Text
TWO NORTH NINTH STREET, ALLENTOWN, PA.
18101 PHONE: (215) 821-5151 NORMANW. CUIITIS Vice President. Engineering 8 Construction 821-538 t May 20, 1981 Mr. B.J.
Youngblood, Chief Licensing Branch No.
1 U.S. Nuclear Regulatory Commission Washington, D.C.
20555 Susquehanna Steam Electric Station SER Issue No. 21, 22, 23, 24 ER100450 File 841-2 PLA-796 Docket Nos 50-387 and 50-388
Dear Mr. Youngblood:
The" NRC Material Engineering Branch is an April,l, 1981 Working meeting with the BWR-Licensing Review Group defined the necessary and sufficient action to review NTOL plants that pre-date 10 CFR 50, Appendices G
and H.
The enclosed data provides the basis for that review of Susquehanna and closure of SER issues 21, 22, 23, and 24.
Very truly yours, N.W. Curtis Vice President-Engineering 8 Construction-Nuclear CC:
R.M. Stark
.8 10.528035%
Table 1 - Sus uehanna l Beltline Plate Tou hness Data SA-533 Grade B, Class 1 Plate - Lukens Steel Co.)
Char V-Notch Tou hness (To /Bottom)
Plate Heat 0-Slab 8
Dropweight NDT (Top/Bottom) 0F Orientation (L or T)
Charpy Test Temp.
0F Energy Ft.-Lb.
Lat. Expansion Hi 1s
% Shear
~wer Shell 21-1 21-2 B5083-1 C0770-2
- 10
- 30
+ 10
+10 61,64,45/44,74,5 38,46,50/45,56,3
/
73,82,78/92,106, 65,61,60/78,72,7 99 40,40,40/50,50,50 60,60,60/70,70,70 21-3 C0814-2
- 30
+10 110,108,120/86, 84,91 80,81,85/63,62,6 80,80,80/60,60,60 iwer Int.
gael 1 22-1 22-2 22-3 C0803-1 C0776-1 C2433-l~
- 10
- 10
-50/-50
+10
+10
+10 81,56,66/78,73,6 66,53,56/29,63,5 37.,38,54/53,56,4 44,32,33/36,44,4 4,53,43/34,31,3 44,36,44/33,31,3 40,40,40/40,40,40 40,40,40/40,40,40 40,40,40/30,30,
~. This m terial is al surveillance progra o in the react r vessel
Table 2 - Sus uehanna 1
Beltline Meld Toughness Data (Shielded Metal Arc Melds)
Post Meld 1150 F for 50 Hr. T ical Char Tou ness Weld Seam Type Heat ¹ Lot ¹ or Flux ¹ Drop-weight NDT QF Charpy Temp.'F Charpy Energy Ft.-lbs.
Lat. Expan-"
sion Nils
% Shear tD O tt$ U U
CP r r
~r tt$
5-tD t/lU 0 5-O
~r I
~
+) =
t U
C U
~r t/l Ul CPVl o5 5-VP Q U O CP
~
Ql CP r
tt$ Vl O
~r 5-M tD tD 0
)e U
~
QP O Vl tt$
tt$
~t 5
CP M 5-O tD tD 3:r CP Vl tt$ ~
'r 5-QP 5Q rt$ tt-E tt$
UW r
tt$
CP U
~
Vl Vl tD CP M O UU I Mr O.
0 O 4 C CP N't-t/l
tt$ ~r
~t r
s CP CPCM U
~t
'U
~ tt E
OCP0 E8010G (Trade
- Name, Atom Arc 8018 NM) 40150371 629616 402K9171 411L3071 494 K2351 402C4371 412P3611
- These mater surveillanc NA= Not Availa B504B27AE L320A27AG K315A27AE*
- 80
- 70
- 70 L311A27AF*
- 70 L307A27AD C115A27A J417B27AF
- 80
- 80 als are also in the reactor v
program.
le
- 20
+10
- 108:.
- 70
- 20
+ 10
+ 40
+ 130
- 108
- 70
- 30
+ 10
+ 40
+ 130
+ 10
+10
- 20 ssel 57,58,62 51,52 5,6 8,13,17 26,34 58,58 80,106 128,135,140 6,6 8,11,13 36,40 51,67 90,100 124,126,129 87,96 82,84,92 52,65,69 5,3 9,13,16 25,32.
52,52 50,67 93,91,86 5,4 9,11,14 21.27 39,54 61,71 94,88,99 NA NA NA 15,1O,1O 25,25 50,50 40,60 100,100,100 5,5 12,8,10 30,30 50,60 80,70 100,100,100 NA
Tbl 3-~Sh 1
Beltline Plate 5 Weld RTNDT Estimates (Peak End-of-Life, EOL, fluence
= 1.4 x 101 n/cm2.
(>1 Nev.) at 1/4 T wall from vessel ID)
Ht.
Wt.
/o Cn A.
Plates - beltline Wt.
P Y1006A006
"'Start RTNDT (~ F )
Reg.
Guide 1.99 Extrap.
RTNDT (o F)
Estimated EOL NDT B5083-1 C0770-2 C0814-2 C0803-1 C0776-1 C2433-1*
0.14
- 0. 14 0.13 0.09 0.12 0.10
'.010
- 0. 008
- 0. 011 0.009 0.010 0.009
- 20 20
- 10
+ 6
+18 41 37 39 21 34 24
+33
+17
+19
+11
.+40
+42 (Limitin Plate)
Ht./Lot Wt.
X C.u B.
Welds - beltline
. Wt.
"P Y1006A006 Start NDT Reg.
Guide 1.99 Extrap.
RTNDT (')
Estimated EQL RTNDT (o F) 401 50371/B504B27AE 629616/L320A27AG 402 K9171/K315A27AE*
411L3071/L311A27AF*
0.03 0.04 0.03 0.03 0.013 0.015 0.015 0.016
-80
-50
-50
-50 28 28 30
-56
-22
-22
-20 (limiting field) 494K2351/L307A27AD 0.04 402C4371/Cll5A27A 0.02 412P3611/J417827AF
- 0. 03
.0. 015 0.009 0.016
-50
-50
-80 28 17 30
-22
-33
-50 These materials are also in the, reactor vessel surveillance program.
'hl(. a,<o ilri',~
Ec Iron Co ~
I's
~
'~. i" 4i;:".ia, L';.).a r Chica,",o Bridqo 1 Iron Co.
.;o) la~,
(U.a
~
~
~
~
CD.'
9"-1 Rev.
10 1970
~u.=-,ur l970 Addenda and
',(e I:ore:iy certify that we have cept
) "ra.
L<.v
',i L;r. 3 Claoa l ec,
.'-..".er t g 101-73.
I/
0...
TEST CERTIFICATE
~
~
3lpiip 1 l 3g "I'Iect 7 Kz 5l973 D<)
I cor..plied with all the rcqul.renento of A~I('ode 'ect.
3 1jvU Edition incl.
c 2433 16 l.33 039 I
I I
(<<,',
4'<<(g p
C H E t<'I I C A L 5
cu r<'mi 015 23 63 A N A L Y S I S HO
.57 a
Qr'aha
'pico I-8 y.r,p. Stec3, I
I I
I PHYSICAL PROPERT<E Lon~.
.. V-sot.=n +10'F.-
~ 43-I Lateral Expansion in Inches
,044 I.o36 I.o44
..033
.031 i.030 54@
Y>ccb
'('",'<O MO kS <.
rCuuCC g (.(.oVg, Kri'.
C 2433 ~
654-861" 666: BQ9 24"
- 23 I
TOT. OF Pl XT DFGP QYIGIiT TEmN~ITX4N CURVE
(
R CULTS
. I
-"..3'l'.
Ão Ereak
-IIO'F.
2 5o ieeak pgtF Break C0
-tA'F.
Break "cd F'(roak ff.D.T. is 50'Fo ill he ~t t~ ( n t--.nt re r bp.cificetion Shoe
~
" ('
+>>>>I>>>>I ~ a'
'<>>A
~
~ - ~ '1-"tl.;; y a= n" t. @err.or=.cd op. VJKM~
I I
I t
F 101-73.I
~
~ '
~
(<I ~
< (
< ((Ip ~ Qg
< i' 'II
~
~
~ ~ ~
~ << ~ <<
< ((I)
~
( (I<~I g<(eI<<<<y I
(
I I
I S iruc t,uro Appears:leo.
~near 0&0-40
. 3.-
30-30-30 I <Pl <oN 6--,/16" x l~g x 326 I
I.'0'I fGI!
i)RGP MiIUIi<T L~iu.
-20'F, j
" -Iio'F, vp y<
Op, HoD.X.
OF FL%TE
'lR&,I(;~ITIOUS Cl,RVK Bi~ULTS Ho Break 2 lIo LIraak LXCQk drouk
- Qreak, is -5O'y.
r 5
~ '
~
~I
~
1+ I>>Pt I ~
I
Ill(g Q g p~
33039-1 310'(V-1 t ~ f)
'.".<<=C Loc.-.t:>> on:
Bend
-."p 1-'ic'."le
- Tr=~ovcroc Tens ions
- "c:
('c 'o".Ccz - ~anovcroc Impacts
'.:..'o tc.-.. - L n,",it 'inal Tests 1/4T fr=:-. -o':1- '
rfacc
".~ c'"
CI "..". "T" "-C.-..
L.l cached c; t"-".'"ed cdv>
Fino Grain Practice V.I.P. Steel Baoic Proccos:
Elect,r3.c
.'-'urncce I.'""h".sic((1 Pron(rty R q"uk'(: ( -..,c.s.
5".c
! fication:
SA-53'r.
9 CL-1
~r. c<oure V.-ocl C silty
! ~-1 1'..'v.
10 D3 1 "/9/70
("..e:~:
>>:.".v. 6)
- 'a~co:
husten1tixed at l~+
held ll? hr,/>
Terapered a,t
/~<<< held 1/~."."./'::- i Stress 3.el /evecf <<t /OS 4"+
held l h=.
n"h ~in.,
a ~atcr qu nchcd.
~ ~ J
~ ( ~ p
(
~ 3 ~ C
-.'v'L
~ f
~>>('(3 ~
( ~.
~
(.. (~ ~ 1 k air cooled.
LB-'3"'cv.
8 DTD 10/4/71
'rotc - A.'.1 i".:.:pcrct "eo ohoi:n belcic arc ac ual.
Tc nolle; Y1cld:
l.",".::c':
Grain Slr.e:
GO/lOO,OOO PSZ V.in...".; 0l font
'J ft. lbs.F10 'F, Lit. r.:1 ';"noicn X " "'>ca-.
i'ra'ore.or inforr.:at>>on only.
Final Plate Grain Si=>>. f/> or finer deter:.".incd on p.
fully 1 cat tre...'d t<<ot coupon,
~
(
(
(
~
th:n cut fr,. plate, aS SCress relieved at
/ ~
1"..'J 50 hro.
- 8. f r..."."e cc.l';1 o belo~ C"'3 r".
t.".c.". am cooled.
o HaX.
31eatf.isa l~ate R 1 0 (7tl7, Nzx. Cooll33 Ra.te
.Ra CeA'>>r, 100 1-.
+(,
~
f
( ~ ( '
~ ((>>'~
<<(I c<':r. '>>~ c.',r
~.
fg(jp gn
(
)( ', ',
t
((s rnpan.
~ ~ '(J
))( ~
C ~
t$ ~ / I i") e+
1((
~ t(
"rr"-:~"""'
'.r"-'>"rr'd e tc>>'l
-.~I- ~~@K
.( 1'(
Table 5 SA-533 Grade B, Class 1 Plate Tou hness Data Base Includina U
er Shelf Vendor - Lukens Steel Co.)
Plant A
La Salle 1, Combustion En ineerin
)
Heat No.
NDT (F)
Charpy Temp. Orient (oF)
(L or T)
Energy (Ft.-lbs.)
Lateral Expansion (mils) 4 X Shear C5978-1
+10
-40
+10
+40
+110
+160 7.0,7.0,11.0 5.0,33.0,30.0 3.0,48.0,48.0 18.0,116.0,109.0 23.0,136.0,136.0 5,3,7 23,25,23 40,35,36 79,76,74 82,84,84 0;0,0 10,10,10 20,20,20 80,80,80 90,95,95 C5978-2
-40.
+10
+40
+110
+160 22.0,24.0,24.0 49.0,46.0,42.0 62.0,60.0,41.0 98.0,90.0,100.0 119.0,120.0,118.
17,18,19 38,36,33 46,44,34 73,67,75 88,86,82 0,0,0 25,25,25 35,35,25 80,70,80 99,100,100 C5979-1
-10
-40
+10
+40
+110
+116 9..0,11.0,19.0 61.0,57.0,43.0 73.0,92.0,65.0 117.0,116.0,100.
134 ',136.0,134.
5,7,13
. 45,41,32 51,63,43 78,76,68 87,86,85 0,0,0 30,30,20 35,45,35 80;80,70 99,99,100 C6345-1
-40
-80
-40
+10
+40
+110
+160 8,6 29,15,23 109,88,77 103,96,122 147,147 151,165 4 4 21,13,16 76,58,56 68,65,77 84,82 87,94 0,0 5,0,1 50,35,35 45,40,60 100,100 100,100 C6318-1
-20
-40
+10
+40
+110
+160 25,17,14 80,66,72 85,95,112 126,145,117 140,140,139 18,11,9 57,47,50 64,68,75 81,89,76 86,89,88 1,0,0 35,30,30 40,40,50 90,100,90 100,100,100
~ ~
~TBbl8 SA-533 Grade B, Class 1 Plate Tou hness Data Base, Includin U
er Shelf Vendor - Lukens Steel Co.
Plant A
La Salle 1, Combustion En ineerin
)
Heat No'.
('F)
Charpy Temp.
Orient (oF)
(L or T)
Energy (Ft.-lbs.)
Lateral Expansion (mils)
I Shear
\\
C6345-2 A5333-1
-40'80
-40
+10
+40
+110
+160
-40
+10
+40
+110
+160 10,12 32,16,49 93,94,67 109,125,128'27,165 153,161 21,13,11 56,67,53 82,100,84 126,120,133 155,155,145 7,9.
20,11,33 69,66,48 70,72,82 81,82 86,88 17,11,9 41,47,40
'6,70,60 87,81,84
-92,90,89 0,0 10,0,20 40;40,25 50,60,70 85;100
,100,100 5,0,0 20,30,20
'0,50,40 80,80,80 100,100,100 B0078-1
-10
-40
+10
+40
+110
+160 10,14,25 73,49,70 94,100,100 118,128,140 151,136,143 10,13,21 54,39,53 65,68,70 82,86,89 90,84,88 0,0,5 40,30,40 60,60,60 90,90,100 100,100,100 C6123-2
-80
-40
+10
+40
+110
+160 11,8 28,38,10 77,60,73 113,108,122 120,149 149,151 9,7 22,28,9 56,45,53 73,71,75 89,91 91,93 0,0 10,10,0 40,35,40 65,60,75 90,100 100,100
Table 5
A-533 Grade B, Class 1 Plate Tou hness Data Base, Includin U
er Shelf Vendor - Lukens Steel Co.
Plant A
La Salle 1
Combustion En ineerin Heat No.
('F)
Charpy Temp. Orient
( F)
(L or T)
Energy (Ft.-lbs.)
Lateral Expansion (mils)
X Shear C5987-1 C5987-2
-10
-40
+10
+40
+110
+160
-40
+10
+40
+110
+160 19,13,14 63,55,35 80,99,87 122,134,122 122,134,127 15.0,8.0,10.0 76.0,79.0,51.0 57.0,76.0,75.0 106.0,102.0,113 140.0,133.0,138 14,10,13 47,41,26 59,68,61 84,86,84 86,86,84 777 54,59,57 42,57,54 72,68,76 87,81,84 0,0,0 35,35,30 50,70,55 100,100,100 100,100,100 0,0,0 35,35,30-30,35,35 80,80,80, 100,100,100 C6003-2 C5996-2
-10
-10
~ g
-40
+10
+40
+110
+160
-80
-40
+10
+40
+110
+160 L'-
10,7.0,8.0 37.0,31.0,51.0 65.0,49.0,50.0 81.0,95.0,82.0 121.0,107.0,120 7.0,10.0 18.0,25.0,25.0 62.0,71.0,66.0 81.0,100.0,91.0 124.0,130.0 149.0,151.0 7,4,3 28,22,37 44,34,36 60,67,61 82,78,87 5,8 14,20,19 45,50,47 52,71,64 83,88 89,91 0,0,0 20,.20,30 35,30,30 60,70,60 100,99,100 0,0 10,10,10 20,30,25 35,50,40 90,90 100,100
~
~
<Ja 't Tabl e 5
-533 Grade B, Class 1 Plate
'ou hness Data Base, Includin U
er Shelf Vendor - Lukens Steel Co.
Q3 Plant A
La Salle 1 - Combustion En ineering Heat No.
NDT (F)
Charpy Temp.
(~F)
Orient (L or T)
Energy (Ft.-lbs.)
Lateral Expansion (mils)
% Shear C5979-2 C5996-1
-10
-10
-80
-40
+10
+40
+110
+160
-40
+10
+40
+110
+160 L.
8.0,11.0 28.0,17.0,18.0 64.0,63.0,49.0 72.0,76.0,79.0 107.0,102.0 134.0,141.0
- 12. 0,53. 0,12. 0
- 65. 0,60. 0,77. 0
- 88. 0,113. 0,78. 0 111.0,126.0,134.
146.0,148.0,143.
E 5,9 20,16,14 44,44,34 47,49,5Q 77,"74'9,83 10,20,11 46,42,54
. 56,70,54 74,85,83 86,89,86 0,0 15,10,10 30,30,20 35,35,35 88,80 100,100 0,15,0 30,30,40 40,60,40 80,90,90 100,100,10Q
~
~
fabl e SA-533 Grade B, Class 1 Pl ate
'Tou hness Data Base, Includin U
er Shelf
(Vendor - Lukens Steel Co.
21
"'Plant'A'a.'Salle 1
Combustion En ineerin Heat No.
(.'F).
Charpy Temp.
(. F) rient (L or T)
Energy (Ft.-lbs.)
Lateral xpansion (mils)
/ Shear
'C6318-1
-40
-10
+10
+40
+61
+120
+200 7.5.
32.5,31.0 41.5,42.0 31.5,60,49,63 70,71.0 95 100.0,91.0,90.0 5.0
. 27.0,28'5 36.0,37.0 26.0,44.0,34.0,49 57.2,57.5 70.5 75.0,63.5,69.5 5,5 25,25 35,30,40,40 59.,50 99 99,100,.100
~
~
Table 5
SA-533 Grade B
Class 1 Plate Tou hness Data Base Includin U
er Shelf Vendor - Lukens Steel Co.
22 Plant E
Ho e Creek 2 CBIN Heat No.
('F)
Charpy Temp
('F)
Orient (L or T)
Energy (Ft.-lbs.)
Lateral Expansion (oils)
X Shear C9533-2 0/10
-50 F
-30
-20
+10
+70
+100
+130
+212 9-7 7-12 9-14, 19-40 34-26,45-47 48-64,70-76 82-62,82-71 72-68,92-86 88-81,110-9 7-4, ll 7$
28-23, 48-40, 53-65, 60-57, 75-73, 7-4 5-30 36-35 57-60 63-61 72-69 87-81 10-10, 20-20, 40-40, 60-60, 60-60, 99-99, 20-20 30-30 40-40 60-60 80-80 99-99
-'40/-5
-"70
-50
-20
+10
+70
+100
+212 6-4 10-13 14-27 30-42 70-64 76-79
.106-108 20-20 23-14 29-39 56-54 64-63 66-81 10-10 20-20 30-30 40-40 60-60 90-90
-70
-40
-20
+10
+40
+70
+100
+130 5-7 12-12 36-45 35-46 48-56 79-81 90-110 114-11 16-18 30-36 29-34 47-49 74-,75 70-82 86-85'0-10 20-20 30-30 50'-50 70-70 80-80 99-99
Tabl e SA-533 Grade B
Class 1 Plate
Tou hness Data Base, Includin U
er Shelf Vendor - Lukens Steel Co.
23 Plant C
La Salle 2 - CBIN Heat No.
NDT (0 F)
Charpy Temp.
(F)
Orient (LorT)
Energy (ft.-lbs.)
Lateral Expansion
'I I Shear
.'C9481-1
-30
+40
+40 74,74,81 103,61,85 61,58,60 48,66,72 50,50,50 40,50,50 C9481-1
-40
+10
+25
+40
+51
+70
+93
+120
+200
- 17. 0 23.5,22.0 36.0
- 45. 0,35. 0,42. 0
- 40. 5
- 51. 0,50. 0 71.0
- 93. 0 93.5,100.0,93.0
- 15. 0 1.0,20.5
- 31. 0 42,0,34.2,38.0 35.0 44.5 42.5
- 58. 5 69.5 74.0,72.0,69.0 10,10 20-25 30-35,30,30-35 30 40,40 70 90-95 95,95,95
Tabl e SA-533 spade B, Class 1 Plate Tou hness Data Base, Includin U
er Shelf Vendor - Lukens Steel Co.
Plant D
Fermi 2 - Combustion En ineerin Heat No.
NDT (F)
Charpy Temp.
(F)
Orient (L or T)
Energy (Ft.-lbs.)
Later al Expansion (mils)
%%d Shear C4574-2
-30
-80
'-40
+10
+40
+110
+160 8.0,16.0 34.0,32.0,27.0 48.0,49.0,60.0 76.0,63.0,69 '
98.0,103.0 121.0,119.0 6,13 25,24,20 36,37,43 56,47,51 72,76 85,82 0,0 10,10,5 15,15,20 30,20,25 93,95 100,100 C4574-2
-20
+10
+40
+65
+102
+119
+201
+202
- 22. 0 32.0,35.0 50.0,52.5 64.0,55.0 75.0 108 ',88.0 112.5 108.5
- 17. 5
- 22. 5,27. 5 35.5,41.5 47.0,42.5 60.5 75.0,66.0 83.5 79.0 1
5,5 10,10 30,30 50 100,85 100 100
Tabl e 5
SA-533 Grade B
Class 1 Plate Tou hness Data Base, Includin U
er Shelf Vendor - Lukens Steel Co.
Plant B
Shoreham-Combustion En ineerin Meat No.
NDT (F)
Charpy Temp.
(F)
Orient (L or T Energy (Ft.-lbs.)
Lateral Expansion (mils)
I Shear C4882-1
-60
-80
-40
+10
+40
+110
+160 16.0,14.0 41.0,32.0,54.0 75.0,68.0,48.0 83.0,95.0,100.0 104. 0,116. 0 130.0,131.0 15,11
'8722~38 52,49,35 59,65,70 75,82 86,84 0,0 20,20,25 30,30,25 45;50,60
,85,90 100,100'4882-2
-40
-80
-40
+10
+40
+110
+160 10.0,7.0 46.0,43.0,30.0
- 75. 0,50.0,66.0 90.0,80.0,88.0 120.0,107.0 137.0,129.0 10,8 36,35,26 58,44,52 71,62,63 84,82 94,90 0,0 10,10,10 30,20,20 40,35,40 85,80 100,100
26 SA-533 Grade B, Class 1 Plate Tou hness Data Base,Includin U
er Shelf Vendor - Lukens Steel Co.
Plant B
Shoreham - Combustion En ineerin Heat No.
(.F)
Charpy Temp.
(F)
Orient (L or T)
Energy (Ft.-lbs)
Lateral Expansion (mils)
X Shear C4882 -80
-50
-30
+10
+39
+70
+121
+200 19.0 41.0,25.0,37.5 41.0,40.0 61.0,68.0 77.0,71.0 91.0,71.0 113.0 115.5,113.5 15.5 29.0,16.5-26.0 30.0,29.5 45.0,49.5 54.0,54 '
62 0 53'0
- 79. 0
- 82. 5,74. 0 20,10,20 20,20 30,30 50,30 7P',40 95 95,95
L~ ~ ~ ~ee- >~
~~ $ A svtsg u 8 a M~~ /
r
. I(>>~ee, u/e/Aroc,eg~w 7
( ~
~
4
>V Ge>Led%)
E:.Lac.t'.K.i.c CoTAphgy HUcLEAAf vFsM.Ls (c l a ss 1) p 8 Ltbgf~p.
1 Mh'cg r i g 1 PRCc Guy' S
3
--.-.- 3(7 22iqAD HrrEi~r.:.CE '>"'LIFIC>lI IL>>S I Genera1.
@PS 800 l.atest Revision
>'OLL ~.>n>.'.~~L>rIC>ii ~ <>.>
PRE'HEAT':::; j::::t.:::".";,:
o~
300'1= mini>>g>
lVQ.
I 61,6 f'OS! T IO:>
Tli!C8:.L.'
>>::.:O'L 3>t'1C" L() 8" 96?
6
~
POST HEAT TREA1'ht pz'yccluy'e qualified vi"1 50 hours5.787037e-4 days <br />0.0139 hours <br />8.267196e-5 weeks <br />1.9025e-5 months <br /> at: 1150'>
425'F/-50'F.
I P a s t b e 1 d
> e 0 C
- e. r e 3 t-..
. we) dmeTTt. shall be in: coo
<':..::c ~;
z CB.j i zpr roved procedure.
BASE METAL I
ASH SR-$ 33 Gr B
C 1 - "
1 or SA-5'08 Class 2
A ~~8 Group No.
Pl ZB SU&'.jrollp 1
I NTHRP ASS
~
~
1
~
"6'.'c(.".'0 0 P
LAWx i%~>
I
~ $
I ~
I 1
FIL L E R %ET AL,RSME 57ec L f I cat:on SFP -5. 5 Cl a~s ificayioa E8013-6 Analys is h-3(except, Ni 0. 50 to i.
Usual i l i ty F4 T'Yzde Name Al.)oy Roofs E801SNpf ELEC rRtcAL CftARACQE'RfSY7CS-D.C. Reverse PolarLty SH>iLPtNG SAS-BACKV7&AS fL.VX None
.-;,=-"L=ASco 2 5')
l%(
C>>l&I'>t-,s>>r.n
(
.4 q, 4'
~
D
~
\\
I I
t" 0
>. ~ >~,
~
> C,.
~
~
L j
~
~
~
'C g
w~ > Q Q
>I QP
LEASED FOR CBQ CONTRACTS ONTRACT NO.
OY DATE
/
cj'eneral Electric Comaanv PRODUCT ass A
DEscRIPTIDN Shie 1ded hie ta 1 Arc and Sub Ieraed Arc Weldin of ASNE P12B Sub rouo 1 hlaterial WELD PROCEDURE SPECI F ICATION Low Alloy Sfu' SA Grooves
& Buildup PROCE DURE WP S PAGENO.~OF~
DATE 7-6
">>~:
REFERENCE SPECIFICATIONS General WPS 800 Latest Revision General WPS 820 Latest Revision PROCEDURE QUALIFICATION POSITION 963(
W)
F(Sub Arc)
F,V, H (ShIA) 1261 (SW)
F (Sub Arc)
F,V (StlA)
THICKNESS RANGE 4 l/2" to 9.9" 2 3/4" to 8" FILLER METAL ASIDE See Adjacent Colu~
ELECTRICALCHARACTERISTICS See Adjacent Column SHIELDING GAS Non e BAGKUP GAs None POST HEAT TREATMENT Procedure qualified with 50;, hrs. at 1150'F +25'/-50'F.
Post weld heat treatment of the we 1 dmen t shall be in accordance with a CB&I approved procedure.
BASE METAL-ASHE SA-533 Gr B Class 1 or SA-508 Class 2
AS>1E Group No.
P12B Subgroup 1
P REHEAT PZQU IRZ!'iE:ITS:
hlinipum preheat of 300'F shall be applied uniformly to the full th'ckness of the weld joint and adjacent base material for a minimum'distance of "T" or 6",
whichever is least, where "T"
is the material thickness.
hfain ain preheat temperature until start of post weld heat treatment.
INTERPAS.
TEhfPEPDTURE REQUI REM
'PTS The interpass temperature shall not exceed 500'F maximum.
FILLER Yi:-TAL:
SubmercIed Arc Specification N.A.
Classification N.A.
Analysis A3 (except Ni 0.50 to 1.25)
I Usability - F6 Trade Name Adcom 1Nhi~l (1%
NickeI'r equal Shielded h'.etal Arc Specification SA-316 Classification E8018-G
, Analysis A3 (except Ni 0.50 to 1.25)
.Usability F4 Trade Name Alloy Rods E8018Nhf.
ELECTRICAL CHARACTERISTICS:
Linde 124 P/=~ ~8/2-iZ >
7'a 4/e.z -
E/ante//
j,*y//~ g,
//cl)'/inaSW~'py/.
oo I
oo f oo I oo I oo I vo I u>
I oo ENGS}ENGRIENGRIWEI.D}IN P
'} 0
}
NU
} NU nr ~
c.
r.
seqv~
1 C' f nn nr~ ~
REG~AEG REG I
REG MFG
} MFG CONST}CON5Tft nr
~ ~
~ Qh OY DATE
~,rs
~/c/r.'e I
Submerged Arc Tandem Wire Lead Wire -
DCRP
~
Trail Wire AC Single Wire DCRP
y,fP
$ >>.r
, ~
CHl~O DRXCCZ S ZWH CO VrELD PROCEDUpF Q ECIFICATIQ:g
~ Alloy Sp~
Croovas S, Bcigd">
~~o Ganaral Electric Cc~"..an
~OOvCT kelt!inc os,.~."
i3 '
crcun 1? ater?,al Arc PAVt w+%
<>>L>><<yt <<
5 5 '>>
~
~
P4
~
~
<<>>< r Qp>>
~
~ r
~
~
RfbfRI<.~ Srtrtf>CAT:~S Canoral RPS I)00 Latest Pavisicn Conaral IG 5 820 Latest Feviaicn to" OCR 0'JR E C'<<AltF >CAT <CH DOS'fT!CH 7H>CK)vfSS RARQX 1890 (Sr>)
1891 (SMD) l892 (S..h) 1893 (SA-1 2200 (S~-2f 8
G?I, F F
3/1 6 3/16 3/'
3/1 5" 3/1 6" to 8
to 8" to 8
Po 8
to 8
~ST l EAT TRINA.M$.%T-Proco"ura ~alifiod Mith 50 ):rs. at liKQ F +25 / 50PP ostveld boat
.".oa=:ont cf PLe Me P.-
.ent shalX he in acmr8anca vi"0 a C3Ll-approved procoduro
~
P $ T
'P f & ~ ~<<>><'P<)<<'5
?IinLwvw @recoat of 30 applied vskfowlv to t".ick~ess of t?;e ~old a")acont base r ateria d s>>tanco of T
c eve" 's 'ear L<"e-e
.-..aterr al t.".ickiness.
A ~ F tea r
c n
C P ~ 4 gP ha
~
a<<
a r gL P L
~
~
>> P c
P>>
'".til a art of p r~e."..ea=
<<lrc" <<0>>e..
a<<
s..c ll an>>
area sea.-..s
-"e.".eat;<<av Le Crcr-d c piig o e
aa c
4 0
{'e ~<<<>><<$ '
~ \\
SASK L4%TAt AS?iE SA-533 Cr 3 Class 1 o" SP-5LnB Class 2
k5.K Cr" ~ No. )'123 S'borough
'E not exceed 50"'F =rm=..~.
P Q>><
ted>>
~
~
~ v~ <>>
~
~
~L>>
<<P
~-e a.L,a. 1
~ ~~r J, ~
~ ~
PZ
~
~
Y~.P.
~ 0w
~<P
~ ~
P.N'olt'.cD ?iota'.
<~ c Spo<:S 'k<lo<l vi~A5 Cla~aificat'or. - E8018M Analysis A3 (oxcopt Wi 0.50 to1.2 Usali y - F4 Trade t:r=o - A lov bc& ES018VN Su~arced Arc CLECTRtCAL uIARACTKR~STICg-ae Ad)aeon Column.
Ia'iWC GAS-BacxL I CAS Hone PL.vx-'ndc 124
@vier c~kR ~nov AL Spkci icat
<I. <>>.
L".ai.rsis - h3 (except
)
l.. 25)
Vsahili"v - F&
J ra<<o Vaw C3P P<<Y'i or et; a'i 0.50 to
('i Ã:eke
)
mc-.~:CZ r.!ha.~c.=~:5-.:CS:
QiA XAP St MeracC P rc Tan@a~ T~iro lAad Piro C DC<>
Tra'1 Hire'f-hC Scnglo piro -
DC'Pe~~
Pan& a-8<lfi'<<e 7
/le'l/t
/p( p~ +8, ~~
0 C<<>>
l An Qu
>><<CIP J
~I
~ <<<>> f LL'a It,gyp<< ~ g~ RIP<<t gQ ~
Qg j l
lt>>I <<<(
~ >>
'<lip
~ ~
~
~ <<<'<
~ <
g(t:I>>
'<>> t
~<<<P
< ~ <
~
~
< ~ ~
'~>>>. rl? $ 3/f f~ ~<< r>>P 'J1 <~ ~ I J 4 p<hn j Tabl e 1Nt<H Electrode Trade Name Raco Linde 124 Flux, Submer ed Arc 30 Post Weld ll50'F for 50 hr. T ical Plant C La una Verde 2 CBIN Heat No. Flux No; NDT ('F) Charpy Temp S Ingl e (~ F) ~T~p)em SorT Energy (Ft. - lbs.) Lateral Expansion (mils) / Shear 5P7397 ,0156 -50 -70 -50 +10 +10 +40 +212 25,21 42,27,19 64,67,55 64,70 91,84,85 103,92,94 18,15 33,25,20 53,53,52 53,54 78,68,79 59,66,59 5,5 10,15,10 30,35,40 40,45 85,90,95 100,100,100 3P4966 0342 -80 -80 -20 +10 +10 +40 +70 +212 51,27,9 71,66,54 85,84,71 83,76 87,91 100,101,97 108,111,108 45,25,12 57,57,45 68,72,61 67,64 71,60 82,89,71 66,84,86 5,5,5 30,25,20 70,80,65 65,55 75,80 90,95,90 100,100,100 4P7465 0751 -60 -80 -70 0 +10 +10 +40 +212 27,14 48,43,26 63,57,68 56,58,90 87,55 67,97 118,102,112 21,12 42,36,22 54,45,63 62,62,86 83,42 71,90 88,71,72 5,0 15,15,5 30,25,35 30,25,45 40,30 45,50 100,100,100 1P6484 0156 -20 -80 -60 0 +10 +30 +40 +212 5,8 22>16,12 17,36,30 30,38,17,34,28 34,46,42 72,60,72 93,81,83 6,11 23,13,10 20,27,28 25,38,12,28,30 29,37,45 54,47,49 65,66,69 5,5 10,10,10 25,20,25 15,15,15,15,20 25,50,35 50,45,50 100,100,100 Tail e 9 1NHM Electrode (Trade Name - Raco) Linde 124 Flux 'Submer ed Arc Post Weld 1150 F for 50 hr. T ical Plant C La una Verde 2 -'HIN Heat No. Flux No. ~NDT ('F) Charpy Temp. ('F) Sin~le Tandem Wire SorT Energy (Ft. - lbs.) , Lateral Expansion (mils) / Shear 5P5657 0931 -60 -80 -60 0 +10 +10 +40 +212 39,39 19,20,32 51,55,58 69,69,66 62,C7, 77,66 88,91,85 27 37 18,22,28 50,50,63 61,65,59 60,63 '3,72'6,75,83 ,5 10,10,10 30,30,55= 0,50,40 0,40 0,80 100,100,100 lP6484 156 -20 -80 -60 00 +10 +10 +30 +40 +212 5,8 22,16,12 17,36,30 30,38,17 34,28 34,46,42 72,60,72 93,81,83 6,11 23,13,10 20,27,28 25,38,12 28,30 29,37,45 54,47,49 65,66,69 ,5 10,10,10 5,20,25 15,15,15 15,20 5,50,35 50,45,50 100,100,100 Tabl e E8018 NM Electrode (Trade Name - Atom Arc) Shielded Metal Arc Post Weld, 1150 F for 50 hr. T ical 32 Plant C Laauna Verde 2 RPV CBIN Heat No. Lot No. NDT ('F) Charpy Temp. ('F) Energy (Ft.-lbs.) Lateral Expansion (,-l ) X Shear 492L487i 421 B27AE -60 -108 -90 -30 -20 -10 0'40 +130 10,11 25,30,32 19.28,31 22,26,30 38,41,43 50,51.,57 135,137 151,160,161 5,4 6,6,6 19,23,25 23,21,27 28,32,30 36,38,40 84,80 80,82,81 8,10,10 20,25,25 25,25,30 30,30,30 30,40,45 90,80 100,100,100 422K851 313A27AD -80 -90 -80 -40 -20 +25 +40 +50 +68 14,17 14,16,20 26,26,40 65,74,127 107,108 125,125,140 153,143,156 153,143,165 15,16 15,16,20 26,24,33 44,48,76 74,80 84,89,82 95,81,91 85,96,91 5,5 10;10,10 30,30,30 40,50,60 80,70 100,100,90 90,80,90 100,100,100 64089 424B27AE -60 -108 -70 -10 0 +40 +130 14,16 15,20,27 38,42,45 55,62,62 56,75 118,122,130 33 8,9,15 26,31,31 38,44,48 42,55 87,89,82 3.3 5,10,10 30,30,30 35,40,40 50,60'00,100,100 ~Tabl e E8018Nt1 Electrode Trade Name Atom Arc E8018NN Shielded Metal Arc Post lleld, 1150 F for 50 hr. t ical Plant C La una Verde 2 RPV CBIN Heat No. ot No. NDT ('F) Charpy Temp. ("F) Energy (Ft.-lbs.) Lateral Expansion (mils) X Shear 401S 0371 B504B27AE -60 -60 -20 -20 0 +40 +70 +212 42,45,23 61,84,77 68,67 80,85,82 95,97 111,107,109 122,114,130 35,36,20 48,66,62 51,52 63,62,60 71,76 87,85,77 92,92,69 5,5,5 30,25;25 25,25 35,50,35 ,40,75 80,90,80 100,100,100 42P 3162 '426B27AE 401P2871 H430827AE 07R458 5403827AG -70 -50 -70 -40 -20 -20 -10 +40 +212 -90 -70 -10 +10 +40 +130 -70 -60 0 +40 +72 +130 11,7 33,52,32 65,62,37 52,55 60,54,68 96,99 119,122,124 7,10 15,16,16 27,39,54 27,50,56 75,76,107 90,100 130,140,142 9,9 10,11,13 59,61,70 99,101 106,110 129,131,132 9,6 27,42,22 52,48,30 36,38" 44,37,53 57,68 ~ 93,90,68 7 ll 14,15,16 25,35,46 25,42,46 60,62,74 71,76 91,94,93 77 9,9,11 51,52,58 77,78 85,87 81,78,81 5,5 10,15,10 20,10,20 15,15 40,30,30 60,60 100,100,100 3,5 8,8,10 35,35,35 40,45,45 60,50,80 70,80 100,100,100 5,5 15,10,10 50,50,60 80,75 80,80 100,100,100 Table 9 E8018NN Electrode Trade Name Atom Arc E 8018NN Shielded Metal Arc Post lleld, 1150 F for 50 hr. t ical Plant C La una Verde 2 RPV-CBIN Heat No. ot No. NDT(') Charpy Temp. . (F) Energy (Ft.-lbs.) Lateral -Expansion (mils) X Shear 03L048 B525B27AF 02R486 404B27AG -60 -70 -105 -80 -20 -10 +40 +130 -100 -90 -30 -20 -10 +40 +130 8,9 10,16,19 31,50,65 36,53,58 61,75,?9 104,108 122,123,126 12 13 16,17,19 17,30,31 41,42,44 52,64,66 84,87 121,124,129 23 7,10,11 22,37,50 34,43,45 44,58,59 75,77 89,83,91 3,5 6,8,7 15,24,23, 33,34,35 39,45,46 63,68 91,96,95 3.3-10,10,10 30,30,30 40,40,40. 50,60,60 80,80 100,100,100 3,5 8,8,10 15,20,20 30,30,30 40,40,40 60,60 100,100,100 L83978 414B27AD -80 -100 -80 -20 -20 -20 +40 +72 +130 10,12 14,15,24 51,52,81 64,63,69 67,56 120,123 128,140 148,156,168 6,7 10,12,18 3?,40,63 51,47,55 53,45 72 73 78,81 90,81,87 4,5 10,10,12 35,50,40 15,15,15 15,10 80,80 90,90 100,100,100 Table 9 lNHM Electrode Trade Name - Techallo Linde 124 Flux Submer ed Arc Post Weld 1150 F for 50 hrs. t ical Plant A Zimmer RPV CHIN Heat No. NDT ('F) Charpy Temp. ('F) Sinp e Tandem Wire (S or T) Energy (Ft.-lbs.) Lateral Expansion (mils) % Shears KN203 0171 '-80 -130 -80 -20 +10 +40 +212 7,6 34,18,22 68,70,62 75,72 94,82 94,92,86 77 32,16,21 61,57,56 64,64 81,71 76,80,80 5,5 40,35,40 80,70,75 90,90 100,95 100,100,100 -130 -100 -80 -20 -10 +10 +40 +212 7,5 25,16 24,22,25 48,49,54 59,54,54 78,67 80,79 86,89,87 6,5 24,19 21,19,25 44,42,46 48,49,46 65,56 '8,68 87,86,85 5,5 10,10 25,20,30 45,45,60 60,45,60 95,80 95,95 100,100,100 Tabl e 9 E8018-G Held Electrode, Shielded Metal Arc Trade Name - Atom Arc E8018 NN Post Held 1150~F for 50 hr. t ical Plant A Zimmer RPV CBIN Heat No. Lot No. NDT ('F) Charpy Temp. ('F) Energy (Ft.-lbs.) Lateral Expansion (mils) %%d Shear 640967 D502B27AF -80 -105 -80 -20 +40 +72 +130 13,14 16,22,28 58,76,86 102,106,119 119,127 130,140,150 11,13,18 18,42,56 69,74,86 86,82 90,92,80 5,5 10,12,15 15,50,50 90,80,90 90,90 "100,100,100 Table 9 1NNN Electrode Trade Name - Raco Linde 124 Flux, Submer ed Arc Post Meld 1150'F for 50 hr. T ical 37 Plant B La Salle 2 RPV, CBIN Heat N ux No. NOT ('F) . Charpy Temp. (F) Single or Tandem Ener (Ft. - lbs.) SorT Lateral Expansion (mils) I Shear 5P7397 0342 -70 -70 -10 +10 +10 +40 +70 +212 22,16,36 58,68,61 76,73,75 75,69 91,84 79,75,77 84,81,87 22,18,28 54,50,47-60,65, 60 58,56 75,63 73,63,74 69,67,75 5,5,5 25,20,20 30,45,50 35,35 80,85 90,95,95 100,100,100 -70 -10 +10 +10 +40 +70 +212 20,34,27 54,50,59 65,59,69 70,75 71,78 92,101,94 100,95,96 16,32,22 47,47,53 60,56,65 56,61 65,68 82,65,69 88,58,82" 5,5,5 25,20,20 50,25,75 45,55 75,90 95,95,100 100,100,100 t ~ Table 9 E8018-6 Weld Electrode Shielded Metal Arc Trade Name - E8018 NM) Post Weld 1150 F for 50 hr. t ical 38 Plant B La Salle 2 RPV~CBIR Heat No NDT Lot No. (~F) Charpy Temp (OF) Energy (Ft. lbs.) Lateral Expansion (mils) X Shear 401P287 30B27AF -50 -90 -70 -20 -20 -10 ~ 0 +10 +40 +130 7,10 15,16,16 66,76,64 63,81 27,39,54 27,50,56 75,76,107 90,100 130,140,142 7 11 14,15,16 58,61,58 50,61 25,35,46 25,42,46 60,62,74 71,76 91,94,93 ,5 ,8,10 5,15,15 5,15 5,35,35 0;45,45 0,50,80 0,80 00,100,100 402P3162 H426B27AE -70'70 -40 -20 -20 -10 +40 +212 11,7,14 33,52,32 65,62,37 52,55 60,54,53 96,99 119,122,124 9,6,8 27,42,22 52,48,30 36,38 44,37 57.,68 93,90,68 ,5,5 0,15,10 0,10,20 5,15 0,30,30 0,60 00,100,100 Ir i e:.~S Valve: HSIV Table 10 Sh. No. 1 C p:~Bd Applicable Code: ASME Sct. III 1971 and 1971 Summer Addenda Valve Vendor: Atwood 5 Morrill Co. Material Vendor: uaker Allo Castin Co. Material .Specification - SA-216 Grade WCB Heat No. - F9930 Chemical Composition - (wt.X) - C/.25 Hn/.76 Si/.49 P/.017 S/.014 Al/NA Grain Size (ASTM No.) NA C Heat Treatment Normalize 1680-1700 F (6 hr. 5 min.) Air Cool, Temper 1340-1370~F (12 hr. 10 min.) Air Cool, Post Weld 1325-1365~F (7 hr. 20 min.) Air Cool, 1150 F (5 hr. 45 min.) Air Cool Charpy V - Notch Impact Toughness Test Temperature: Ft.-lb. Mi1s % Shear Note - Welding rods used for Susquehanna 1 HSIV were ASME SFA 5.1 Type E7018. These materials were charpy V-notch impact tested at -2(f F in both as-welded and stress relieved (135 F or 1100 F for 8 hrs.): conditions. Results of three specimen averages ranged from 54 to 240 0 ft.-lb. at -20 F. NA - Not Available 7 39 Table 10 h. No. 2 Project: Sus uehanna 1 Valve: MSIV Component: Cover Bonnet Applicable Code: ASME Sct. III 1971 and 1971 Summer Addenda Valve Vendor: Atwood 5 Morril Co. flaterial Vendor: Cann 5 Saul Steel Co. Material Specification - SA-105 Grade II Heat No. 6068582 Chemical Composition (wt. %) - C/.26 Mn/;84 Si/.22 P/.015 S/.024 Al/NA Grain Size (ASTM No.) - Fine grain practice (No grain size available) Heat Treatment - Normalize 1650 F (8hr. ) Air Cool Charpy Y-Notch Impact Toughness Test Temperature: Ft.-lb. Mils / Shear NA NA - Not Available 0 Table 11 Sh. No 1 Project Clinton 1 Valve MSIV Component Body A Applicable Code ASME Sect-III 1974 Valve Vendor Atsvood 5 Morrill Co. Material Vendor: quaker Alley Casting Co. Material Specification - ASME SA216 Grad WCB Heat No. - F7516 Chemical Composition (ult/)- C'n Si P S Al .25 .78 . 53 .018 .013 NA Grain Size (ASTM No.) - N/A Heat Treatment - 1690/1710 F (6hr. 5 min.) air cool + temper 1350/1360 F (6 hrs) air cool + post 'lleld 1200 F (6 hr, 5 min) air cool. Charpy V - Notch Impact Toughness Test Temperature: +60 F Ft-lb Mil s / Shear 30, 24, 34 37>> 27>> 33 40, 40, 40 NA - Not available 41 Table ll Sh. No 2 Project Clinton 1 Val ve MS IV Component Cover (Bonnet Applicable Code Same Valve Vendor Atwood 8 Morrill Co Vendor:Cann 5 Saul Steel Co.- Material Specification - ASME SA 105 (}T Heat No. - 214934 Chemical Composition (wtX)- C. Mn Si .28 .76 .22 P S Al . 017 .023 NA Grain Size (ASTM No.)- Heat Treatment - 1600 F (12hr) quench, Water + 1175 F (12hr) furnace cool Charpy V - Notch Impact Toughness Test Temperature: +60 F -Ft-lb. 62, 60, 55 Mils 48, 45, 50 X Shear 30, 30, 30 NA - Not available 42 A 1 Table 11 Sh. No 3 Project Grand Gulf 1 Val ve HS IV Component Bod Applicable Code ASHE Sect. III 1974 Valve Vendor Atwood 8 Horrill, Co. Material Vendor uaker Allo Castin Co. Material Specification - ASHE SA 216 Grade 1JCB Heat No. - F6406 Chemical Composition.(wt %) - C/.23 Hn/.89 Si/.53 P/.019 S/.012 Al'/NA Grain Size (ASTH No.). NA Heat Treatment 1680/1710 F (5 hrs. 30 min) air cool '-+ temper 1350'F (Shr. 30 min) air cool + Post weld 1200 F-(6 hr.) air cool C Charpy V - Notch Impact Toughness Test Temperature +60 " Ft-lb.. 32,31,34 Mils 33 32 3] % Shear 40 40 40 NA - Not Available Table 11 Sh. No. 4 project Valve Component Applicable Code S Valve Vendor Atwood 8 Morrill Co. Material Vendor. Cann 5 Saul Steel Co. Material Specification .SA"-105 (qT) Heat No. 632202 Chemical Composition . (wt. /) - C/.26 Mn/.94 Si/.20 P/.023 S/.015 A'l/NA'rain Size - (ASTM No.) Heat Treatment - 1550 F (12 hr.) quench.'in water + 1175 F. 12 hr.), furnace cool. Charpy V - Notch Impact Toughness Test Temperature: .+60 F Ft-lb : 66,74,65 Mils '58,64,54 g Shear 20,20,20 NA - Not Available Table 11 Sh. No 5 Project Ri.verbend 1 Valve MSIV Component Bod Applicable Code ASME Sect III, 1974 Valve Vendor Atwood 8 Morrill Co , Material Vendor Atwood 5 thrill, Ltd. Material Specification - SA 216 Grade MCB Heat No. - 35 Chemical Composition (wt'/)- -4 .24 Mn Si P S Al .82 .46 .022 .013 NNN Grain Size (ASTM No.) - N/A Heat Treatment - 1650 F - 1800 F (8hrs) Air cool to 400 F + temper 1150 /1250 F (8hrs) air cool-,+ post weld 1095 /1195 F (18 hrs) furnace cool to 800 F (100 F/N) I, air cool Charpy V - Notch Impact Toughness. Test Temperature: +60 Ft-1 b . 31. 5, 37.5.
- 39. 5 Mils 33, 41, 40 X Shear 10, 10, 10 NA-Not Available
Table 11 Sh. No. 6 Project b nd 1 Valve MSIV Component Cover Bonnet Applicable Code SAME Valve Vendor SAME Material Vendor: Cann & Saul Steel Co. Material Specification - ASME SA105 QT Heat No. 216149 Chemical Composition. (wt. !) - C/.30 Mn/.88 Si/.16 P/.006 S/.014 Al/NA Grain Size - (ASTM No.) NA Heat Treatment 1550~F (12 hr.) quench in water+ 1225~F (12 hr.) Furnace cool. Charpy V - Notch Impact Toughness .Test Temperature '-.+6 F Ft-lb 62,64,60 Mils 56,54,52 / Shear 20,20,20 NA - Not Available Table 11 Sh. No 7 Project a una Verde 1 Valve MSIV Component Bod Applicable Code ASME Sect. III, 1971 with Summer 1973 addenda Valve Vendor Rockwell International, Material Vendor. Material'pecii'ication - ASME SA216 Grade 'IfCC Heat No., 1750262 Chemical Composition.(wt.%) -'C/.21 Mn/1.19 Si/.43 P/.011 'S/.009 A'l/.043 Grain Size (ASTM No.) NA Heat Treatment-1700'F (10 hrs.) normalize + 1225 F (7;5 hrs.) Temp.. 1100oF (6 hr.) Post weld Charpy V - Notch Impact Toughness Test Temperature +40 " Ft lb: 29.0,33.0,35.0 Mils: 25.0 26 0 30.0 / Shear: 15 15 15 NA - Not Available 47 4 o Table ll 0 Sh. No. Project Valve SIV una Verde 1 Component Bonnet Applicable Code SAME Yal ve Vendor SAME , Material Vendor: Cann 8 Saul Steel Co. Material Specification - ASME SA105 Nuc. Heat No. 211971 Chemi cal Compos ition. (wt X)- Grain Size - (ASTM No..) - NA Heat Treatment - 1550~F (10 hr.)
- 1175'F (10'hr.)
C/.27. Mn/1.03 Si/.22 ,P/.010 S/.014"Al/NA Quench in water '+ Furnace cool Charpy V Notch Impact Toughness Test Temperature: +40 F I't lb 35,45,34 Mi1s: NA I Shear: 30i40 30 31,34,35 NA 30,30,30 45,38,48 64,57,65 15,15,15 Ft-lb: 55, 47, 43 ~ Mils: 66, 64, 60 62, 64, 52 58, 62, 72 39, 44, 38 40, 45, 52 74, 72, 65 70, 68, 75 56, 60, 57 '8, 60, 60 X Shear:, 20, 15, 15 20, 20, 20 20, 20, 20 15, 15, 15 20, 20, 20 NA - Not Available 1 ~ ~ + ~ Table ll Sh. No 9 TVA X20 Valve HSIV Component Bod Applicable Code ASHE Sect. III, 1974 with summer 1975 addenda.= Valve Vendor Atwood 5 Horrill Co., Haterial Vendor: quaker Alloy Casting Co. Haterial Specification - ASHE SA216 Grade llCB Heat No. F3547 Chemical Composition . (wt. !) - C/.23 Hn/.88 Si/.38 P/.016 S/.015 .Al/NA Grain Size (ASTH No.).- NA Heat Treatment 1700/1721 F (6 hr. 20 min.) air cool + temper 1345~F (6 hr. 45 min,) air cool +post weld 1200/1225 F (6 hrs. 30 min) air cool V Charpy V - Notch Impact Toughness Test Temperature: +60 " 0 Ft lb: 66, 56, 54 Nils: / Shear 40 40 40 NA - Not Available 49 Table 11 Sh. No 10 Project TVA Valve MSIV Component Cover Bonnet Applicable Code Same Valve Vendor Same , Material Vendor Cann & Saul Steel Co. Material Specification - ASME SA 105 Heat No. - 217630 Chemical Composition (wt/) - ~ C Mn Grain Size (ASTM No.) - 5'9 Si P S Al .19 .013 .013 NA ~g Heat Treatment - 1650 F (6 hrs) air cool + 1550 F (6 hr 30 min} water quench + Temper 1200 F (12 hr 30 min) Charpy V-Notch Impact Toughness Test Temperature: +60 F Ft-lb Mi1s 90, 89, 77 71, 67, 59 / Shear 50, 50, 40 NA - Not available 50 0 Table ll Sh. No.ll Project CNV Valve MSIV Component Bod Applicable Code ASME Sect III, 1971 with 573 Addenda Valve Vendor Rockwell International , Material Vendor-"Rockwell International Material Specification SA216 Grade WCC Heat No. - 3760171 Chemical Composition (wtX)- Grain Size (ASTH No.) - N/A C Hn Si .17 1.09 .50 P S Al .008 .011 .060 Heat Treatment - 1700 F (8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />) normalize 1275 F (8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />) Temper 1100 F (8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />) Post Weld Charpy V - Notch Impact Toughness ,Test Temperature: + 40 F 0 Ft-lb. Mi 1 s 35.0, 38.0, 29.0 32.0, 36.0, 29.0 % Shear 20, 20, 20 NA.-..'Not available Table 11 Sh. No 12 Project CNV Val ve NSIV Component Bonnet Applicable Code Same Valve Vendor Same Naterial Vendor.Cann 8 Saul Steel Co. Material Specification SA 105 Heat No. - 214943 Chemical Composition (wt%)- .35 Nn Si P S Al .78 .25 .014 .023 NA Grain Size (ASTN No.) - N/A Heat Treatment - 1550 F (10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />) water quench 1175 F (10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />) furnace cool 1100 F (10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />) post weld 'harpy V - Notch Impact Toughness Test Temperature: +40 F Ft-lb. Nils / Shear 25, 25, 29 36, 34, 34 20, 20, 20 28, 30, 34 36, 37, 35 20, 20, 20 NA-Not Available 52 0 ~ L 'l ~ Waa~~O 3LoX ~ Ib p Oping-]