRIP SET POINTS: <25°F Requires EOP Actions UNIQUE SYSTEM DESC: Saturation temperature determined from pressurizer pressure. Average CET temperature subtracted from saturation temperature to determine subcooled margin. Output value negative if superheated.

LIB REF-TC07 6

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 NRC ERDS PARAMETER: CORE FLOW

--.....-;..._.;;--.~~~~~--~~~~~~~~-

PLANT SPEC POINT DESC: Primary Coolant Loop lA DP GENERIC/COND DESC: Total Reactor Coolant Flow ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSID

. I ENGR UNITS CONVERSION: 48 PSID = 62 MLB/HR

~~~~~~~---~~~~~~~~~~-

MINIMUM INSTR RANGE: 0 MAXIMUM INSTR 63.75 RANG~:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: _l_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Point provides differential pressure across "A" steam generator and is indicative of flow thru *the loop

  • LIB REF-TC07 7

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DI:SC: *Primary Coolant Loop 2A DP GENERIC/COND DESC: Total Reactor Coolant Flow ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSID I

ENGR UNITS CONVERSION: 48 PSID = 62 MLB/HR

---~---~---------------~~~~~~~~~-

MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: _6_3*._7....5_ __

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

S NUMBER OF SENSORS: """l_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Point provides differential pressure across 11 8 11 steam generator and is indicative of flow thru the loop

  • LIB REF-TC07 8

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Stm Gen A Lvl Best Estimate GENERIC/COND DESC: Steam Generator A Water Level ANALOG/DIGITAL: A ENGR UNITS/DIG STATES:  %

I ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: -138 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

UTubes REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: Selects between narrow/wide r.ange SENSOR LOCATIOHS: Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: -138% corresponds to 15 inches above tube sheet. 100% corresponds to top of moisture separators.

LIB REF-.TC07 9

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: *stm Gen B Lvl Best Estimate

A ENGR UNITS/DIG STATES:  %

~----

I ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: -138 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

UTubes REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: Selects between narrow/wide range SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: -138% Corresponds to 15 inches above tube sheet. . 100% corresponds to top of moisture separators.

LIB REF-TC07 10

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Steam Generator E-SOA Pressure GENERIC/COND DESC: Steam Generator A Pressure ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIA

/

ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

0

_1_00_0_ __

REFERENCE POINT NOTES:

PROC OR SENS: ""'S_ _ __

NUMBER OF SENSORS: ""'!_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: _I_ns_1_'d_e__C_o_n_ta_i_nm

__en

__t _____________________

ALARM/TRIP SET POINTS: <500 PSIA Isolates HSIV's UNIQUE SYSTEM DESC:

LIB REF-TC07 11

  • DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A NRC ERDS PARAMETER: SG PRESS B

~------------------

PLANT SPEC POINT DESC: -Steam Generator E-508 Pressure GENERIC/COND DESC: Steam Generator B Pressure ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIA

/

ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

0

_l..._00._0_ __

REFERENCE POINT NOTES:

PROC OR SENS: .-s_ _ __

NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: Inside Containment

~----------------------~

ALARM/TRIP SET POINTS: <500 PSIA Isolates MSIV's UNIQUE SYSTEM DESC:

  • LIB REF-TC07 12

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 DATA FEEDER: _N.._/A_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __

NRC ERDS PARAMETER:

POINT ID:

MN FD FL A FT0701 PLANT SPEC POINT DESC: *Feed Flow to Steam Gen E-50A GENERIC/COND DESC: Steam Generator A Main Feedwater Flow ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: LBM/HR

/

ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

O.OE5 6.0E6 REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: .Turbine Building ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC:

LIB REF-TC07 13

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Feed Flow to Steam Generator E-SOB GENERIC/COND DESC: Steam Generator B Main Feedwater Flow ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: LBM/HR I

ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

o. . .o...E=s_ __

6.0E6 REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: Turbine Building ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC:

  • LIB REF-TC07 14

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 NRC ERDS PARAMETER:_ _AX_F_D_F_L_A_ _ _ _ _ _ _ _ _ _ _ _ _ __

POINT ID: FT0749A


~

PLANT SPEC POINT DESC: *Aux FW Flow to Steam Generator E-50A GENERIC/COND DESC: Stm Gen A Auxiliary Feedwater Flow ANALOG/DIGITAL: A

~----

ENGR UNITS/DIG STATES:

/

ENGR UNITS CONVE~SION:

GPM MINIMUM INSTR RANGE: . ;.,0_ _ __

MAXIMUM INSTR RANGE: 450..._

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S

~----

NUMBER OF SENSORS_: -.1_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: Auxiliary Building ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Two AFW trains provided. Train 1 consists of 1 electric and 1 turbine driven pump. Train 2 consists of 1 electric driven pump. This is flow to steam generator A from train 1*

LIB REF-TC07 15

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: *Aux FW Flow To Steam Generator E-SOA GENERIC/COND DESC: . Stm Gen A Auxiliary Feedwater Flow ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM

~~..,...---

./

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: """0_ _ __

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

450 REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: _!_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: Auxiliary Building ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Two AFW trains provided. Train 1 consists of 1 electric and 1 turbine driven pump. Train 2 consists of 1 electric driven pump. This is flow to steam generator A from train 2*

LIB REF-TC07 16

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Aux FW Flow to Steam Generator E-508 GENERIC/COND DESC: Steam Generator B Auxiliary Feedwater Flow ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM

~------

/

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGF.: o____

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

450 REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: _l_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: Auxiliary Building ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Two AFW trains provided. Train 1 consists of 1 electric and 1 turbine driven pump. Train 2 consists of 1 electric driven pump. This is flow to steam generator B from train l.

LIB REF-TC07 17

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Aux FW Flow To Steam Generator E-508 GENERIC/COND DESC: Steam Generator A Auxiliary Feedwater Flow ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

0 450 REFERENCE POINT NOTES:

PROC OR SENS: _s_ _ __

NUMBER OF SENSORS: .-1_ __.__

HOW PROCESSED:

SENSOR LOCATIONS: Auxilia-ry Building ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Two AFW trains provided. Train 1 consists of 1 electric and 1 *turbine driven pump. Train 3 consists of 1 electric driven pump. This is flow to steam generator B from train 2

  • LIB REF-TC07 18

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Hot Leg Loop 1 Temperature GENERIC/COND DESC: Steam Generator A Inlet Temperature ANALOG/DIGITAL: A

~----

ENGR UNITS/DIG STATES: F I -------

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: so____

MAXIMUM INSTR RANGE: ..._70.._0..___ __

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: On Hot Leg Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC:

LIB REF-TC07 19

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Hot Leg Loop 2 Temperature GENERIC/COND DESC: Steam Generator B Inlet Temperature ANALOG/DIGITAL: A

=-----

ENGR UNITS/DIG STATES: F

/

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 50 MAXIMUM INSTR RANGE:

700 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: _s_ _ __

NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: On Hot Leg Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC:

LIB REF-TC07 20

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: told Leg Loop lA Temperature GENERIC/COND DESC: Steam Generator A Outlet Temperature ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: F

/

I -----

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 50 MAXIMUM INSTR RANGE: 700 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: _l_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: On Cold Leg Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: One hot leg and two cold legs per steam generator. This is temperature at outlet of primary coolant pump lA.

LIB REF-TC07 21

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Cold Leg Loop lB Temperature GENERIC/COND DESC: Steam Generator A Outlet Temperature ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: F

/ -----

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 50 MAXIMUM INSTR RANGE: 700

"'---~---

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: 1 HOW.PROCESSED:

SENSOR LOCATIONS: On Cold Leg Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: One hot leg and two cold legs per steam generator. This is temperature at outlet of primary coolant pump lB *

  • LIB REF-TC07 22

DATA POINT LIBRARY REFERENCE FILE DATE: 06/ 01 /89 DATA FEEDER:

  • N/A

~----

NRC ERDS PARAMETER: CL TEMP B

""'-""--~--~~~~~---~----

POINT ID: TT0122CA


~~-~~~-~~~~~~

PLANT SPEC POINT DESC: Cold Leg Loop 2A Temperature GENERIC/COND DESC: Steam Generator B Outlet Temperature ANALOG/DIGITAL:

A ENGR UNITS/DIG STATES: F ENGR UNITS CONVERSION:

. MINIMUM INSTR RANGE: 50 MAXIMUM INSTR RANGE:. 700 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S

~----

NUMBER OF SENSORS: .;;..l_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: On Cold Leg Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: One hot leg and two cold legs per steam generator. This is temperature at outlet of primary coolant pump

. 2A *

  • LIB REF-TC07 23

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: Cold LegLoop 28 Temperature GENERIC/COND DESC: Steam.Generator B Outlet.Temperature ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: F

/

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 50 MAXIMUM INSTR RANGE: 700 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: On Cold Leg Inside Containment ALARM/TRIP SET POINTS:.

UNIQUE SYSTEM DESC: One hot leg and two cold legs per steam generator. This is temperature at outlet of primar? coolant pump 2B.

LIB REF-TC07 24

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl

~------------------

DATA FEEDER:

NRC ERDS PARAMETER:

N/A

_R_CS_P_R_E_ss.....UR_.....E..___ _ _ _ _ _ _ _ _ _ __

POINT ID:

PLANT SPEC POINT DESC:

PZRBE Pressurizer Pressure Best Estimate GENERIC/COND DESC: Reactor Coolant System Pressure ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIA ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: ""0_ _ __

MAXIMUM INSTR RANGE: .;;.3..;...00"""0'----

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: . 2 HOW PROCESSED: Selects Between Narrow/Wide Range SENSOR LOCATIONS: Inside Contaiment

  • ALARM/TRIP SET POINTS: Safety Injection at 1600 PSIA UNIQUE SYSTEM DESC:

LIB REF-TC07 25

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: *PAl

.,.----------~~----~---~

DATA FEEDER: N/A

"-"--------~-~-~----~--~

NRC ERDS PARAMETER: PRZR LEVEL

.;;.......-----------------~---~

POINT ID: LPRZC


~

PLANT SPEC POINT DESC: _P_z_r_L_v_l_C_o_m.._p_e_n_sa"""t....e_d_ _ _ _ _ _ _ _ _ __

GENERIC/COND DESC: Primary System Pressurizer Level ANALOG/DIGITAL: A ENGR UNITS/DIG STATES:  %

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 100 ZERO POINT

REFERENCE:

Lwhead REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: Temperature Compensated SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS: Top of Heaters 36%

UNIQUE SYSTEM DESC: Taps in pressurizer heads. Level is temperature compensated for process temperature *

  • LIB REF-TC07 26
  • DATA POINT LIBRARY REFERENCE FILE .

DATE: 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A NRC ERDS PARAMETER: *acs CH/MU

~o;_;;..;;.;.;....;,;-._ _ _ _ _ _ _ _ _ _ _ _ _ __

POINT ID: FT0212

~--"---------------------

PL ANT SPEC POINT DESC: _Ch_a....r_.g,._i_n...g_.._L1..._*n-"e--.F_l....o_w_ _ _ _ _ _ _ _ _ __

GENERIC/COND .DESC: Primary System Charging Flow ANALOG/DIGITAL: .A ENGR UNITS/DIG STATES: GPH ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

0 140 REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS:

  • _l_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: ~A_ux_1_*1_i_a_ry.....__su_i_l_d_i_n ...s_*_____________

ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Flow provided by up to 3* positive displace-ment pumps.

LIB REF-TC07 27

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 PLANT SPEC POINT DESC: HPSI Total Flow


~~~~~~~~~~~~~~~

GENERIC/COND DESC: High Pressure Safety Injection Flow ANALOG /DIGITAL: A ENGR UNITS/DIG STATES: GPM

. ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: _10_0.....,0_ __

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 4 HOW PROCESSED: Addition SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Sum of flow from up to two HPSI pumps thru 4 injection paths. Shutoff head = 1200 PSIG. Desfgn flow JOO GPM/Pump LIB REF-TC07 28

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl

~--------~~~~----~-

DATA FEEDER: N/A

~----~--~~~~~--~-~-

NR C ERDS PARAMETER: LP SI FLOW

~---~----~~~~--~~~-

PO INT ID : FTOTLPSI

~--~~----~~~~-~~---

PL ANT SPEC POINT DESC: LPSI Total Flow

~-~~~~~-~~~-----~~-

GENERIC/CO ND DESC: Low Pressure Safety Injection Flow ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: GPM ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 8000 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: P NUMBER OF SENSORS: _4_ _ __

HOW PROCESSED: Addition SENSOR LOCATIONS: Inside Containment

=-~""""-....;..;;..;.;..;;_=-'-==------~~~--------~-

ALARM/TR IP SET POINTS:

UNIQUE SYSTEM DESC: Total flow from up to two LPSI pumps, thru 4 injection paths. Shutoff head = 170 PSIG.

Design flow = 3000 GPM/Pump

  • LIB REF-TC07 29

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAI

~~~~~~~~~~~~~~~~~~-

DATA FEEDER: N/A

~~~~~~~~~~~~~~~~~~-

WC @~PAR~~@t C'NTS~PW

~~~-~~~~~~~~~------

PO INT ID: LT0382

~~~-~-~--~~~~~~-~--

PL ANT SPEC POINT DESC: *containment Sump Level GENERIC/COND DESC: Containment Sump Narrow Range Level ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: FT ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 585.0 MAXIMUM INSTR RANGE: . 590.5 ZERO POINT

REFERENCE:

Sealev REFERENCE POINT NOTES:

PROC OR SENS: .; . .S_ _ __

NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Instrument range is displayed in feet of elevation from bottom to top of sump. 585.0 ft = sump bottom LIB REF-TC07 JO

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A NRC ERDS PARAMETER: CTMNT SMP WR POINT ID: LT0446A PLANT SPEC POINT DESC.: CNMT Floor Water Level GENERIC/COND DESC: Containment Sump Wide Range Level ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: FT ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

590.3 597.3 Sealev REFERENCE POINT NOTES:

PROC OR SENS: *. ; . S_ _ __

NUMBER OF SENSORS: . ; . l_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Instrument range is displayed in feet of elevation from containment floor to top of scale.

590.0 ft = containment floor elevation.

LIB REF-TCO 7 31

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl

. DATA FEEDER: N/A NRC ERDS PARAMETER: EFF GAS RAD POINT ID: RIA2327 PLANT SPEC POINT DESC: *stack Hi Rng Noble Gas GENERIC/COND DESC: Radioactivity of released gasses ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MR/HR ENGR UNITS CONVERSION: CI/SEC= (.774)MR/HR

  • MINIMUM INSTR RANGE:

MAXIMuM INSTR RANGE:

ZERO POINT

REFERENCE:

l.OEl l.OE7 REFERENCE POINT NOTES:

PROC OR SENS: . ; . S_ _ __

NUMBER OF SENSORS:

1 HOW PROCESSED:

SENSOR LOCATIONS: _Aux __i_l_i_a_r_y_B_u_i_l_d_i_n_g_____________________

ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Stack flow rate not provided in computer.

Conversion to CI/SEC based on normal stack flow (82000 CFM).

LIB REF-TCO 7 32

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: ~PA_l ____________________________________

DATA FEEDER: """'-..;......

N/ A _______________________________

NRC ERDS PARAMETER: .; ;E.FF;;._.;;L=I""'Q""""R=AD=-*-------------

POINT ID: ~R~l0. . .4~9'----------.,..--------------

PLANT SPEC POINT DESC: Rad Waste Discharge Mon GENERIC/COND DESC: Radioactivity of Released Liquids ANALOG/DIGITAL: A

~----

ENGR UNITS/DIG STATES: C/MIN

~--------

ENGR UNITS CONVERStON:

MINIMUM INSTR RANGE: i.OEl MAXIMUM INSTR RANGE: l.OE6 ZERO POINT REFEREN~E:

REFERENCE POINT NOTES:

PROC OR SENS: .; ;. S_ _ __

NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS:

ALARM/TRIP SET POINTS: Service water structure UNIQUE SYSTEM DESC: Discharge flow not measured LIB REF-TCO 7 33

DATA POINT LIBRARY REFERENC.E FILE DATE: 06/01/89 REACTOR UNIT: PAl

--~~--~-~----~-----

DATA FEEDER: N/A


~-----

NR C ERDS PARAMETER: COND A/E RAD


~-------------

PO INT ID: RIA0631


~---------

PLANT SPEC POINT DESC: -_O_ff_G_a_s_M_on_i_t_o_r_i_ng_ _ _ _ _ _ _ _ _ _ __

GENERIC/COND DESC: Condensor Air Ejector Radioactivity ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: C/Min ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: l.OEl MAXIMUM INSTR RANGE: l.OE6 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: _!_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: ~Tu_r_b_i_n_e-.;;;.B~u1-*l~d-i~n~g-------------

ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC:

LIB REF-TC07 34

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PA!

DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT RAD POINT ID: RI1805 PLANT SPEC POINT DESC: CNMT Radiation Iso RI1805 GENERIC/COND DESC: Radiation Level in the Containment ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: R/HR ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: l.OE-2 MAXIMUM INSTR RANGE: l .OE4 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: s NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS: 20 R/Hr Isolate Containment .

UNIQUE SYSTEM DESC:

  • LIB REF-TC07 35

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT RAD POINT ID: RIA2321 PLANT SPEC POINT DESC: CNMT Hi Range Gamma RIA2321 GENERIC/COND DESC: Radiation Level in the Containment

.ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: R/HR

    • ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

l.OEO 1.0E7 REFERENCE POINT NOTES:

PROC OR SENS: s NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: Inside Containment ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Instrument reads offscale low during normal operations *

  • LIB REF-TC07 36

DATA POINT LIBRARY .REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A NRC ERDS PARAMETER: RCS LETDOWN RAD POINT ID: RR0202B PLANT SPEC POINT DESC: Failed Fuel Monitor GENERIC/COND DESC: Rad Level of the RCS Letdown Line ANALOG/DIGITAL: A

. ENGR UNITS/DIG STATES: C/Min ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

1

. ; . 0_ _ __

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: s NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: Auxiliary Building ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Instrument reading must be multiplied by exponent determined by switch setting in control room. Switch setting not available in computer. Monitor isolated following isolation of letdown.

LIB REF-TC07 37

  • DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A NRC EROS PARAMETER: MAIN SL A POINT ID: RIA2324 PLANT SPEC POINT DESC: Stm Gen A Gamma RIA2324 GENERIC/COND DESC: Stm Gen A Steam Line Rad Level ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: C/Min ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 1.0El MAXIMUM INSTR RANGE: 1.0E6 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: s NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: On Stm Line Awr: Bldg ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Flow thru atmospheric dump valves not measured, calculated by procedure *

  • LIB REF-TC07 38
  • DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR uNIT: PAl DATA FEEDER: N/A NRC ERDS PARAMETER: ""MA.;. .I; . ;N"--"S;. . ;L;_, ; ; ,B_ _ _ _ _ _ _ _ _ _ _ _ _ __

POINT ID: RIA2323

=-...;~~--------~~~-----

PL ANT SPEC POINT DESC: *stm Gen B Gamma RIA2323 GENERIC/COND DESC: Stm Gen B Steam Line Rad Level ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: C/Min ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: l.OEl MAXIMUM INSTR RANGE: l.OE6 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: S NUMBER OF SENSORS: _1_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: On Stm Line Aux Bldg ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Flow thru atmos*pheric pump valves not measured, calculated by procedure *

  • LIB REF-TC07 39
  • DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAI DATA FEEDER: N/A NRC EROS PARAMETER: CTMNT PRESS POINT ID: PT1805A PLANT SPEC POINT DESC: *Containment WR Press 1805A GENERIC/COND DESC: Containment Pressure ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: PSIG ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: -14.7 MAXIMUM INSTR RANGE: 185.3 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS : S NUMBER OF SENSORS: _1_ _ __

HOW PROCESSED:

SENSOR LOCATIONS: Auxiliary Building Outside Containment ALARM/TRIP SET POINTS: Containment Isolation at 3.7 PSIG UNIQUE SYSTEM DESC: Normal Pressure 0 PSIG LIB REF-TC07 40

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAl

~------------------

DATA FEEDER: N/A


~~------~------

NR C ERDS PARAMETER: CTMNT TEMP

~---~--~-----------

PO INT ID: TE1815

~---~--------------

PL ANT SPEC POINT DESC: "containment Bldg Dome Temp GENERIC/COND DESC: Containment Temperature ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: F ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

0

_40_0_ _ __

REFERENCE POINT NOTES:

PROC OR SENS: s NUMBER OF SENSORS: 1 HOW PROCESSED:

SENSOR LOCATIONS: Containment Dome Near Top ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC:

LIB REF-TC07 41

  • DATA POINT LIBRARY REFERENCE FILE DATE: . 06/01/89 REACTOR UNIT: PAl DATA FEEDER: N/A PLANT SPEC POINT DESC: CNMT H2 Cone Left

~---~---------~~~~~~~~~~-

GENERIC/COND DESC: Containment Hydrogen Concentration ANALOG/DIGITAL: A ENGR UNITS/DIG STATES:  %

/'

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGE: 20 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: s ____

NUMBER OF SENSORS: _l_ _ __

~ow PROCESSED:

SENSOR LOCATIONS: Auxiliary Building ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Instrument turned off during normal opera-tions.

LIB REF-TC07 42

DATA POINT tIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PA!

DATA FEEDER: N/A NRC EROS PARAMETER: BWST LEVEL.

POINT ID: LT0331 PLANT SPEC POINT DESC: *sIRW Tank Level GENERIC/COND DESC: Borated Water Storage Tank Level ANALOG/DIGITAL: A ENGR UNITS/DIG STATES:  %

ENGR UNITS CONVERSION:

  • MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

0 100 TNKBOT REFERENCE POINT NOTES: 0% = 18,646 Gal, 100% = 298 1 400 Gal PROC OR SENS: s NUMBER OF SENSORS: 1 HOW PROCESSED:

\

SENSOR LOCATIONS: On Tank

---==------------------~

ALARM/TRIP SET POINTS: Recirculation.Actuation at 2%

UNIQUE SYSTEM DESC: Safety injection and refueling water (SIRW) tank is nomenclature used at Palisades LIB REF-TC07 43

  • DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: PAI DATA FEEDER: N/A NRC EROS PARAMETER: WIND SPEED

~------------------

PLANT SPEC POINT DESC:W __in_d....._S...,p_e....e_..d_6_0._M_ _ _ _ _ _ _ _ _ _ _ __

GENERIC/COND DESC: Wind Speed at the Reactor Site ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: MPH

. I I -----

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: 0 MAXIMUM INSTR RANGF.: 100 ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: p NUMJ!ER OF SENSORS:

HOW PROCESSED: 15 Min Average SENSOR LOCATIONS: Met Tower ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Point updated every 15 minutes to indicate average for preceding 15 minutes.

LIB REF-TCO 7 44

I)

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 REACTOR UNIT: ~P_A_l ___________________________________

DATA FEEDER: ~N~/A--------------------------------~

NRC EROS PARAMETER: -'------..;...

WIND DIR ______________________________

POINT ID: MWD60

~------------------------------------

PLANT SPEC POINT DESC: Wind Direction 60H

~------......-...... ~.o.-.;;------------------------

GENERIC/COND DESC: Wind Direction at the Reactor Site ANALOG/DIGITAL: . A ENGR UNITS/DIG STATES: DEGFR ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE: .....o____

MAXIMUM INSTR RANGE: 360 ZERO POINT

REFERENCE:

REFERENCE. POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 1 HOW PROCESSED: 15 Min Average SENSOR LOCATIONS: Met Tower ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Point updated every 15 minutes to indicate average for preceding 15 minutes.

LIB REF-TC07 45

DATA POINT LIBRARY REFERENCE FILE DATE: 06/01/89 NRC ERDS PARAMETER: ~S-TA~B~C-L~AS~S------------~--

PLANT SPEC POINT DESC:  ; . ; M_e.. _t_.So....;t'""a...,b.-..i_l_it....y.......__ _ _ _ _ _ _ _ _ _ _ __

GENERIC/COND DESC: Air Stability at the Reactor Site ANALOG/DIGITAL: A ENGR UNITS/DIG STATES: STAB!

ENGR*UNITS CONVERSION:

MINIMUM INSTR RANG.E: _!_ _ __

MAXIMUM INSTR RANGE: ...7_ _ __

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS: p NUMBER OF SENSORS: 2 HOW PROCESSED: T60M-TlOM, 15 min average SENSOR LOCATIONS: Met Tower ALARM/TRIP SET POINTS:

UNIQUE SYSTEM DESC: Point updated every 15 minutes to indicate average for preceding 15 minutes *

  • LIB REF-TC07 46