SEISMIC CONSULTATION FOR SAFETY-RELATED ELECTICAL EQUIPMENT CONSUMERS POWER COMPANY PALISADES PLANT COVERT, MICHIGAN Interim Report l EQUIPMENT CHECKLIST prepared for Consumers Power Corporation Jackson, Michigan March 20, 1980 prepared by URS/Jann A~ Blume and Associates, Engineer~
130 Jessie Street (at New Montgomery)
San Francisco, California 94105
Revision Number 0
SEISMIC CONSULTATION FOR SAFETY RELATED ELECTRICAL EQUIPMENT CONSUMERS POWER CORPORATION COVERT, MI CH I GAN Date 3/20/ec Interim Report 1 Equipment Check List Prepared Checked by by
~( uP Approved by
~
Description In it i a 1 Release
Purpose Scope Results TABLE Equipment Checklist CONTENTS 2
Attachments............. *.................................................. 5
Purpose This report summarizes a walkdown inspection of all safety-related electrical equipment at Consumers Power Company's Palisades Plant near Covert, Michigan.
The inspection was conducted by URS/Blume personnel between March 3 and 14, 1980.
Scope The walkdown inspection included all safety-related electrical equipment.
The equipment type and. identification were recorded on the equipment checklist.
Cover panels were removed to allow the inspection team to examine the equipment base.
The presence or absence of a positive structural co~nection between the equipment and floor slabs or wal Js was recorded on the check I ist.
Positive anchorage is defined as any competent load carrying mechanism other than fric-tion.
Non-Category I items which 'could damage or interfere with the operation of safety-related equipment were noted on the checklist and tabulated on the checklist attachments.
Results Table I is the equipment checklist.
Attachments I through 27 tabulate non-Category I items and these attachments are cross-referenced on the checklist.
. The ad~quacy of an equipment anchorage dep~nds upon a number of factors, in-cluding the equipment weight and floor response spectrum at the mounting location.
This information had not been compiled prior to the inspection walk-down; hence, the checklist presents no judgments as to the adequacy of exist-ing anchorages.
Thii issue will be verified by calculations and covered by Interim Report 2.
Design modifications are being prepared for items with no positive anchorage.
TABLE I EQUIPMENT CHECKLIST I tern Positive Type of Attachment Number For Number Equl1>111ent ID Anchorage Anchorag_e 5 Non-Category I ltem2 Comments A. i.1 Diesel Generators Hain Skids 1-1 & 1-2 Yes BTCS 5 and 6 A.1.2 Diesel Generator Control Panel
' G201 Yes BTE 5 and 6 A.1.3 Diesel Generator Control Panel 621 1 Yes BTE 5 and 6 A.1.4 Stat I c Exe I te rs C22 & C26 No 5
A.1. 5 Air Tanks Yes BTCS 5
A.1.6 Fuel 011 Day Tanks Yes BTCS A.2.1 2400V Busses 1-C & 1-D Yes WTEC 4 for 1-C, 9 for 1-D A.2.2 Relay Test Panels C18 & CIBA Yes BTE 4
A.2.3 Relay Test Panels C19,& C19A
- Yes BTE 9
A.3.1 2400V Station Power Transformer Xii Yes WTEC 12 A.3.2 2400V Station Power Transformer X12 No 12 A.4 48ov Busses Bil & B12 No 12 A.5 48ov Motor Control Centers 801 & B02 Yes WTEC 13 A.6 Stat I on Batter I e's #1 and #2 DOI & D02 Yes BTCS 10 A.7 Battery Chargers No. 1,2,3. & "
D15, D16 Yes BTCS 13 D17, Df8 A.83 Inverters No, 1,2,J, & "
D06, Do7 Yes BTCS 13 DOS, D09 A.9 DC -Bus*ses and DC Distribution Panels DIO, Dll Yes BTCS 13 D20, D21 A.103 Preferred A.C. Busses No. 1,2,3, & "
YlO, Y20 Yes BTCS 13 I
Y30, Y40 A.11 Bypass Regulator, YOI Buss & lnstru-X21 and Yes BTCS 13 Instrument AC Transformers X22 A.12 480V Motor Control Centers BO] & BOS No 7
Item Number A.13.1 A.13.2 A.1'4.1 A.1'4.2 A.1'4.3 A.15 8.1.1 8.1.2 e.1.3 8.1.'4 8.1.5 8.1..6
- 8. I. 7 8.1.8 B. J. 9
- 8. I. 10
- 8. I. 11 8.1.12
- 8. I. 13 B. 1.1 '4 8.1.15
- 8. I. 16 8.1. 17 8.1.18 8.1.19
- 8. 2. 1 8.2.2 8.3
- 8. '4
- 8. 5.1 B.5.2 8.5.3 Eauloment Dressurlzer Heater Transformers No. 15 & 16 Load Center Susses No. 15 & 16 Data Logger Batteries Chargers Inverters Control Rod Drive Transformers Control Room Panel Control Room Panel Control Room Panel Control Room Panel Control Room 'Panel Control Room Panel Control Room *Panel Control Room.Panel Control Room Panel Control Room Panel(Reactor Drive Cal lb. Cab.)
Control Room Panel (Noise Analyzer)
DELETED Control Room Panel Control Room Panel (Feed Water Purl ty)
Control Room Panel Control Room Panel Control Room Pane.I Control Room Panel Control Room Panel Alternate Shutdown Panel Alternate Shutdown Panel Speed Control for P55A Charging pump Air Compressor Panel Diesel Fire Pump Control Panel Diesel Fire Pump Control Panel Diesel Fire Pump Batteries ID X15, X16 D20'4 D206, D207 Y210, Y220 xi.5, xi.6 COi C03 C02 C13 Cll Cl2 Coli C06 CO]
C27 Cll 5 SP-'4 C106 C126 C125 C51 C302 CH ci.o Cl]
C35 C37 C137 D36, D38 TABLE Positive Anchoraqe No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No Type of Anchoraqe 5 BTCS BTCS BTCS BTCW BTCS BTCS BTCS
.BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCS BTCW BTE4 Comments Attachment Number Non-Cateaory 1 I tem 2
~.:...;..;:;;::.~~~~~~~~~~~~~~~~~~
1 2
9 9
1'4 19 19 19 20 20 21 22 23 23 2'4 2'4 25 25 7
7 16 15 18
TABLE I Item Positive
!~~~o~:ae 5 Attachment Nwnber 2
Number Eauloment ID Anchoraae Non-Cateaorv 1 Item C011111ents B.6.1 Hydrogen Recomblner Power Panels C122, C123 Yes BT,CS 11 B.6.2 Hydrogen Recomblner Control Panels C121, C124 Yes BTCS & BTC\\il 11 B. 7.
DELETED 8.8 Con Itel 2100 Computer Cabinet C09 Yes BTCS 13 B.9 Control Room HV~C Panel Yes BTCW 8
- e B.10 Rod Drive Control Logic and Contactor Panel C15 Yes BTCS 13
- 8. 11. 1 Fire Hod. Panel In Battery Rm 1 Yes BTCW 10 B.11.2 Fire Hod. Panel In Battery Rm 2 Yes BTBW 10 B.12 Sample Station C101 Yes BTCS 27 B. 13 Sample Station C1D6 Yes BTCS 27 C.1 Refueling Disconnect Panel Yes*
BTCS 3
C.2.1 Cable Trays Above Buss 1-C Yes BTCS 4
C.2.2 Cable Trays at Tunnel Cableway Yes BTCW 26 c.2.3 Cable Trays at North Penetration Yes BTCW (outs I de cont a I nme.rit)
C.2.4 Cable Trays over Cable Spreading Rm
'Yes BTCS C.2.5 Cab le Trays at North Penetration (Inside containment)
Yes BTCW C.2.6 Cab le Trays at North Penetration e
(Inside containment)
Yes BTCW, & BTCS C.2.7 Cable Trays at S.W. Penetration (Inside containment)
Yes BTCS C.J.1 Terminal Board Near 1-D J9401 Yes BTCW C.3.2 Terminal Board Near 1-D JL275 Yes BTCW
TABLE I Item Positive Number Eauloment ID Anchoraae c.3.3 Terminal Board Near 1-D jL274 Yes C.J.4 Terminal Board Data logger Bypass Swl tch Yes C.3.5 Noah Tank Piping Prot. Panels Cl 45, C146 Yes C.3.6 Power Available light Boxes Yes c.3.7 Terminal Board TCAC2 Yes C.3.8 Terminal Board.at Load Centers Yes 15 & 16 SCR Control Notes:
I. One attached to Generator 1-1 and one.to Generator 1-2.
- 2. Blank In this column.Indicates no non-category I Items In vicinity.
- 3. Items A.8 and A.lo In same cabinet (Inverter No. 1 with Buss No.* I., etc)
- 4. Bolted to Hotor Control Center 4.
- 5. Abbreviations used to descdbe type. of anchorages as fol lows:
BTE
= Bolted to Equipment WTEC
= Welded to Embedded Channel.
BTCW
=Bolted to Concrete Wall BTCS
= Bolted to Concrete Slab BTBW
=Bolted *to Bio.ck Wall Type of Attachment Number 2 Anchoraae5 Non-Cateaorv I Item Comments BTCW BTCW BTCW 11 BTCW 11 e
BTCW BTE 2
l Category I Non-Category I Equipment Type & ID #
Equipment Type Pressurizer Fan Heater Transformer X15 & X16 II Fi I e Cabinet
~
Attachment I
.Non-Category I Equipment Off set Dist.
(ft) 1 ' from X16 6" from X16 Positive Anchorage (yes/no)
No No
I Category I Equipment Type Load Center Buss es 15 & 16 Term Ina 1 Box at Load Center Buss es 15 & 16 Non-Category I
& ID#
Equipment Type.
Ducts (Same As Above)
Non-Category I Equipment Off set Dist.
(ft) 31 Up Positive Anchorage (yes/no)
Yes I
I Category I I Equipment Type & ID #
Refue Ii ng Disconnect Panel Non-Category I Equipment Type Refue Ii ng Platform Non~Category I Equipment Off set Dist.
(ft) 6' Positive Anchorage (yes/no)
No I
Non-Category I Equ.lp~ent Category I Non-Category I Offset *DI st.
Positive AnchoraQe Equipment & ID#
Equipment Type (ft)
( ye~/no) 2400V Terminal Box a* Up Yes Buss 1-C 4 x 2-1/2 x 1 1/2 2400V Heating Steam Duct a* Up Yes Buss 1-C 1 I dla.
3' Off Relay Test Pane 1 C18 & CIBA (Saine As Above)
Cable Trays Above Buss 1-C.
(Same;As Above)
I
Category I Equipment Type & ID II Static Exe i ters C22 & C26 Air Tanks Diesel Generators 1-1 and 1-2 Diesel Generator.
Control Panels G20 & G21 Non-Category I Equipment Type 3' dla.* Damper (Same As Above)
(Same As Above)
(Same As Above)
Non-Category I Equipment Off set Di st.
(ft) 3' Up 3' Off Positive Anchorage (yes/no)
Yes I
Category I Equipment & ID #
Diesel Generators 1-1 and 1-2 Diesel Generator Control Panels
- G20 and G21 Non-Category 1 **
Equipment Type 41 dia. Vent Fan (Same As Above}
Attachement 6 Non~Category I Equipment Offset DI st.
(ft) 1 I Up Positive Anchoraqe (yes/no)
Yes
Category I Non-Category I Equipment & ID #
Equipment Type A 1 ternate Air Duct
- Shutdown C33 and C4o 48ov
~cc 7 & 8
{807,808)
(Same As Above)
Non-Category I Equipment Offset Dist.
(ft) 2' Up 3' Off Positive AnchoraQe (yes/no)
Yes i
Category I Non-Category I Equipment & ID #
Equipment Type Control Room Air Filter HVAC Panel
/
Non-Category I Equipment Offset Dist.
(ft) 3' Up I
Positive Anchoraqe (yes/no)
Yes I
. Non-Category I Equipment Category I Non-Category. I Off set 0 Is t.
Positive Anchoraqe Equipment & ID #
Equipment Type (ft)
(yes/no) 2400V Duct 3* Up Yes Buss 1-0 2400V Buss 1-0 Lights
. 3
- Up Yes (Chain) 2400V Dry Bulb 10 1 Away No (Rollers)
Buss 1-0 Sensors 2400V Oo11y 10 1 Away No (Ro 11 ers)
Buss 1-0 2400V Cabinet o*
Yes Buss 1-0 3611W x 78 11H x 21 110 (Bo1 ted to 1-0)
Relay Test Panels (Same As Above)
C19 & C19A I
Chargers (Same As,*Above) 006 & 007 Inverters (Same As Above)
Y210 & Y220 I
Category I Equipment & ID #
Station Batteries DOl & D02 Fire Hod. Panel In Battery Rooms 1 & 2 Non-Category I Equipment Type Ducts (Same as above) O Non~Category I Equipment Offset Dist.
(ft).
5* Up Positive AnchoraQe
- (yes/no)
Yes I
Category I Equipment & ID #
Hydrogen Recomblner Power Panels Hydrogen Recomblner Control Panels Hydrogen Recomblner Control Panels Noah Tank Piping Prot. Panels Clli5 and Clli6 Power Ava 11 ab le Light Boxes Non-Category I Equl pment Type Planks Scafolding Piping Sprinklers?
Portable Holst (Same as above)
(Same as above) 1 Non-Category I Equipment Offset Dist.
(ft) 6 1* Up
. 6' Up Positive AnchoraQe (yes/no)
Yes Yes No (Roi I ers)
Category I Non-Category I Equipment & ID #
Equipment Type 24oov to 48ov Dutt Power Trnsf.
Kl 1 andX12 48ov LI ghts Buss es Bll and B12 2
~on-Category I Equipment Offset Dist.
(ft) o* Up 2' Off o* Up 2' Off Positive Anchoraqe-(yes/no)
Yes Yes
~
Category I Equipment & ID #
480V Motor Control Centers 801 & 802 480V Motor Control Center:s 801 & 802
~attery Chargers No. 1
- 2. 3. & 4 Inverters No. 1
- 2. 3. & 4 DC 8usses and DC D I s t r I but I on Panels Preferred AC 8usses No. 1,2,3, & 4 Con Itel 2100 Computer Cablne~
Rod Drive Control Log I
~nd Contactor Panel Cl 5 Non-Category I Equipment Type Duct Portable Hoist (Same as above}
(Satrie as above}
(Same as above)
(Same as above)
(Same as above (Same as above} 3 Non-Category I Equipment Offset Dist.
(ft) 2' Up I
Positive Anchoraqe
( y.es/no)
Yes No.(Rollers)
I Category I I Equipment Type & ID #
Control Rod Drive Transf.. X45 & X46 Non-Category I Equipment Type Duct 4 Non-Category.I Equipment Off set Di st.
(ft}
. 12.
Positive Anchorage (yes/no)
Yes I
I
I Category I Equipment Type & ID II Fire Pump Control Panel C137 Fire Pump Control Panel C137 Fire Pump Control Panel C137 Non-Category I Equipment Type Lights front & back Fire System Pipe J 811 di a. 5 Non-Category I Equipment Off set Dist.
(ft) 3' Offset 12 1 Up above floor 8' Above Control I er Steam & Conden~ate Lines JO' Above Controller Positive Anchorage (yes/no)
Yes (Chain)
Yes Yes I
Category I Equipment Type & ID H FI re Pump Control Panel CH Non-Category I Equipment Type.
Condenser :6
~o~-Category I Equipment Off set Di st.
(ft) 51 Above Panel Water Pipe non-Cr it Serv-Hdr.
i I
I r, Ii.
Positive Anchorage
.. (yes/no)
Yes
- e I
t Category I Non-Category I Equipment Type & 1.D II Equipment Type VOID - This Attachment Numbe Was Not Used.
- . 7 Non-Category I Equipment Off set Di st.
(ft)
I I
I Positive Anchorage (yes/no)
I
. Attachment 18 Non-Category I Equipment Category I Non-Category I Off set Dist.
Positive Anchorage Equipment Type & ID #
Equipment Type (ft)
(yes/no)
Fire Pump Cable Tray 18 1 + Overhead Yes Battery Tray 036 511 x l 211 w Fire Pump
. Light Fixt4re 12' Overhead Yes (chain)
Battery 038
I Category I I Equipment Type Control Rm Panels COi; C02, C03 Control Rm Panels COl, C02, C03 Control Rm Panels
- COl, C02, C03 Non-Category I
& ID #
Equipment Type Desk Chai rs *
(Roi I ers)
Bookcase (Rollers) 9 Non-Category I Equipment
. Offset Di st.
(ft) 8 1 -10 1 8 1 -:10 1 8 1 -10 1 Positive Anchorage (yes/no)
No No No I
Attachment 20 Non-Category I Equipment I Category I Non-Category I Off set Dist.
Positive Anchorage Equipment Type & ID II Equipment Type
{ft)
(yes/no)
Control Rm Panel Teletype 5'
No C04, C06 II Tools 5'
No I
I Category I I Equipment Type & ID u Cont ro I Rm Panel C27 (Reactor Drive Cal ib. Cabinet)
Non-Category I Equipment Type Lights I 1 Non-Category I Equipment Off set Di st.
(ft) 1' Up 3' Off set Positiye Anchorage (yes/no)
Yes
I Category I Equipment Type & ID #
I Control Rm Panel Noise Analyzer Control Rm Panel Noise Analyzer II
~
- Non-Category I Equipment Type Light Teletype Instrument Rack
.. 2 Non-Category I Equipment Off set Dist.
(ft) 4' Up Adjacent Adjacent Positive Anchorage.
(yes/no)
Yes No No (Ro 11 ers)
I Category I Non-Category I Equipment Type & ID #
Equipment Type Control Rm Panels Supply Cabinet Cl 15 and SP-4 (Feed Water Purity)
Control Rm Panels C115 and SP-4 Lights (Feed Water Purity)
Control Rm Panels C 115 & SP-4 Vent Ducts *
(Feed Water Purity)
-* 3 Non-Category I Equ i pnient Off set Dist.
(ft) 2' 2 l/2i Up 2 1/2 1 Up I
Positive Anchorage (yes/no)
No Yes (Chain)
Yes
! Category I I Equipment Type & ID #
Control Rm Panels C106 and C126 Control Rm Panels C106 and C126 Control Rm Panels C106 and C126 Control Rm Panels C106 and C126 I-Non-Category I Equipment Type 2 Fi le Cabinets Lights Ducts Teletype Adjacent to 106 4 Non-Category I Equipment Offset Di st.
(ft) 4-1/2' Offset 3' Up 3' Up Adjacent Positive Anchorage (yes/no)
No Yes (Chain)
Yes No
I Category I I Equipment Type & ID #
Control Rm.Panels CSl and C302 r-Non-Category I Equipment Type Fi le Cabinet 5 Non-Category I Equipment Off set Dist.
(ft) 2' Positive Anchorage (yes/no)
No
Category I Non-Category I Equipment Type & ID #
Equipment Type Tunnel Lights Cableway 6 Non-Category I Equipment Off set Dist.
(ft)
. 2
- Off I I Up Positive Anchorage (yes/no)
Yes
~
I Category I Non-Category l Equipment Type & ID N Equipment Type Sample Stations Gas Bott I e CIOI, CI06 21 Ta 11, 8" dla.
-* 7 Non-Category I Equipment Off set Dist.
(ft) 3' I
I I
Positive Anchorage (yes/no)
Yes (Chain to Wal I)