~ t; 0

REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:8008120538 DOC ~ DATE: 80/08/05 NOTARIZED; NO DOCKET FACIL:50-010 Nine Mile Point Nuclear, St'ationE Unit 2F Niagara Moha 05000410 AUTH. NAME AUTHOR AFFILIATION RHODEPG.K. Niagara Mohawk Power Corp.

RECIP ~ NAME RECIPIENT AFFILIATION

SUBJECT:

Final deficiency rept re environ L seismic qualifications of electrica) equipment. During avdit of steam supply sysg found. qualification documentation in wrong filch Steam supply sys will be modified to cross-ref records.

DISTRI8UTION CODE: SOI9S COPIES RECEIVED:LTR J ENCL TITLE: Construction Deficiency Report (10CFR50 ~ 55E) j SIZE:

NOTES'EC IP IENT C,OP IES RECIP IENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL ACTION:" A/D LICENSNG 21 1 1 YOUNGBLOODFB 15 1 1 RUSHBROOKPM ~ 20 1 1 KIPER E K. 14 1 1 INTERNAL: AD/RCI/IE 1 1 AEOD 1 1 D/DIR HUM FAC S 1 DIREHUM FAC SFY 1 1

/

EDO L STAFF 07 1 1 EQUIP QUAL BR16 1 1 IEE 05 2 2 LIC QUAL BR 1 1 MPA 08 1 1 NRC PDR 02 1 1 OELD QA BR, RUTHERFORD F W ~

23 10 IE 1

1 1

1 1

PROC/TST REV BR S

G FI S

01 EV 11 1

1 1

1 1

1 "EXTERNAL: ACRS 2P 16 16 LPDR 03 1 1 NSIC 00 1 1 Aug 15 t980 TOTAL NUN8ER OF COPIES REQUIRED: LTTR 39 ENCL 39

. lt

~ ~

e "I ~

I

  • IP I' g

,i i

I Il Ii

NIAGARA MOHAWK POWER CORPORATION/300 ERIE BOULEVARD WEST, SYRACUSE, N.Y. 13202/TELEPHONE (315) 474-1511 August 5, 1980 Office of Inspection and Enforcement Region I Attention: Mr. R. T. Carlson Reactor Construction and Engineering Support Branch U.S. Nuclear Regulato'ry Commission 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Carlson:

Re: Nine Mile Point Unit 2 Docket No. 50-410 On April 10, 1980, your staff was informed by -telephone of a potential reportable deficiency in accordance with 10CFR50.55(e). This deficiency concerns the environmental and seismic qualifications of some electrical equipment to be used at Nine Mile Point Unit 2. In accordance with paragraph 50.55(e)(3) of the Commission's Regulations, attached is a final report which provides a description of the deficiency, an analysis of the the corrective action taken. safety.'mplicationsand Very truly yours, NIAGARA M WK POWER CORPORATION c ..~.:

Gerald K./Rhode Vice President System Project Management PEF/kmb Attachment cc: Director of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C. 20555

FINAL REPORT t t'i tel . () f Qualification of Electrical E ui ment Descri tion of the Deficienc During an audit of our nuclear steam supply system Vendor conducted the week of March 26, 1980, no evidence (lack of documentation) was found to indicate that the three electrical instruments indicated below were adequately qualified: .

Instrument MPL No. Qualification Lackin Conductivity Element E12-N001 Environmental and Seismic Level Transmitter E12-N008 Environmental and Seismic Rosemount Model 1151DP E12-N058 Environmental Test Differential Pressure Incomplete Transmitter II. Subse uent Findin s and Corrective Action As indicated in our interim report dated May 12, 1980 for the Rosemount Model 1151DP differential pressure transmitter, an additional search of

'he qualification records following the audit located the qualification documentation in another record file. To prevent the recurrence of being unable to retrieve documentation in a timely manner, the nuclear steam supply system Vendor's Quality Assurance Program is being modified to cross-reference qualification records and vendor-supplied documentation.

Regarding conductivity element E12-N001 and level transmitter E12-N008, it has been determined that no corrective action is required. These instruments are considered to be passive and are not required to function either during or after a design basis accident. Since a failure analysis shows that an electrical short circuit or open circuit in the instrument can damage the power source, no additional qualification is required.

III. Anal ses of the Safet Im lications The electrical instruments have been shown to be adequately qualified to satisfy their intended design function. Therefore, this condition could not have adversely affected the safety of operation of Nine Mile Point Unit 2 at anytime throughout its expected lifetime.