ML17341A823
| ML17341A823 | |
| Person / Time | |
|---|---|
| Site: | Turkey Point |
| Issue date: | 01/18/1982 |
| From: | FLORIDA POWER & LIGHT CO. |
| To: | |
| Shared Package | |
| ML17341A822 | List: |
| References | |
| NUDOCS 8201250418 | |
| Download: ML17341A823 (15) | |
Text
3.0 LIMITING CONDTIONS FOR OPERATION Appl icabi 1 ity 3.0.1 If one of the below listed limiting conditions for operation can not be satisfied because fewer components are operable than are
- required, the unit shal I
be placed in hot shutdown within seven hours and cold, shutdown within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> unless appropriate corrective action is taken before the time expires.
This specification applies only to specifications 3.3.1, 3.4.1.b, 3.4.2.b, 3.4.3.b, 3.4.4.b, 3.4.5.b, 3.4.6.b, 3.4.7.b, 3.5, 3.6.d, 3.7.2 and 3.13.3.
3.0.2 For purposes of determining if a component is operable for LCO considerations, the component need not be considered inoperaole
,due to inoperability of its normal or emergency power supply if all of its redundant components are operable with thei r normal or emergency power supplies operable.
3.0-1 1-18-82
III l
1.
ONE emergency containment cooling unit may be out of service for a period of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
Prior to initiating maintenance the other TWO units shal I
be tested to demonstr ate operability.
2.
ONE containment spray pump may be out of service provided it is restored to operable status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
The remaining containment spray pump shall gabe tested to demonstrate operability before initiati'ng maintenance of the inoperable pump.
3.
Any valve in the system may be inoperable provided repairs are completed within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
Prior to initiating repairs, all valves that provide the duplicate function shall be tested to demonstrate operability.
EMERGENCY CONTAINMENT FILTERING SYSTEM a.
The reactor shall not be made critica'I, except for low power physics tests unless:
1.
THREE emergency containment filtering units are operable.
2.
All valves, interlocks and piping associated with the above components and required for post-accident operation, are operable.
b.
During power operation:
1.
ONE unit may be inoperable for a period of 7 days if the other TWO are operable.
2.
Any valve in the system may be inoperable provided repairs are'completed within 7 days.
Prior to initiating maintenance, all valves that provide the duplicate function shall be tested to demonstrate operability.
3.
-If after 7 days the unit is stil I inoperable Specification 3.0.1 applies to 3.4.3.b.
4.
COMPONENT COOLING SYSTEM a.
The reactor shall not be made critical, except for low power physics tests, unless the following conditions are met:
1.
THREE component cooling pumps are operable.
2.
THREE component cooling heat exchangers are operable.
3.
All valves, interlocks and piping associated with the above compone'nts are operable.
3.4-4 1-18-82
"g A
b.
During power operation, the requirements of 3.4.4.a may be modified as stated below.
If the system is not restored to meet the conditions of 3. 4.4.a within the time period specified, the reactor shall be placed in the hot shutdown condition.
If the requi rements of 3.4.4.a are not satisfied within an additional 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />, the reactor shall be placed in the cold shutdown condition.
Specification 3.0. 1 applies to 3.4.4.b.
1.
ONE pump may be out of service for 7 days.
2.
ONE additional pump and ONE heat exchanger may.be out ot service for period of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
5.
INTAKE COOLING WATER SYSTEM a.
The reactor shall not be made critical.unless the following conditions are met:
1.
THREE intake cooling water pumps and TWO headers are operable.
2.
All valves, interlocks and pipi'ng associated with the operation of these
- pumps, and required for post accident operation, are operab'le.
b.
During power operation, the requirements of 3.4.5.a.,
- above, may be modified to a'liow any one of the fol,lowing components to be inoperable provided the remaining systems are in continuous operation.
If the system is not restored to meet the requirements of 3.4.5.a.
within the time period specified, the reactor shall be placed in the hot shutdown condition.
If the requi rements of 3.4.5.a are not satisfied within ani additional 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />, the reac or shall be.placed in the cold shutdown condition.
Specification 3.0.1 applies to 3.4.5.b.
1.
One of the two headers may be out of service for a period of. 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> s.
2.
One intake cooling water pump may be out of service for a period of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
3.4-5 1-18-82
6.
POST ACCIDENT CONTAIWENT VENT SYSTEl1 a.
The reactor shal;i not be made critical, except for low power phys i cs tests.
un I es s:
1..
The post accident containment vent system is operable.
2.
All valves, interlocks, and piping associated with the above components and required for post-accident operation are operable.
b.
During power operation:
1.
The unit may be inoperable for a period of 7 days.
2.
Any valve in the system may be inoperable provided repairs are compl,eted within 7 days.
Prior to initiating maintenance, all val'ves that provide the duplicate function shall be tested to demonstrate operability.
3.
If after 7 days the unit is still inoperable, Specification 3.0. 1 applies to 3.4.6.b.
7.
CONTROL ROOM VENTILATION a.
The reactor shall not be made criti'cal, except ror low power physics tests un'less; 1.
The control room ventilation system is operable.
2.
All valves, interlocks, and piping associated with the above components, and required d'or, post-accident
,operation are operable.
b.
During power operation:
1.
The unit may be inoperable for a period of 3 1/2 days.
2.
Any valve in the system may be inoperable provided repairs are completed within 3 1/2 days.
Prior to initiating maintenance, all valves that provide the duplicate function shall be tested to demonstrate opera bi 1 ity.
3.
If after 3 1/2 days the unit is still inoperable, Specification 3.0.1 applies to 3..4.7.b.
3.4-6 1-18-82
4.7 EMERGENCY CONTAINMENT FILTER SYSTEM, POST ACCIDENT CONTAINllENT VENT
- SYSTEM, AND CONTROL ROOM VENTILATION SYSTEM.
~Aplicability:
Applies to the Emergency Containment Filter System, the Post Accident Containment Vent System, and the Control Room Ventilation System.
Objectives:
To verify that these systems and their components will be able to perform their design t'unctions.
In the event that painting, tire, or chemical re'lease occurs such that the filters are exposed to the effluents of these
- events, the system will be tested to verify its performance ot'esign t'eatures.
Specification:
1.
EMERGENCY CONTAINMENT FILTER SYSTEM 1.
~0 crating Tests System tests shall be performed once per operating cycle or once per 18 months, whichever comes tirst.
The tests shall consist ot pressure drop and tlow measurements across all filter banks in the plenum.
Less than 6" of water pressure drop at design tlow (37,500 cfm +
10K) across the combined HEPA filter and charcoal adsorbers shall constitute acceptable performance.
Visual i nspection shall include search for any toreign material and gasket deterioration of the HEPA filters and charcoal adsorbers.
g.g-l 1-18-82
Once per operating cycle, each unit of the Emergency Containment Filtering System shal l be tested to demonstrate automatic initiation upon receipt of a Safety Injection signal.
Each unit of the Emergency Containment Filtering System shall be operated monthly for at least 15 minutes on a staggered basis to demonstrate operabi 1 ity.
- 2. Performance Tests a 0 b.
A visual inspection shall be made before each in-place air flow distribution test, DOP test or halogenated leak test.
At least once per 18 months.or after every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of system operation, in-place DOP and halogenated hydrocarbon tests at design flow. (37,500 cfm +
10K) and carbon analysis for each Emergency Containment Filter plenum shall be performed.
'In addition, carbon analysis and in-place
- DOP, and halogenated hydrocarbon tests at design flow
'(37,500 cfm + 10K) shal l be performed after (1) any structural maintenance on system
- housings, which. might have affected t',ilter bank efficiency, (2) after complete or partial replacement of a filter bank, or (3) after operational exposure of the i'ilters to effluents from painting, fire, or. chanical release.
Removal of > 99/
DOP and
> 99', halogenated hydrocarbon shall constitute acceptable performance.
Fans shall operate at design flow (37,500 cfm + 10/).
The charcoal surveillance specimen from one of the emergency containment filters shall show
> 99.9$ removal efficiency for elemental iodine.
Samples will be taken in accordance with position C.6.b of Regulatory Guide 1.52.
Carbon analysis will be performed in accordance with ANSI.N510-1975.
Analysis shall verify the above removal efficency for elemental iodine withi n 45 days after removal of the sample.
Failing this, the charcoal shall be replaced with charcoal which meets or exceeds the criteria of position C.6.a of Regulatory Guide 1.52 (Revision 2).
An air distribution test shal I
be performed at design flow (37.,500 cfm + 10',) at least once after maintenance affecting flow distribution.
co Flow rate should be verified following maintenance to HEpA or charcoal housing, or fol lowing painting or chemical release in its ventilation zone while the system is operating, or once each 18 months.
1-18-82
~ ~
'I
POST ACCIDENT CONTAINHENT VENT SYSTFH 1.
Operating Tests Operating tests shall be performed during refueling but not longer than 18 months.
The tests shall consist of visual inspection of the system, operation of alI valves, and pressure drop and air flow measurements.
Visual inspection shaII include a search for any foreign materials and gasket deterioration in the HEPA filters and charcoal adsorbers.
Less than 6" of water pressure drop at 55 cfm flow sha'll constitute acceptable performance.
2.
Performance Tests a.
A visual inspection of the system shall be made before each DOP test, halogenated hydrocarbon leak test, and upon completion of the above tests when the system is installed in its opei.ational status in the auxiliary building.
At least once per 18 months or after 72U hours of system operation, in-p'Iace UOP and halogenated hydrocarbon tests at design flow (55 cfm + 105) and
.carbon analysis, or carbon replacement, tor the Post Accident Containment Vent filters shai'I be performed.
In addition carbon analysis (or carbon replacement),
DOP, and halogenated hydrocarbon tests at design flow (55 ctm +
10%%d) shall be performed after
( 1) any structural maintenance on system housings.
Which might have affected filter bank efficiency, (2) at'ter complete or partial replacement of a filter bank or (3) after exposure of the filrers to et'fluents from painting, fire or chemical release.
RemovaI of > 99$
DOP and
> '.i9f'alogenated hydrocarbon shall constitute acceptable performance.
b.
Laboratory carbon sample, analysis shall show
- 90K, methyl radio-iodine removal or the charcoal shaII be r "placed with charcoal that meets or exceeds the criteria of position C.6.a of Regulatory Guide 1.52 (Revision 2).
The sample shalI be taken in accordance with position C.6.b. of Regulatory, Guide 1.52.
Carbon analysis shall be performed in accordance with ANSI N510-1975.
Analysis shall verify the above removal efficiency for radioiodine within 45 days after removal of the sample.
c ~
The hydrogen concentration measurement instrument shall be calibrated with proper consideratiun for hum>dity.
- 4. 7-3 1-18-82
3.
CONTROL ROOM VENTILATION (fMERGENCY INTERNAL CLEANUP SYSTEM 1.
A visual inspection shall be made before each in-place DOP
- test, hydrogenated hydrocarbon leak test, and airflow distribution test.
The Control Room Ventilation System shali be operated monthly for at least 15 minutes to demonstrate operability.
Auto initiation of the systems operations shaii be checked during refueling, but not ionger than
'lU months.
Pressure drop measurements across the fi'lter bank shall be made annually.
Less than 6" of water pressure drop at designed flow ( 1,000 cfm + 105) across the combined HEPA tilter and charcoal adsorb=rs shall constitute acceptaole performance.
A visual inspection shall include a search for any foreign materials and gasket deterioration in the HEPA filters and charcoal adsorbers.
2.
Performance Tests b.
A visual i nspection shall be made before each in-place DOP test, halogenated hydrocarbon leak test, and airflow distribution test.
At least once per 18 months or after every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of system operation, in-p'lace DOP and halogenated hydrocarbon tests at design flow (1,000.cfm + 10$ ) and carbon analysis shall be performed.
In addi tion', carbon analysis (or carbon replacement) i n-place DOP.
and halogenated hydrocarbon tests at design flow (1,000 cfm + 10$,) shall be performed aft=r (1) any structural maintenance on system
- housings, which might have affected tilter bank efficiency, (2) after complete or partial replacement of a filter bank, or (3) after operational exposure of the filters to effluents from painting, fire, or chemical release.
Removal of > 99$
DOP and
> 99$
halogenated hydrocarbon shall constitute acceptable performance.
A charcoal surveillance specimen trom one of the charcoal adsorbers shai.l be removed and analyzed for methyl radio-iodine removal capability.
The results of the laboratory carbon sample analysis shall show
> 90$
methyl radio-iodine removal efficiency.
Samples shali be taken in accordance with position C.6.b of Regulatory Guide 1.52.
Carbon analysis shall be performed in accordance with ANSI.N510-19/5.
Analysis shall verify the above removal eft'iciency for methyl radio-iodine within 45 days after, removal of the sample.
Failing this, the charcoal shall be replaced with charcoal which meets or exceeds tne criteria of position C.6.a of Regulatory Guide 1.52 (Revision 2)
Co, System flow rate should be verified once each 18
- months, following maintenance to HEPA or charcoal
- housings, or fire, or chemcial rel'ease in its ventilation zone while the system is operating.
4.7-4 1-18-82
~i
)
(4
84.7 BASES FOR EMERGENCY CONTAINMENT FILTERING SYSTEM, POST ACCIDENT CONTAINMENT VENT SYSTEM, AND CONTROL ROOM VENI'ILATION SYSTEM.
System components are not subject to rapid deterioration, having lifetimes of many years, even under continuous flow conditions.
Visual inspection an operating tests provide assurance of system reliability and will insure early detection of conditions which could cause the system to fail or operate improperly.
The performance tests prove conclusively that filters have been properly instal led, that no deterioration or damage has occurred, and that all components and subsystems operate properly.
The tests are performed in accordance with the methodology and intent of ANSI N510 (1975) and provide assurance that filter performance has not deteriorated below required specification values due to aging, contamination, d'or other effects.
84.7-1 1-18-82
~t 1'