CONSUMERS POWER COMPANY PALISADES PLANT - DOCKET 50-255 - LICENSE DPR-20 PROPOSED TECHNICAL SPECIFICATIONS CHANGE REQUEST

... ' 8309020360 B30B29

~DR ADOCK 05000255 PJ)R OC0483-0002C-NL02 PROPOSED PAGES 1 Page

c- --'--5. ----NUCLEAR-S'l'EAM- -SUF-FLY SYSTEM-(NSSS)---(Gontd}- ---- - ------- --- --------- ---------------

5.3.2 5.3.3 5.4 5.4.1_

Reactor Core and Control

a.

The reactor core shall approximate a right circular cylinder with an equivalent diameter of about 136 inches and an active height of about 132 inches.*

b.

The reactor core shall consist of approximately 43,000 Zircaloy-4 clad _fuel rods containing slightly enriched uranium in the form of sintered U02 pellets.

The fuel rods shall be grouped into 204 assemblies.

A core plug or plugs may be used to replace one or more fuel assemblies subject to the analysis of the resulting power distribution.

c.

The fully loaded core shall contain approximately 211,000 pounds uo2 and approximately 56,000 pounds of Zircaloy-4.

Poison may be placed in the fuel bundles for long-term reactivity control.

d.

The core excess reactivity shall be controlled by a combination of boric acid chemical shim, cruciform control rods, and mechanically fixed boron rods where required.

Forty-five control rods shall be distrib_uted throughout the core as shown in Figure 3..:5 of the FSAR.

Four of these control rods may consist of part-length absorbers.

Emergency Core Cooling System

These subsystems shall include four safety *injection tanks, two high-pressure and two low-pressure safety injection pumps and a safety injection and refueling water storage tank.

FUEL STORAGE New Fuel Storage

a.

The pitch of the new fuel storage rack lattice is +/- 9.375 inches,

_ and every other position in the lattice shall be permanently occupie'd nu0483-0105a-43-46 5-3 Proposed