Provides Justification for 880129 Request for 24 H Discretionary Enforcement from Requirements of Tech Spec 3.0.1.Procedures Acceptance Criteria & as-found Values Fall within Allowable Value
ML17347A673
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 02/03/1988
From: Woody C
FLORIDA POWER & LIGHT CO.
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
L-88-54, NUDOCS 8802190052
Download: ML17347A673 (7)


Text

'I

,ACCELEMTED DI IBUTJON DEMONSTR TION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

'ACCESSION NBR:8802190052 DOC.DATE: 88/02/03 NOTARIZED: NO FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C AUTH.NAME AUTHOR AFFILIATION WOODY,C.O.

Florida Power

& Light Co.

RECIP.NAME RECIPIENT AFFILIATION GRACE,J.N.

Region 2, Ofc of the Director

SUBJECT:

Provides justification for 880129 request for discretionary enforcement from requirements of Tech Spec 3.0.1.

'DISTRIBUTION CODE-IEOlD COPIES RECEIVED:LTR + ENCL~ SIZE:

TITLE: General (50 Dkt)-Insp Rept/Notice of VioTation Response

NOTES

DOCKET 05000250 05000251 D

RECIPIENT ID CODE/NAME PD2-2 PD INTERNAL: AEOD NRR MORISSEAU,D NRR/DLPQ/QAB NRR/DREP/EPB NRR/DRIS DIR OE I'TIBEkgRMAN,J

~REG VJJ Kl RGN2 FILE 01

.EXTERNAL: LPDR NSIC COPIES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 RECIPIENT ID CODE/NAME EDISON,G DEDRO NRR/DLPQ/PEB NRR/DOEA DIR NRR/DREP/RPB NRR/PMAS/ILRB OGC/HDS2 RES/DRPS DIR NRC PDR COPIES LTTR ENCL 2

2 1

1 1

1 1

1 2

2 1

1 1

1 1

1 1

1 j

A 8

A

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 22 ENCL

P. 0 14000, JUNO BEACH, FL 33408.0420 FEBRUARY 3

1888 L-88-54 Dr. J. Nelson Grace Regional Administrator, Region II U. S. Nuclear Regulatory Commission 101 Marietta St.,

N.W., Suite 2900

Atlanta, GA 30323

Dear Dr. Grace:

Re:

Turkey Point Units 3 and 4

Docket Nos.

50-250 and 50-251 Re est for Discretionar Enforcement On January 29,

1988, Florida Power

& Light Company (FPL) requested a

24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> discretionary enforcement from the requirements of Technical Specification (TS) 3.0.1.

Following detailed discussions with the NRC

Staff, our request was granted and a written justification was requested to document the technical basis for the application of discretionary enforcement.

The purpose of this letter is to comply with this request as well as to provide the circumstances which brought this issue to our immediate attention.

On January 27,

1988, a

Management on Shift (MOS) observer noted that certain procedure requirements did not seem to be consistent with the Turkey Point TS.

The MOS observations were reviewed the next day and an action item was assigned to address the concern.

In the course of resolving the concern, a

review of instrument surveillance procedures for TS compliance was initiated.

This review identified instances where the surveillance procedures for instrument channels would allow the channel to be left in a

slightly nonconservative setting.

Although the setpoints for these channels were set as close as possible to the TS values, the procedures did allow for a tolerance around the specified value which would allow the channel to be left slightly on the nonconservative side of the TS required value.

Our preliminary investigation has determined that one or more of these procedure errors resulted from an incorrect determination that the TS value was a

nominal value which allowed application of a

tolerance band.

Because of the possibility of nonconservative

settings, the actual setpoints of the affected channels were reviewed.

'8802i90052 880203 DCD PDR ADOCK 05000250 PLP/001/MOS an FPL Group company z o/

Dr. J.

Nelson Grace Page two L-88-54 On January 29, 1988 it was preliminarily determined, based on these

reviews, that during the last surveillance, four of nine channels of the low low steam generator (SG) level were left slightly below the TS setpoint of greater than or equal to 15%.

Because two of these channels affected one SG, the minimum channels operable requirements of TS 3.5.1, Tables 3.5.1 and 3.5.2 could not be met.

Because no other action statement is provided for this condition, TS 3.0.1 was

entered, necessitating the unit to be in hot standby (mode 3) within 7

hours.

At this time, the NRC was contacted regarding the application of discretionary enforcement for the situation.

Justification For Continued Full Power 0 eration Not to Exceed 24 Hours FPL determined that a

24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> extension of TS 3.0.1.

is acceptable based on the following reasons:

1)

Each SG has three level transmitters that feed the reactor protection system and auxiliary feedwater (AFW) initiation logics.

The reactor trip and AFW automatic initiation logics for SG low low level is any two out of three channels indicating low low level on one out of three SGs.

The data from the last surveillance showed that three channels were set at 14.975%

and one channel was set at 14.954.

The as found settings of two channels on the 4B SG at 14.954 and one channel on the 4A SG at 14.925~

fall within the allowable values (greater than or equal to 14%)

provided by our NSSS vendor for the proposed upgrade TS.

The current TS trip setpoint for SG low low level is greater than or equal to 154.

2)

The power range flux low setting (less than or equal to 25%

power) which provides protection during reactor startup can be manually bypassed when two out of four power range channels reach the P-10 setpoint (10%)

of rated thermal power).

During a unit shutdown, three out of four power range channels reaching the P-10 setpoint automatically reinstates the trip function and enables the P-6 permissive to re-energize the source range channels.

During normal power operation the power range flux high setting (1094

power, actual setpoint of 108%

power) provides the reactor trip protective function on overpower condition.

The P-10 permissive does not provide any protective functions during normal power operation.

PLP/001/MOS

Dr. J. Nelson Grace L-88-54 Page three One channel (N-42) of the power range P-10 setpoint was indicated to be set slightly higher than the TS limit (104 rated thermal power).

The as found value of 10.5%

falls within the allowable values provided by our NSSS vendor for the proposed upgrade TS.

3)

Our current TS do not provide any action statements for this condition.

The TS upgrade project submittal for Turkey Point provides action statements that require the setpoint to be readjusted if it exceeds the trip setpoint but is within the "allowable value",

thus not requiring the channel to be declared inoperable.

These action statements are consistent with the standard technical specifications.

The "allowable value" is a

nominal allowance for setpoint drift between calibrations and has been used in several

. plant specific standard technical specifications.

Based on the above, it is FPL's determination that the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> extension of TS 3.0.1.

is justified since the procedures acceptance criteria and the as found values fall within the "allowable value" which our NSSS vendor has determined to be bounded by calculations used in the Turkey Point safety analysis.

Besides the SG level channels and the P-10 setpoint discussed

above, three other instruments had surveillance procedures which could have allowed nonconservative settings.

Each of these instruments was reviewed to identify the as found condition of the channels.

All of these were found to be in compliance with the TS settings.

The following corrective actions were taken:

The setpoints of the affected channels were rechecked, calibrated and the as found values recorded.

This action was completed within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of entering TS 3 ' '

'nstructions have been provided to the Instrumentation and Control (I&C) Department to ensure notification of the I&C supervisor prior to any maintenance on the affected instruments.

The affected procedures which allowed the nonconservative setpoints are being revised to ensure that the acceptance criteria falls within the limits provided in the current TS.

PLP/001/MOS

Dr. J. Nelson Grace L-88-54 Page four The results of the verification are shown in the attachment.

The attachment consists of a matrix showing the following:

1)

Affected Instruments 2)

Current TS Values 3)

Precaution, Limitation, and Setpoint Values 4)

Surveillance procedure acceptance criteria 5)

NSSS Vendor "Allowable Value" 6)

As Found Data 7)

As Left Data This letter has been reviewed by the Plant Nuclear Safety Committee.

Should you or your staff have any questions on this information, please contact us.

Very truly yours, le

c. o.

ody Executive Vice President COW/PLP/JA/gp Attachments cc:

Document Control Desk, USNRC Senior Resident Inspector, USNRC, Turkey Point Plant PLP/001/MOS

ATTACHMENT INSTRUMENTS SUBJECT TO NONCONSERVATIVE TOLERANCES Instrument T.S.

Value PLS NSSS Procedure "Allowable Value" As Found As Left

S/G Lo-Lo Level II A S/G 8474 B S/G 8484 C S/G f494 A S/G 4475 B S/G

$ 485 C S/G 4495 A S/G 0476 B S/G 4486 C S/G 4496

>154 154 154 +.254

>144 15.025 14 '50 15.000 15.000 14 '50 15.025 14.925 15 '75 15.050 15.175 15.175 15.200 15.175 15.175 15.200 15.175 15.200 15.200 Turbine Trip (Auto Stop Oil Pressure)

<45 psig 45 44-46 psig psig

>40 psig 45 dec* 45 dec*

Power Range Neutron Flux-Low

<25%

25%

24-264

<26%

<25%

<254

'Power Range Neutron Flux Interlock P-8 Low Setpoint Neutron Flux Interlock P-10 N-42

<454 45%

44-464 104 104 9-114

<46%

<454

<45%

>94,<114'0.54 10%'

The turbine trip is set to trip at 45 psig and decreasing.

The as found value is conservative with respect to the current TS value.

PLP/001/MOS