,,ACCELERATED DI UTION DEMONS ION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR: 9106190007 DOC. DATE: 91/06/10 NOTARIZED: NO FACIL:50-400 Shearon Harris Nuclear Power Plant, Unit 1, Carolina AUTH.NAME AUTHOR AFFILIATION FLOYD,S.D.

Carolina Power

& Light Co.

RECIP.NAME RECIPIENT AFFILIATION Document. Control Branch (Document Control Desk)

SUBJECT:

Forwards 910513 application for amend to NPDES Permit NC0039586,reflecting addi source of hydrazine discharge.

DISTRIBUTION CODE:

COOID COPIES RECEIVED:LTRi ENCL i

SIZE:

TITLE: Licensing Submittal: Environmental Rept Amdt 6 Related Cor NOTES:Application for permit renewal filed.

DOCKET 05000400 espondence 05000400 RECIPIENT ID CODE/NAME PD2-1 LA MOZAFARI,B.

INTERNAL: ACRS NRR/DET/ESGB 8D OGC/HDS 1 RGN2 DRSS/RPB EXTERNAL EGE(G S IMPSON i F NSIC COPIES LTTR ENCL 3

3 1

1 6

6 1

1 1

0 1

1 2

2 1

1 RECIPIENT ID CODE/NAME PD2-1 PD AEOD/DSP/TPAB OC EG FILE 01 NRC PDR COPIES LTTR ENCL 1

1 1

1 1

0 1

1 1

1 NOTE TO ALL"RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 20079) TO ELIMINATEYOUR NAMEFROM DISTRIBUTION LISIS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 21 ENCL 19

p il,,: !

0

~ r 1

l I

1 E

"r

~

1

~

CNK Carolina Power & Light Company SERIAL'LS-91-147 United States Nuclear Regulatory Commission ATTENTION: Document Control Desk Washington, DC 20555

/

SHEARON HARRIS NUCLEAR POWER PLANT DOCKET NO. 50-400/LICENSE NO. NPF-63 NPDES PERMIT RENEWAL AMENDMENT Gentlemen:

Carolina Power

& Light Company (CP&L) hereby transmi'ts a copy of an amendment to the application for renewal of the Shearon Harris Nuclear Power Plant (SHNPP) National Pollutant Discharge Elimination System (NPDES) Permit.

The renewal request was transmitted to NRC by CP&L letter dated September 28, 1990.

As required in Section 3.2 of Appendix B to the SHNPP Operating License, a copy of the new permit will be transmitted to the NRC within 30 days of its renewal.

Please refer any questions regarding this submittal to Mr. Steven Chaplin at (919) 546-6623.

Yours very truly, S.

D. Floyd Manager Nuclear Licensing Section SDF/SDC Enclosure cc:

Mr. S.

D. Ebneter Ms.

B. L. Mozafari Mr. J.

E. Tedrow 411 Fayettevilte Street o P. O. Box 1551 o Raleigh, N. C. 27602 9106i90007 910610 PDR ADOCK 05000400 P

PDR

4 1

Carolina Power 8 Light Company MAY I 3 l99l Mr. Dale Overcash, P.E.

N.C. Division of Environmental Management P.O.

Box 27687

Raleigh, N.C.

27611-7687 RE:

Shearon Harris Nuclear Power Plant NPDES Permit No. NC0039586 Amendment to Permit Application

Dear Mr. Overcash:

On September 27, 1990, Carolina Power

& Light Company (CP&L) submitted a request for the Shearon Harris Nuclear Power Plant (SHNPP) permit to be renewed.

Currently, the existing permit and permit renewal application only address hydrazine discharges through low volume waste.

Because of changing plant conditions since submittal of the application, wastewater containing hydrazine may occasionally need to be discharged through the radwaste system, as well as the low-volume waste system.

Therefore, this is intended to amend the application to reflect this additional source of hydrazine discharge..

I Additionally, CP&L is respectfully requesting modifications to the current hydrazine discharge period and the notification requirements.

A description of the alternate routing of hydrazine and the requested permit changes are included in the enclosure.

Thank you for your cooperation.

Should you have any questions or require further information, please call Mr.

Cam Wheeler at 546-6725 or Ms. Barbara Stephens at 546-7777.

Yours very truly, George J. Oliver, Ph.D.

Manager Environmental Services Enclosure cc:

Mr. A.

bcc: Mr. R.

Mr. S.

Mr. M.

Mr. D.

Mr. C.

Mr. J.

Mr. B.

Mouberry, Raleigh Regional Office, DEM M. Coats (w/out enclosure)

D. Floyd R. Greeson E. Hollar S. Hinnant (w/out enclosure)

M. McDowell A. Meyer 411 Fayettevilte Street

~ P. O. Box 1551

~ Raleigh. N. C. 27602

4

r tl

~

~

g ~

AMENDMENT TO SHEARON HARRIS NUCLEAR POWER PLANT NPDES PERMIT APPLICATION CHANGES IN P T OPERATION HYDRAZINE DISCHARG S The present NPDES permit allows for low volume wastes to be routed to either of two

systems, the low-volume waste system (Serial No. 004) for non-radioactive wastes or the radwaste system (Serial No. 005) for radioactive wastes.

(Flow diagrams submitted previously to the Division of Environmental Management (DEM) indicate both of these flow paths.)

One component of low volume waste is secondary

waste, which consists of water from the secondary cooling system (the normally non-contaminated steam component in this nuclear power plant).

The secondary cooling system contains hydrazine as an oxygen scavenger for corrosion control.

The "Summary Description of Hydrazine Wastes" submitted to DEM in February of 1989 stated that "all wastes that might contain hydrazine flow via plant drains to the low volume waste treatment system."

This statement is no longer valid.

Within the past year, there has been an occurrence of a steam generator (primary system) tube leak, causing the secondary waste to become radioactively contaminated for a brief period.

During this incident, secondary waste was routed to the radwaste system (Serial No.

005) for treatment rather than through the low-volume waste system (Serial No.

004).

The plant promptly corrected the leaks, treated the contaminated wastewater, and resumed the routing of secondary waste to the regular low volume waste treatment system.

Such incidents are expected to occur infrequently.

RE VEST FOR PERMIT MODIF1CATIONS OF H D

Z NE RE UIREMENTS CP&L requests two changes to the current hydrazine requirements:

1

, RELEASE PERIOD The permit currently allows the discharge of hydrazine at a concentration above 60 pg/1 and no greater than 2 mg/l for a period of no more than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. It is requested that this be changed from a 24-hour to a 48-hour total period.

The additional time is needed primarily due to the extra time required to treat and release water through the radwaste system, in the event that secondary waste is routed through this system.

Following wet layup, if the steam generators contained radioactivity, the water would be drained from the generators and batch-treated for removal of radioactivity.

Only 25,000

~ y

gallons can be treated at the time in the radwaste tanks, and the discharge rate from radwaste, based on NRC requirements, is limited to 34-90 gpm according to the activity level.

A minimum of six hours processing time is needed between releases.

Normally, secondary waste containing hydrazine is routed through low volume waste rather than radwaste.

Normal low volume wastes typically can be released in a 24-hour total period; however, there could be instances in which a longer time may be needed.

NOTIFICATION PERIOD The current permit requires that CP&L "shall notify the DEM Raleigh Regional Office at least one week prior to the conclusion of any wet layup period and shall specify if there willbe a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period in which hydrazine will be discharged at a level greater than 60.0 pg/1."

CP&L requests that the notification requirement be dropped.

This change is requested because it would be impractical to provide prior notification since hydrazine-containing equipment may be needed at a

moment's notice during normal plant operation and since plant outage schedules are often subject to change.

Alternatively, the permit could be changed to require notification within one working day after a release of hydrazine at a concentration exceeding 60 pg/l.

Per recent conversation between Mr.

Tim Donnelly of DEM's Raleigh Regional Office and Mr.

Cam Wheeler of CP&L, it is our understanding that this notification is not necessary.

~ >

'C