Monthly Operating Rept for Aug 1988 for Palisades Nuclear Plant
ML18053A563
Person / Time
Site: Palisades 
Issue date: 08/31/1988
From: Goralski G, Packard G
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
NUDOCS 8809150169
Download: ML18053A563 (5)


Text

OPERATING DATA REPORT DOCKET NO 50-255 DATE 09-09-88 COMPLETED BY GCPackard TELEPHONE (616)764-8913 OPERATING STATUS NOTES

1.

Unit Name: Pali sades

~~~~~~~~~~~~~~~~~~

2.

Reporting Period:

880801-880831

3.

Licensed Thermal Power (MWt):

2530

4.

Nameplate Rating (Gross MWe):

811.7

5.

Design Electrical Rating (Net MWe):

805

6.

Maximum Dependable Capacity (Gross MWe): **770

7.

Maximum Dependable Capacity (Net MWe):

'l.'"*730

8.

If Changes Occur in Capacity Ratings (Items Number 3 through 7) since last report, give reasons:

9.

Power Level to Which Restricted, if any (Net MWe):

10.

Reasons for Restrictions, if any:

This Month

11.

Hours In Reporting Period 744.0

12.

Number of Hours Reactor Was Critical 186.7

13.

Reactor Reserve Shutdown Hours

14.

Hours Generator On-Line 186.5

15. Unit Reserve Shutdown Hours
16.

Gross Thermal Energy Generated (MWH) 4442768

17.

Gross Electrical Energy Generated (MWH) 137 2200

18.

Net Electrical Energy Generated (MWH) 1292443

19.

Unit Service Factor 25.1

20.

Unit Availability Factor 25.1

21.

Unit Capacity Factor (Using MDC Net) 23.8

22.

Unit Capacity Factor (Using DER Net) 21.6

23.

Unit Forced Outage Rate o.o

24.

Shutdowns Scheduled Over Next Six Months (Type, Date and Yr-to-Date Cumulative 52855.0 1462414.0 42587.9 78 2604.9 42547.9 74 2814.1 1028792104 158 2067 2021 32480 2785 4923942305 3 2297 2879 4625142913

77. 7.

51.1

77. 7 51.1 77.2
  • 48.9 70.0 39.5 14.2 34.9 Duration of Each):
25. If Shut Down at.End of Report Period, Estimated Date of Start Up: November 30, 1988
26.

Units in Test Status (Prior to Commercial Operation):

INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

    • Based on condenser backpressure Forecast
  • Weighted Average (635 MWe used as MDC Net prior to October 1985)

OC0185-0001B-OP03

,. - -~

Achieved

~AVERAGE DAILY UNIT POWER LEVEL ~

DOCKET NO 50-255 UNIT __

P_a_l_i_s_a_d_e_s DATE 09-08-88 COMPLETED BY GCPackard TELEPHONE (616)764-8913 MONTH AUGUST 1988 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

(MWe-Net) 1 704 17 0

2 699 18 0

3 700 19 0

4 700 20 0

5 702 21 0

6 710 22 0

7 710 23 0

8 468 24 0

9 0

25 0

10 0

26 0

11 0

27 0

12 0

28 0

13 0

29 0

14 0

30 0

15 0

31 0

16 0

INSTRUCTIONS:

On this format, list the average daily unit power level in MWe-Net for each day in the reporting month.

Compute to the nearest whole megawatt.

OC0185-0001C-OP03

REPORT MONTH AUGUST 1988


~

No.

Date Type1 20 880808 s

1.
2.

F:

Forced S:

Scheduled OC0185-0001D-OP03 Duration Reason2 (Hours) 557.5 c

Reason:

A-Equipment Failure (Explain)

B-Maintenance or Test C-Refueling D-Regulatory Restriction E-Operator Training & License Examination F-Administrative G-Operational Error (Explain)

H-Other (Explain)

UNIT SHUTDOWNS AND POWER REDUCTIONS Method of Licensee Shutting Event Down Reactor3 1

3.

Report #

Method:

1-Manual 2-Manual Scram 3-Automatic Scram 4-0ther (Explain)

4.

System Component Code4 Code5 Exhibit G - Instructions for Preparation of Data Entry Sheets for Licensee Event Report (LER) File (NUREG-0161)

J DOCKET NO.

50-255 UN IT NAME Palisades DATE ----""""0""""9--'0"""7--8"-"-8 COMPLETED BY GCPackard TELEPHONE (616)-764-8913 Cause & Corrective Action to Prevent Recurrence Scheduled refueling

5.

Exhibit I - Same Source

SUMMARY

OF OPERATING EXPERIENCE FOR AUGUST 1988 The plant was operating at 95% power until August 8, at 1840 hours0.0213 days <br />0.511 hours <br />0.00304 weeks <br />7.0012e-4 months <br /> when the plant was shutdown due to a Primary-to-Secondary leak in the B Steam Generator.

Since core burnup was at End Of Life, the plant then entered its scheduled Refueling Outage and remained shutdown through the end of the reporting period.

OC0185-0001E-OP03

consumers Power POW ERi Nii MICHlliAN"S PROliRESS Palisades Nuclear Plant: 27780 Blue Star Memorial Highway, Covert, Ml 49043 September 9, 1988 US Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 LICENSE REPORT OF MONTHLY OPERATING DATA DPR-20, DOCKET NO 50-255 Enclosed is a copy of the Monthly Operating Data and a Summary of Operating Experience for the Palisades Nuclear Plant for the month of August, 1988.

~~

~fl"\\.JL})_:

George Goralski Reactor Engineer CC: KMHaas, Palisades A8Davis, USNRC KW8erry, P24-6148 CSKozup, Palisades Resident Inspector, Palisades DLHackett, Pll-4208 GW8ruckmann, Div of Radiological Health Services, Lansing, Michigan SLHall, Michigan Dept of Labor RCallen, Michigan Public Service Commission Records Center, INPO, Atlanta, GA RWTaylor, CE, Palisades AAAlatalo, Palisades LL8umb, P21-324 G8Szczotka, P-21-3118 HRSnider, P-21-326 Administrator, USNRC Document Control, 950~<22~<35*10/L GCP88-031 OC0185-0001A-OP03 A CMS e;tERGY COMPANY