REGULATOR NFORMATION DISTRIBUTION EM (BIDS)

ACCESSION N

8004220451 DOC,DATE! 80/04/15 NOTARIZED!

NO FACIL:50 40 Shearon Har ris Nuclear Power Planti Unit ii Carolina 50>>

01 Shearon Har ris Nuclear Power Plant~ Unit 2i Carolina 50-402 Shearon Harris Nuclear Power Plant~

Unit 3~ Carolina AUTH,NAME AUTHOR AFFILIATION MCDUFFIEiMA, Carolina Power L Light Co ~

REC IP, NAME RECIPIENT AFF ILIATION SELLSrDeEe Environmental Projects Branch 2

SUBJECT:

Submits info in-response to NRC '800324 questions re electrical field gradients surrounding proposed Harris Harnett 500 kV line,.

DISTRIBUTION CODE:

C002B COPIES RECEIVED:I TR 4 ENCL ~

SIZE;~4'ITLE:

Envir on,

Comments,

'I NOTES; DOCKET 0

05000400 05000401 0500040?

9'o8 RECIPIENT COPIES ID CODE/NAME LTTR ENCL ACTION:

05 PM P<E44CCS'Elf 1

18 LA PPQ gy~

1 INTERNAL:

0 REG FIJ 1

07 2

10.CST BNFT ANL 1

13 HYDRO METEOR 1

15 EFLT TRT SYS 1

19 DIR DSE 1

AD SITE ANALY 1

EXTERNALt 03 LPDR 20 NATL LAB RECIPIENT ID CODE/NAME 17 BC E/AS 4~

Ao

rneOWa, 02 NRC PDR 09 ENVN SPEC BR 12.GEOSCIEN BR 14 ACDENT ANALY 16 RAD ASMT BR AD ENVIRON TECH OELD 04 NSIC ACRS COPIES LTTR ENCL 1

1 1

1 1

1 lh Rn /c. oft g~R R s 8c rein/84 dR +Q L8

~W aa

)gag il 0

TOTAL NUMBER OF COPIES REQUIRED!

LTTR ~

ENCL

f r

CSQE, Carolina Power & Light Company April 15, 1980 Mr. Donald E. Sells, Acting Chief Environmental Projects Branch 2

Division of Site Safety and Environmental Analysis U. S. Nuclear Regulatory Commission Washington, D.

C.

20555 SHEARON HARRIS NUCLEAR POWER PLANT UNIT NOS. 1, 2, 3, AND 4 DOCKET NOS. 50-400, 50-401, 50-402, AND 50-403 HARRIS-'HARNETT'500 KV'LINE*''ear Mr. Sells:

Your letter of March 24, 1980 transmitted questions concerning electrical field gradients surrounding the proposed Harris-Harnett 500 kV line.

The following information is submitted in response to your questions:

(1)

Maximum Predicted'Pield Gradierits Maximum operating voltage Maximum electrical field within the right-of-way Maximum electrical field at the edge of the right-of-way 550 kv 8.4 kv/M 1.5 kv/M (2)

Ex ected Electrical Field Gradients Normal operati.ng voltage Normal electrical field within right-of-way Normal electrical field at the edge of the right-of-way 525 kv 6.34 kv/M 1.42 kV/M 411 Fayetteville Street o P. O. Box 1551 o Raleigh, N. C. 27602 8064 2sv'foal

h Ak tl

April 15, 1980 (3)

Actual Measurements on Existin 500 kV Lines The proposed 500 kV structure for the Harris-Harnett Line is a triangular configuration with three 1590 MCM 45/7 ACSR conductors per phase.

The sub-conductors are 18 inches apart.

The center phase is 29.8 feet above the two outside phases.

The outside phases are 42.4 feet apart.

This design is not yet in service; therefore, actual field measurements are not available.

Please advise us if you have any further questions concerning the proposed Harris-Harnett 500 kV line.

Yours very truly, SDF/jc (1156)

M. A. McDuf ie Senior Vice President Engineering

& Construction

0

~

L IH