ML18017B460

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 810620-0720
ML18017B460
Person / Time
Site: Harris 
Issue date: 08/05/1981
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML18017B455 List:
References
50-400-81-14, NUDOCS 8109240376
Download: ML18017B460 (2)


Text

APPENDIX A NOTICE OF VIOLATION Carolina Power and Light Company Harris 1

Docket No. 50-400 License No.

CPPR 158 As a result of the inspection conducted on June 20 through July 20, 1981 and in accordance with the Interim Enforcement Policy, 45 FR 66754 (October 7,'980),

the following violation was identified.

10 CFR 50, Appendix B, criterion XVII as implemented by PSAR Section 1.8.5.17 and Carolina Power and Light's Corporate gA Program Part I, Section 8.2.2 requires that the results of inspections be properly documented.

Contrary to the above, the results of inspections were not documented, in

that, on July 6, 1981, a Unit 1 containment building Cadweld numbered 032S on drawing 8099 sheet 17A was found not to have the results of the installation inspection recorded and on June 30, 1981, the weld data report for ASME class 3 weld joint 2-SW-207-FW 459 was found not to identify the correct welder who had applied the tack weld.

This is a Severity Level VI Violation (Supplement II.F).

Pursuant to the provisions of 10 CFR 2.201, you are hereby required to submit to this office within thirty days of the date of this Notice, a written statement or explanation in reply, including:

(1) admission or denial of the alleged viola-tion; (2) the reasons for the violation if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved.

Consideration may be given to extending your response time for good cause shown.

Under the authority of Section 182 of the Atomic Energy Act of

1954, as
amended, this response shall be submitted under oath or affirmation.

Date: At)

Si0924037h

Bi09i7, PDR ADOCK 05000400 8

PDR

V

~

\\