Docket No.:
50-400 QCT 1
)A President Construction Mr.
E.
E. Utley, Executive Vice Power Supply and Engineering and Carolina Power and Light Company Post Office Box 1551
- Raleigh, North Carolina 27602
Dear Mr. Utley:
D IS /RIB U1 ION oc e.
a e 50-40'0 NRC PDR LPDR
PRC System LBk3 Reading BBuckley JLee NGrace EJordan
Subject:
Shearon Harris, Unit 1
FSAR Amendment ll Review, Request for Additional Information - Structural Engineering In our review of Amendment ll to the FSAR (Appendix A to Section 3 of the FSAR) we find that additional information, identified in the enclosure, is required in order to continue our review.
If you should have any questions, contact Bart Buckley (301-492-8379).
Sincerely,
Enclosure:
As stated cc:
See next page g
F original qg~~ b
~<~ ~ ~ighton George W. Knighton, Chief Licensing Branch No.
3 Division of Licensing DL.L 83 BBuckley/yt 9/g P/84 D '
ighton 9//}7/84 aoioi~o~~~
~poonoo ggf,001 a
AoOCW O
>O A
I ir li il Il
'I III I
Mr. E.
E. Utley Executive Vice President Power Supply and Engineering and Construction Carolina Power 5 Light Company Post Office Box 1551
- Raleigh, North Carolina 27602 George F. Trowbridge, Esq.
Shaw, Pittman, Potts 5 Trowbridge 1800 M Street, NW Washington, DC 20036 Richard E. Jones, Esq.
Associate General Counsel Carolina Power 5 Light Company 411 Fayetteville Street Mall Raleigh, North Carolina 27602 M. David Gordon, Esq.
Associate Attorney General State of North Carolina Post Office Box 629
- Raleigh, North Carolina 27602 Thomas S. Erwin, Esq.
115 W. Morgan Street Raleigh, North Carolina 27602 Mr. George Maxwell Resident Inspector/Harris NPS c/o U.S. Nuclear Regulatory Commission Route 1, Box 315B New Hill, North Carolina 27562 Charles D. Barham, Jr.,
Esq.
Vice President 5 Senior Counsel Carolina Power 8 Light Company
-Post Office Box 1551 Raleigh, North Carolina 27602 Mr. John Runkle, Executive Coordinator Conservation Council of North Carolina 307 Granville Road Chapel Hill, North Carolina 27514 Mr. Wells Eddleman 718-A Iredel 1 Street
- Durham, Nor th Carolina 27705 Shearon Harris Mr. George Jackson, Secretary Environmental Law Project School of Law, 064-A Univeristy of North Carolina Chapel Hill, North Carolina 27514 Dr. Phyllis Lotchin 108 Bridle Run Chapel Hill, North Carolina 27514 Mr. Travis Payne, Esq.
723 W. Johnson Street Post Office Box 12643 Raleigh, North Carolina 27605 Mr. Daniel F.
Read CHANGE Post Office Box 2151
- Raleigh, North Carolina 27602 Bradley W. Jones, Esq.
U.S. Nuclear Regulatory Comm.
Region II 101 Marietta Street Atlanta, Georgia 30303 Richard D. Wilson, M. D.
725 Hunter Street Apex, North Carolina 27502 Regional Administrator - Region II U.S. Nuclear Regulatory Commission 101 Marietta Street Suite 3100 Atlanta, Georgia 30303 Mr. Robert P. Gruber Executive Director Public Staff -
NCUC Post Office Box 991 Raleigh, North Carolina 27602
Dr. Linda Little Governor's Waste Management Board 513 Albemarle Building 325 North Salisbury Street Raleigh, North Carolina 27611
ENCLOSURE Staff guestion on Amendment ll to the Shearon Harris FSAR Concerning Concrete Curing (Appendix A to Section'3 of the FSAR) 1.
The amendment states that there has been engineering data available to justify"the alternative requirements for concrete curing.
Please provide such:data.
2.
The amendment provides minimum temperature and moisture requirements for the first three days out of seven day curing. Provide the require-ments for the fourth through seventh day. If there is no requirement during these days, provide justification.
$ h
~~
~ r 4
/t
&t 1