Text
REGULATORYIFORNATION DISTRIBUTION 8+8 (RIDE)
ACCESSION NBR: 87091 501 18 DOC. DATE: 87/09/04 NOTARIZED:
NO FACIL: 50-,400 Shearon Harv is Nuclear Poujer Plant> Unit 1> Carolina AUTH. NAME AUTHOR AFFILIATION COLLINS':M.
Region 2> Office of Div ector RECIP. NAME RECIPIENT AFFILIATION UTLEYiE. E.
Car o 1 ina P oujer
& Ligh t Co.
DOCf(ET 0 05000400
SUBJECT:
Advises that 870528 Rev 10 to emergency plan consistent e/provisions of 10CFR50. 47(b)
& acceptable. Confirmation re use of "no detectable alpha above background" v equested.
DISTRIBUTION CODE:
IE35D COPIES RECEIVED: LTR i ENCL 0 SIZE:
TITLE:
Emev gencg Preparedness-Appraisal/Conf irmatorg Action Ltr/Exev'cise Rep NOTES: Application %or permit renewal filed.
05000400 REC IP IENT ID CODE/NAME PD2-1 PD INTERNAL: ARM/DAF/LFMB NRR/PMAS/ILRB RQN2 FILE 01 EXTERNAL:
LPDR NSIC COPIES LTTR ENCL REC IP IENT ID CODE/NAME BUCKLEYiB NR EPB E~L 02 DRSS/EPRPB NRC PDR COPIES LTTR ENCL TOTAL NUMBER OF COPIES REQUIRED:
LTTR 11 ENCL
SEP 04 1987 Carolina Power and Light Company TN:
Mr. E.
E. Utley Senior Executive Vice President Power Supply and Engineering and Construction P. 0.
Box 1551
- Raleigh, NC 27602 Gentlemen:
SUBJECT:
SHEARON HARRIS RADIOLOGICAL EMERGENCY PLAN REVIEW DOCKET NO. 50-400 We have completed our review of Revision 10 to the Shearon Harris Emergency
- Plan, dated May 28, 1987.
Our review indicated that'he changes to your Emergency Plan were consistent with the planning standards of 10 CFR 50.47(b) and the requirements of Appendix E to 10 CFR 50; however, one item is brought to your attention.
In this revision the alpha contamination limits contained in Table 4.6-1 of the Emergency Plan were changed from non-detectable to 10 cpm.
On August 13, 1987, in a telephone conversation between A. Poland and A. Garrou of your staff and A.
Tabaka of Region II, it was clarified that the 10 cpm represented the minimum detectable count rate using the specified instrumentation.
However, to ensure compliance with 10 CFR 20.301, the licensee representatives comitted to revise the alpha contamination limit to "no measureable count rate."
On September 1,
- 1987, during a telephone conversation between A. Garrou of your staff and E. Testa of Region II, it was indicated that the Plant Review Committee had reviewed and approved the wording= "no detectable alpha above background."
If your understanding of this commitment differs from the above, please contact our office promptly.
Completion of this change will be reviewed during the next Plan revision.
Please be reminded that 10 CFR 50.54(q) requires NRC approval of any changes to your Plan which may decrease the effectiveness of the Plan.
However, if your safety review indicated no decrease in the level of emergency preparedness, then changes can be made without NRC approval.
In all cases, you should furnish copies of each proposed change to the NRC in accordance with 10 CFR 50.54(q).
- Also, any changes to the Emergency Plan Implementing Procedures should be made in accordance with the requirements of 10 CFR 50, Appendix E, Section V.
8709'02 i8 870904 PDR ADOCK 05000400 PDR
Carolina Power and Light Company Should you have any questions regarding this letter, please contact Mr. Thomas R. Decker of our staff at 404/331-2559.
Sincerely, CPJG(MAL SfGNFD 6'lt'OUGLAS M, C<~.~'~-~<
Douglas M. Collins, Chief Emergency Preparedness and
,Radiological Protection Branch
'ivision of Radiation Safety and Safeguards cc:
S.
A. Watson, Vice President Harris Nuclear Project i)-. L. Tibbitts, Director of Regulatory Compliance Q. L. Willis, Plant General Manager bcc X~ Barth, OGC QIRC Resident Inspector M. Upchurch,
- Chairman, Triang'1e J Council of Governments RI I ~)
ATabaka 8/~/87 Rrr)
TRDt,cker 8/ A/87 RI P redrickson 8/yg+87