Carolina Power & Light Company P.O. Box 101, New Hill, NC 27 JAN 2R P 2

~

January ll, 1985 Mr. James P. O'Reilly United States Nuclear Regulatory Commission Region II 101 Marietta Street, Northwest (Suite 2900)

Atlanta, GA 30323 NRC-312

Dear Mr. O'Reilly:

The purpose of this letter is to inform you of the status of corrective action being taken to resolve violation RII: GFM/RLP 50-000/83-37-01, "Failure to Control Electrical Cable Installation" and to establish a new projected full compliance date.

As previously reported, the Harris Plant Engineering Section has now issued design criteria to control past and future cable support within safety related panels.

Rework and reinspection has been accomplished for the majority of major safety equipment.

This rework consists of the removal of adhesive backed support bases and installation of approved support in accordance with the approved design criteria.

Efforts are still underway to identify and rework the remaining safety related equipment which may have unapproved cable support materials installed. It is now projected that full compliance will be achieved by April 15, 1985.

Thank you for your consideration in this matter.

Yours very truly, R. M. Parsons Project General Manager Completion Assurance Shearon Harris Nuclear Power Plant RMP/rt cc:

Messrs. G. Maxwell/R. Prevatte (NRC-SHNPP)

Mr. B. C. Buckley (NRC) 8507g70ygg 8~0~~~-~

QPDR ADOCK 05000400 l

PDR,.

K II Cl I

r t ~

I 1 ~

W

)

f