AUG8 5 1981 Tennessee Valley Authority Browns Ferry 2 and 3

APPENDIX-B NOTICE OF DEVIATION Docket Nos-.

50-260 5 296 License Nos.

DPR-52 8 68 Based on the NRC inspection conducted on June 26 through July 26, 1981 certain of your activities appear to deviate from your, commitments to the Commission as indicated below:

The Browns Ferry Final Safety Analysis Reports (FSAR) Section 5.2.6.2 states that the Containment Atmosphere Dilution (CAD) system nitrogen storage tanks are to be maintained at a minimum pressure of 100 psig.

Contrary to the above, on June 13, 1981 the inspector noted that the pressure in the A and, B nitrogen storage tanks were 85 psig and 60 psig respectively.

, 8110160435 811007K',

PDR ADOCK 05000289 I

~r

~

1 t