Responds to NRC Re Violations Noted in Insp Rept 50-400/87-06.Corrective Actions:Auxiliary Feedwater Pump 1A Repaired & Declared Operable on 870117
ML18004B760
Person / Time
Site: Harris 
Issue date: 04/10/1987
From: Watson R
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
CON-NRC-548 HO-870400-(O), NUDOCS 8704140308
Download: ML18004B760 (5)


Text

REGULATORY INFORMATION DISTRIBUTION SYSTEM (R IDS) t'CCESSION NBR: 8704140308 DOC. DATE: 87/04/10 NOTARIZED:

NO

((FAG IL: 50-400 Shearan Harris Nuclear Paver Plant>

Unit ii Carolina TH. NAME AUTHOR AFFILIATION SON> R. A.

Caro 1ina Pa~er 8c Lig ht Co.

EC IP. NAME RECIPIENT AFFILIATION Dacument. Control Branch (Document Control Des'

SUBJECT:

Responds to NRC 870312 ltr re violations noted in Insp Rept 50-400/87-06. Corrective actions:

1A Auxi liar's Feed+a ter pump declared inoperable on 870112 based on review oF OBT-1087 plant cooldoen to Mode 4 comIpleted on 870113.

DISTRIBUTION CODE:

IEOID COPIES RECEIVED: LTR J ENCL l SIZE:

TITLE: Qeneral (50 Dkt)-Insp Rept/Notice of-Violation Response NOTES: Applicatian Por permit rene'!al filed.

DOCKET 05000400 05000400 RECIPIENT ID 'CODE/NAME

. PD2-1 L*

BUCKLEY, B INTERNAL ACRB AEOD ENF LIEBERMAN NRR ROE> M. L NRR/DOEA DIR NRR/DREP/RPB NRR/P MAS/ILRB (gRQ=~g RQN2 FILE 01 EXTERNAL: LPDR NBIC COPIES LTTR ENCL 0

1 1

2 2

1 1

1 1

1 1

1 1

2 2

1 1

1 REC IPIENT ID CODE/NAME PD2-1 PD ACRS WYLIE DEDRO IE/Dl/ORPB NRR/ADT NRR/DREP/EPB NRR/DRIS DIR OQC/HDB1 RES SPEISI T NRC PDR COP IES LTTR E KL 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

TOTAL NUMBER OF COPIEB REQUIRED:

LTlR 25 ENCL 24

Carolina Power h Light Company HARRIS NUCLEAR PROJECT P.

O.

Box 165 New Hill, NC 27562 APR IO 't'-"'oT File Number:

SHF/10-13510E Letter Number'.

HO-870400 (0)

NRC-548 Document Control Desk United States Nuclear Regulatory Commission Washington, DC 20555 Gentlemen:

In reference to your 1'etter of March 12, 1987, referring to I.E.

Report RII:

50-400/87-06, the attached is Carolina Power

& Light Company's reply to the violation identified in Enclosure 1.

It is considered that the corrective actions taken are satisfactory for resolution of the item.

Thank you for your consideration in this matter.

Very truly yours, R. A. Watson Vice President Harris Nuclear Project RAW:sdg Attachment cc:

Messrs.

B. C. Buckley (NRC)

G. Maxwell (NRC-SHNPP)

Dr. J. Nelson Grace (NRC) 8 870410 0

S704f 4030 < 0500040 pgOC pgR MEM/HO"8704000/PAGE 1/Osl

Attachment to CP&L Letter of Response to NRC I.E. Report RII:

50-400/87-06 Re orted Violation.'echnical Specification 4.0.5 requires that inservice testing of ASME Code Classes 1,

2 and 3 pumps and valves shall be performed in accordance with Section XI of the ASME Boiler and Pressure Vessel Code.

Subsection IWP-3220 of Section XI requires that all.

test data shall be analyzed within 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> after completion of a test.

Contrary to the above, analysis of test data for Section XI inservice test was not analyzed within 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> in that test data for Operational Surveillance OST-1087, performed on December 31, 1986 to obtain baseline data for the "A" Auxiliary Feedwater

Pump, was not evaluated until 12 days later on January 12, 1987, resulting in the pump being declared inoperable.

This is a Severity Level IV violation (Supplement 1).

Denial or Admission and Reason for The Violation:

The violation is admitted.

OST-1087 (Motor Driven Auxiliary Feedwater Pumps Full Flow Test 18 Month) was performed on December 31, 1986, for the first time and therefore had no acceptance criteria stated in the procedure.

Since there was no acceptance criteria established to compare the test results to, the OST.was indicated as satisfactory by the Shift Foreman.

The In-Service Inspection (ISI) group received the test for evaluation on January 5, 1987, but a review was not performed until January 12, 1987.

At the time of the review it was discovered that it was a first run OST without acceptance criteria.

After performing an engineering evaluation the test data taken was determined to be unsatisfactory and the 1A Auxiliary Feedwater (AFW) pump was declared inoperable.

Procedure ISI-800 (In-Service Testing of Pumps) requires that all test data be analyzed within 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> after completion of a test, yet this requirement was not met as stated above.

Corrective Ste s Taken and Results Achieved:

The 1A AFW pump was declared inoperable on January 12,

1987, based on the review of OST-1087.

The plant cooldown to Mode 4 was completed on January 13; 1987.

After corrective actions were taken to repair the

pump, OST-1087 was successfully completed and lA AFW Pump was declared operable at 0833 on January 17, 1987.

MEM/HO-8704000/PAGE 2/OS1

Corrective Ste s Taken to Avoid Further Noncom liance'.

CP&L will assure that OST test data is analyzed within 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> after the completion of a test.

This will be accomplished by the following steps:

aO OSTs will have acceptance criteria specified so that an analysis can be accomplished by the Shift Foreman when comparing the test results against the acceptance criteria.

b.

The ISI group will check the status of OSTs on a daily basis.

c.

The ISI group will review all test data to detect adverse trends and establish new reference values as required.

d.

The ISI group will review future OST schedules to be aware of upcoming required tests.

Plant management will continue to evaluate this matter and further improvements may be made.

Date When Full Com liance Was Achieved:

Full compliance was achieved on March 1, 1987.

MEM/HO-8704000/PAGE 3/OS1