Revises 850411 Response to NRC Re Violations Noted in Insp Rept 50-400/85-04.Corrective Actions:Conductor 10 Replaced W/Conductor 2 & Ebasco Performing Review of Power Distribution & Data Sheets to Ensure Cable Safety
ML18019A305
Person / Time
Site: Harris Duke Energy icon.png
Issue date: 07/19/1985
From: Watson R
CAROLINA POWER & LIGHT CO.
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
CON-NRC-378 NUDOCS 8508120308
Download: ML18019A305 (3)


Text

P. 0.

Box 101 New Hill, North Carolina 27562 July 19, 1985 Dr. J. Nelson Grace United States Nuclear Regulatory Commission Region II 101 Marietta Street, Northwest (Suite 2900)

Atlanta, Georgia 30323 NRC-378 Dear Dr. Grace'.

In reference to your letter of March 12,

1985, referring to RII:

GFM/RLP 50-400/85-04-02, CP&L submitted a

response on April 11,

1985, stating the actions taken and planned for resolution of the referenced violation identified in Enclosure 1.

In order to more completely address the corrective actions

taken, the attached is Carolina Power

& Light Company's revised response to the referenced vioLation.

This letter supercedes our April 11,

1985, response.

It is considered that the corrective action taken is satisfactory for resolution of the item.

Thank you for your consideration in this matter.

Yours very truly, gC2C'C~czM~

R.

A. Watson Vice President Shearon Harris Nuclear Power Plant RAW:sae Attachment cc'.

Messrs.

G. Maxwell/R. Prevatte (NRC-SHNPP)

B. C. Buckley (NRC)

Dr. 3. Nelson Grace iVRC-378 bcc:

Mr. H. R. Banks Mr. T. A. Baxter (Shaw, Pittma Mr. C. S. Bohanon Mr. H. W. Bowles Mr. C. Carmichael (2)

Mr. iV. 3. Chiangi Mr. A. B. Cutter Dr. T. S. Elleman Ms. S. F. Flynn Mr. G. L. Forehand Mr. 3. F. Garibaldi (Ebasco)

Mr. 3. L. Harness Mr. P. C. Hopkins Dr. 3. D. E. 3effries Mr. I. A 3ohnson Mr. L. I. Loflin Mr. R. E. Lumsden Mr. R. L. Mayton, 3r.

Mr. S. McManus Mr. G. A. Meyer Mr. C. H. Moseley, 3r.

Mr. D. L. Nordstrom (LIS)

Mr. R. M Parsons Mr. G. A. Sinders Mr. M. Shannon (Westinghouse)

Mr. Sheldon D. Smith Mr. M. F. Thompson Mr. A. C. Tollison Mr. E. 3. Wagner Mr. R. A. Watson Mr. 3. L. Willis File: HI/A-2D File: H-X-0500 n, Potts dc Trowbridge)

NBI/2-OS5

Attachment to CPRL Letter of Response to NRC Report RII: GFM/RLP 50-OOO/85-Oe-02 Re rted Violation:

10 CFR 50.55(f)(l) requires CPRL to implement the quality assurance program described or referenced in the Preliminary Safety Analysis Report.

Section 1.8.5.3 of the PSAR (versus the Quality Assurance Program, as stated in the Notice of Violation) requires that measures be established and implemented for the selection and review for suitability of application of materials, parts, and equipment that are essential to the safety-related functions.

Contrary to the above, on January 28,

1985, the inspector identified an undersized electrical cable in DC panel DP-lASA. This cable (No. 10821A-SA) was a two-conducter 810 AWG that has a maximum ampere rating of 20 amps.

It was protected by a 100-ampere circuit breaker and supplied power to Auxiliary Transfer Panel 1A-SA which had a loading of approximately 100 amps.

This cable had been installed and inspected in accordance with approved design documents and this unsatisfactory condition had not been identified.

This is a Severity Level V violation (Supplement II).

Denial or Admission and Reason for the Violation:

The violation is correct as stated.

As complete information on load was unknown, an arbitrary size was chosen by HPES Electrical and was input into the cable routing system in order to assure an adequate

'route was available for the subject cable.

The cable card was inadvertently released to the field prior to final verification.

Corrective Ste s Taken and Results Achieved:

The subject

$110 AWG conductor was replaced with a

/$ 2 AWG conductor per Field Change Request (FCR-E-0052).

A review has been conducted by Ebasco using the latest issue of the power distribution and motor data sheets (Drawing CAR 2166-8-O~i) ro assure safety related cable sizes are suitable for the breaker rating.

Corrective Ste s Taken To Avoid Further Noncom liance:

Administrative instructions have been issued to HPES Electrical personnel to ensure closer monitoring and control of cable sized by HPES.

In addition, a design guideline has now been issued which requires that cable size be verified based on the feeder breaker rating, connected load, and circuit length, before cable routes and sizes can be released by HPES.

Date When Full Com liance %as Achieved:

Full compliance was achieved on 3une IO, 1985.