ML18017B298

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 800901-26
ML18017B298
Person / Time
Site: Harris  Duke Energy icon.png
Issue date: 10/30/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML16312A190 List:
References
50-400-80-22, 50-401-80-20, 50-402-80-20, 50-403-80-20, NUDOCS 8012180402
Download: ML18017B298 (2)


Text

APPENDIX A NOTICE OF VIOLATION Carolina Power 6 Light Company Shearon Harris Site License Nos.

CPPR-158, Based on the, NRC inspection September 1-26, 1980, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below.

These items have been categorized as described in correspondence to you dated December 31, 1974.

As required by Criterion IX of Appendix B to 10 CFR 50, as implemented by Carolina Power 6 Light Company's (CPM,)

PSAR, Section 1.8.5.9 and CPM,'s Corporate QA Program Part I, Sections 6.2.3 and 7.3.4, measures shall be established to assure welding is controlled in accordance with applicable standards.

Contrary to the

above, piece number 10 on pipe hanger number CC-H-911 was not welded in accordance with the weld symbol shown on its installation drawing; the installation drawing for pipe hanger CC-H"388 and CC"H"911 did not correctly depict the welds to be applied.

Workers and foremen who were responsible for welding pipe hangers did not understand the meaning of some of the installation welding symbols.

Welding inspection personnel were not documenting the pipe hanger welds that were not as depicted on their instal-lation drawings.

This is an infraction.

1 k

0