APPENDIX A Notice of Yiplati on Niagara mohawk Power Corporation License No.

DPR-63 Docket No. 50-220 Based on the results of an NRC inspection conducted on February 9-13 and 24-27,

1981, and in accordance with the Interim Enforcement Policy, 45 FR 66754 (October 7, 1980), the following violation was identified:

Section 3.2.9 of the Environmental Technical Specifications (ETS) specifies that the environmental radiation monitoring program specified in Table 3.2-1 shall be conducted.

Table 3.2-1 of the ETS requires that airborne I-131 be analyzed weekly at the required stations'ontrary to the above, airborne I-131 was not adequately monitored at 11 of 15 stations for an extended period of time including the date of sample station inspection, in that some of the air from the sample stream bypassed the charcoal sample cartridges due to lack of sealing gaskets in the cartridge holders.

This is a Severity Level V Violation (Supplement I).

Si072i0340 Si0706 PDR ADOCK 05000220 6