Environ Qualification of Safety-Related Electrical Equipment,Ie Bulletin 79-01B, Technical Evaluation Rept
ML17340B286
Person / Time
Site: Turkey Point NextEra Energy icon.png
Issue date: 10/28/1980
From: Ruff A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML17340B284 List:
References
IEB-79-01B, IEB-79-1B, NUDOCS 8106010424
Download: ML17340B286 (95)


Text

ENVIRONMENTAL QUALIFICATION OF SAFETY"RELATED ELECTRICAL EQUIPMENT IEB 79-01B TECHNICAL EVALUATIONREPORT DOCKET NO. 50"250 PLANT:

Turkey Point 3 DATED:

October 28, 1980 Licensee:

Florida Power and Light Company Type Reactor:

Westinghouse PWR Prepared by:

A Ruff Engineering Support Section Reactor Construction and Engineering Support Branch, RII s i06 o zo9'/.,

r'>> f '4

TABLE OF CONTENTS PAGE NO.

1.

INTRODUCTION.......

1.1 General 2.

BACKGROUND AND DISCUSSION................

2.1 2.2 2.3 General..................

On-Site Inspection...

Evaluation of I,icensee's Report 1

2 2

3.

GENERAL INFORMATION.. ~........

~

~

~

~

3 3.1 Identification of Class lE Electrical Systems.

3.2 Service Conditions 3.3 Qualification Documentation..

3 4

4 4.

EQUIPMENT DATE REVIEW..............

~

~

~

~ ~

~ ~

~

~ ~

~

~ ~

~

~

~

~

5 4.1 4.2 4.3 4.4 4.5 4.6 4.7

~

~ ~

~

~

~

~

5 5

- Licensee 5

5 5

6 6

Qualified Equipment Equipment With Aging Less Than Plant Life...

~

Equipment to be Replaced, Modified, or Relocated Identified....

~

~

~

~

~ ~

~ ~

~

~

~

~

~

~

~

~

~

Equipment with Unresolved Qualification Items Equipment Not Qualified.......................

Outstanding Items - I,icensee Identified Discussion of On-Site Inspection...

5 ~

CONCLUSIONS

~

~

~

~

~

~

~

~ ~

~

~

~ ~

~

~ o ~

~

~ ~

~

~

~

~

~

~

~

~

~

~

~

~

~ ~

~

~

~

~

~ ~ ~

~

~

~

~

~

6 Attachment 1

Attachment 2

Attachment 3

Attachment 4

Review Tabulation Sheets Used in Evaluation of Licensee's Report List of Standard Systems List of Documents That Support Environmental Qualifica-tion of Licensee's Equipment Outstanding Items (Licensee Identified)

T

1.

INTRODUCTION 1.1 General The NRC Office of Inspection and Enforcement (I/E) issued Bulletin 79-01B, "Environmental Qualification of Class 1E Equipment" in January 1980.

This bulletin required the licensee to perform a detailed, evaluation of the environmental qualification on Class lE electrical equipment required to function under postulated accident conditions and to submit a report on this action.

This document is a report on the evaluation of the licensee's response to this bulletin.

2.

BACKGROUND AND DISCUSSION 2.1 General The evaluation of the licensee's response was accomplished by performing an on-site inspection of selected class 1E equipment and by examining the licensee's report for completeness and technical accuracy.

The licensee's reports used in this evaluation are dated July 3, 1980, and therefore, does not include the response to the bulletin supplement which was issued on 9/30/80 in the form of Generic Questions and 0

Answers.

2.2 On-Site Ins ections The on-site inspection, made on selected 1E equipment, verified proper installation of equipment, overall interface integrity, location with respect to flood level for equipment inside the containment, and manu-facturers nameplate data.

The manufacturer and model number from the nameplate data was compared to information given in the Component Evaluation Work Sheets (CES) of the licensee's report.

Components that were examined during the field inspection are identi-fied by a Delta (W) in Attachment 1. If any discrepancies were noted between the installed equipment and the correspondent equipment addressed in the licensee's

report, they are discussed in Section 4 of this report.

The site inspection is documented by report number 50-250/80-18 of October 29, 1980.

2.3 Evaluation of Licensee's Re ort Each component as addressed on the Component Evaluation Work Sheets (CES) of the licensee's report was examined for completeness and accuracy to the criteria given in the bulletin.

This examination assumed qualification documents (analysis, test reports, etc.) referenced by the licensee in their submittal are acceptable.

The results of this examination are documented in Attachment 1.

The CES page numbers in column 1 of Attachment 1 is the same CES page found in the licensee's report.

3.

GENERAL INFORMATION 3.1 Identification Of Class 1E Electrical Equipment The licensee's list of systems was compared to the systems listed on Attachment 2.

This list is considered to be a

standard list for Westinghouse NSSS PWR reactors.

0 It is recognized that there are differences in nomenclature of systems because of plant vintage and engineering

design, therefore, many of these systems may not exist for Turkey Point 3 plant or the function of these systems for the Turkey Point 3 plant may be performed by comparable systems with different names.

In any case, all the systems of Attachment 2 were not addressed or listed in the licensee's report.

To insure completeness and uniformity of reports of similar design, it is considered that the licensee should address the following systems:

(a)

Feedwater Control (b)

Containment Spray (c)

High Pressure Injection (d)

I.ow Pressure Injection (e)

Accumulators (f)

Pressurizer Spray (g)

Power Operated Relief Ualves (h)

Steam Dump

(i)

Containment Sump (j)

Safety Equipment Area Ventilation Each of the above systems should be analyzed and a brief discussion should explain how the system was addressed or why it was excluded from the report.

For example:

"Reactor Protection System - This is a

valid system designation at Turkey Point 3 plant; however, the input signals to this system are obtained from various components in other systems that are included in this report."

3.2 Service Conditions The service condition accident environment, HELB/LOCA inside contain-ment and HEIB outside containment are indicated or discussed in the licensee's report and are based on the FSAR accident analysis.

3.3 uglification Documentation Attachment 3 is list of documents (test reports,

analysis, letters, etc.) used by the licensee in determining the environmental qualifica-tion of plant equipment for Turkey Point.

These references have been tabulated by the licensee and are indicated on the applicable CES of their report.

I

4.

EQUIPMENT DATA REVIEW 4.1 Equipment that is considered to meet IEB 79-01B requirements are categorized as 1 in the last column of Attachment l.

4.2 Equipment whose qualified life (Aging) is less than the life of the plant is categorized as 2 in the last column of Attachment 1.

4.3 The licensee has identified specific equipment which has been or is being replaced, modified or relocated as a result of their IEB 79-01B efforts.

This equipment is categorized as 3 in the last column of Attachment l.

4.4. Equipment whose qualification is unresolved (such as, a qualification record search is still in process, tests are scheduled to determine qualification, additional information is needed by the NRC reviewer to satisfy him that equipment is qualified, etc.) is categorized as 4 in the last column of Attachment 1.

4.5 Equipment that the licensee has identified as not being capable of meeting environmental qualification requirements for service intended required a"Iicensee Event Report" (LER).

No IZR's with regard to IEB 79-01B actions were received in Region II.

I 4.6 Equipment whose qualification (Aging exempted to a certain degree see DOR guideline Section

4) is unresolved, as identified by the licensee is listed in Attachment 4 as Outstanding Items.

The licensee has provided justification for continued plant operation for many, if not all, of these outstanding items in their report.

In many cases, this is provided on their CES or in a" special section of the report.

In some cases the licensee states that this justification is by Engineering Analysis that are available at their office.

4.7 No differences were noted between the data obtained during the on-site inspection and the data listed on the CES of the licensee report.

Equipment that was examined during the on-site field inspection are identified by an asterisk (-) in Attachment 1.

5.

CONCLUSIONS Due to the time constraints imposed by the Commission Memo and Order of 5/28/80 this evaluation is based on the licensee submittal dated July 3, 1980.

This licensee's report does not address all items that may be pertinent to Turkey Point 3 plant as a result of a bulletin supplement issued on 9/30/80.

This bulletin supplement, in the form of Generic Questions and Answers, was the result of regional meetings with licensees during the week of July 13, 1980.

Any additional information received as a

result of this supplement willbe evaluated by the EQB of NRR.

I

'I

The licenssee's actions meet the requirements of the Commission Memo and Order of 5/28/80 and justification for continued plant operation with many of the components that have unresolved qualification items is indicated in Section 4.6.

Based on the information available, the Region II reviewer considers that the justification is commensurate for the areas identified, that the proposed corrective action meets requirements of the Commission Memo and Order of 5/28/80, and therefore, plant operation can continue until these items are resolved as committed to by the licensee.

This evaluation is based on the on-site inspections, the information supplied by the licensee in their submittal, their CESAR, and the assumption that the qualification Documents (Test Reports, Analysis, Ietter, etc.) are acceptable.

The results of this evaluation does not necessarily imply that the equipment in unreliable, unsafe or represents a significant safety issue; it does imply that additional information is required.

This is indicated by the applicable categorization indicated in the last column of Attacbment l.

yhCILLTY SYSTEM h'! rhcHHENT 1

FOR IEB 79-0)B TER PAPE~ PP~

CES P Page Moo EquipP I.

DP I

Generic Name hccid Profile

Qual, Regia)iyn )upi.

p fil n a nm n Inside Outside Qual.

Chem.

Hethod Spray hccur.

Licensee hction Replace Relocate Outstanding Cstesory Items oF Identified by Items Py 3a

.e p

T C.7 7P f~ Je

/

yr 3 Cods:

B Mor S

-or li UL P

L R

1 2

~ Indicates the item is below the flood level Indicates the item is Satisfactory

~ Indicates the item is Hot hpplicable

~ Indicates the item is Unresolved, Licensee identified

~ Proprietary

~ Licensee identified

~ Reviewer identified

~ Equipment is qualified

~ hging is less than life of plant with licensee indicating periodic replacement 3 ~ Equipment requires modification (resolutionP shielding, etc.)

4 ~ Qualification of equipment unresolved a)

Testing schedule but not complete b)

Reviewer needs additional information c)

Qual. Record search still in process 5 ~ Equipment not qualified 6 i Item identified to EQB for resolution PPPPPPPR ~M~'<

PPPe

'I

FACILITY 7 k

P Z '"0- P~">

SYSTEM ATTAQIHENT I FOR IEB 79-OIB TER PAPE~ QP~

CES.

Page No A Equip.

I. D.

re-s-18 T'E Generic Name hccid.

Profile Qual.

Profile Inside P

I-'utside Raga)iyn )u)l.

Qual.

Method Ch~.

Spray hccurQ Subm.

Licensee Action Replace Relocate Outstanding Items Identified by Category ot Items HoV rAOV I-3 o

7K 2

Code:

B Mor S

-orN UL P

L R

1 2

QQ Indicates the item is below the flood level QQ Indicates the. item is Satisfactory QQ Indicates the item is Not Applicable QQ Indicates the item is Unresolved, Licensee identified

~ Proprietary

~ Licensee identified EQ Reviewer identified

~ Equipment is qualified QQ Aging is less than life of plant with licensee indicating periodic replacement 3

QQ Equipment requires modification (resolution, shielding, etc.)

4 Qualification of equipment unresolved a)

Testing schedule but not complete b)

Reviewer needs additional information c)

Quail Record search still in process 5 ~ Equipment not qualified 6 ~ Item identified to EQB for resolution REVIEWER DhTE

EhCLLITI v'Aw SYSTEM

'"o-Pa f)

Z~p~

hTThCHHENT I FOR IEB 79-OIB TER PAGE~ OP~

CESG Page Noo Equipo I

D.

5y Generic hccid.

Name Profile Qual.

Profile Inside Outside Ra/la)iyn )u~l.

Qual.

Method Chem.

Spray hccur' Subm.

Licensee hction Replace Relocate Outstanding Items Identified by Category Ot IteEEs A(

gV'h cv-a 5G' onR C V~3/I S)P-a D

4)A' OO(

sv-a s

C.

HC V Code:

B Wor S

-orN

~

UL P

L Rl 2

GG Indicates the item is belov the flood level GG Indicates the item is Satisfactory GG Indicates the item is Not hpplicable GE Indicates the item is Unresolved, Licensee identified

~ Proprietary GG Licensee identified

~ Reviever identified

" Equipment is qualified.

~ hging is less than life of plant vith licensee indicating periodic replacement t

4i( J( ~, r P

V'A.. ~~

~(.-P E

I;.(

III ( '~

(tl( II G0 A

( ( IPG/P

/)g J(g

/ (((

~

/$

%$/gn" G'4,"n'.

7 REVIENER CS DhTE 0

3 ~ Equipment requires modification (resolutiono shielding, etc.)

4 " Qualification of equipment unresolved a)

Testing schedule but not complete b)

Reviever needs additional information c)

Qual.

Record search still in process 5

GG Equipment not qualified 6 ~ Item identified to EQB for resolution

FAOILITI 4

Pa i'a8 SYSTEM b

)~+el ATTACHMENT I FOR IEB 79-OIB TER PAGE~ OP~

GEST Page Noo Equip.

Io Do If'sC-

>ra l.C-I=1=3.

Ceneric Name hccidi Profile Qual.

Profile Inside Outside Regia)iran ]u[1.

Qual.

Method Chem ~

Spray hccur.

Subm.

Replace Relocate Licensee Action Outstanding Catesory Items of Identified by Items 4-3P PS 3 P

5'.

5 H3 2ol pS-o-0 Codes B

Wor S

-orN UL P

L R

I 2

~ Indicates the item is below the flood level

~ Indicates the item is Satisfactory

~ Indicates the item is Not Applicable

~ Indicates the item is Unresolved, Licensee identifi

~ Proprietary

~ Licensee identified

~ Reviewer identified

~ Equipment ia qualified

~ Aging is less than life of plant with licensee indicating periodic replacement P

REVIENIIC w

~ ~ 'll'M~~l

~ p 3 ~ Equipment requires modification (resolution, shielding, etc.)

4 ~ Qualification of equipment unresolved s)

Testing schedule but not complete ed b)

Reviewer needs additional information c)

Qual. Record search still in process 5 ~ Equipment not qualified 6 ~ Item identified to EQB for resolution

PACILLTV k

ssad 0<<2+0 SYSTEH dg t-P l ATTACHMENT I FOR IEB 79-OIB TER PAGE~'F~

CES ~

Page No+

Equipo I. D.

]

Generic Accid.

Name Profile Pjr !8~

C W~.~

~

Qual, Profile Regia)i~n fugal.

Inside Outside Qual.

Hethod Chen.

Spray hccur.

Subm.

Replace elocate Licensee hctioa Outstanding Catesory Items oF Identified by Items

.pD Code:

B Wor S

-orN UL P

L RI 2

~ Iadicstes tha iten is below the flood level Indicates tha-item is Satisfactory Indicates the iten is Not Applicable Indicates the iten is Unresolved, Licensee identified

~ Proprietary

~ Licensee identified

~ Reviewer identified Equipment is qualified

~ Aging is less than life of plant vith licensee indicating periodic replacement 3 ~ Equipment requires modification (resolution, shielding, etc.)

4 ~ Qualification of equipment unresolved a)

Testing schedule but not complete b)

Reviewer needs additional information c)

Qual. Record search still in process 5 ~ Equipment aot qualified 6 ~ Item identified to EQB for resolution IIEv!ENER ~cP DATE ~!! " Ng p'/

(

1'hCILLTI SYSTEM Pn)s l 8 g~ gS'0 hTThCHMENT 1

/P yg

/

FOR IEB 19-01B paaE I

or '/

CES ~

Page Ho+

Equip.

I'.

PT-'3-5'90 Generic hccid.

Hame Profile Qual Profile RaLia)i~n )u~l.

Inside Outside Qual.

Method Chem.

Spray hccur.

Subm.

Licensee hction Replace Relocate Outstanding Items Identified by Category ot Items FT'-

-z3 P2/d 4 p/og Jul/

)OV+

0 afaV <LP P

Code:

B Wor S

-orH UL P

L R

1 2

~ Indicates the item is below the flood level

~ Indicates the item is Satisfactory

~ Indicates the item is Not hpplicable

~ Indicates the item is Unresolved, Licensee identified

~ Proprietary

~ Licensee identified

~ Reviewer identified

~ Equipment is qualified

~ Aging is less than life of plant with licens'ee indicating periodic replacement 3 ~ Equipment requires modification (resolution, shielding, etc.)

4 ~ Qualification of equipment unresolved a)

Testing schedule but not complete b)

Reviewer needs additional information c)

Qual.

Record search still in process 5 ~ Equipment not qualified 6 ~ Item identified to EQB for resolution

/

r'avrneR

~~'ata

I I

FACILITY SYSTEH A".TACHNEHT 1 FOR IEB 79-OIB TER PAGE~ OP~

CES, Page No>>

Equipo I

D t

Af)V~ge Generic Accid.

Name Profile Qual.

Profile Ra/is)iyn )u~l.

Inside. Outside Qual.

Chem.

Hethod Spray Accurse Subm.

Licensee Action Replace elocate Outstanding Items Identified by Category oy I'terna u+ p-g P p,/gg nv ov 3 e v fV.P Code:

B Wor S

-orN UL P

L R

1 2

~ Indicatea tha item is below the flood level

~ Indicates the item ia Satisfactory

~ Indicates the item is Not Applicable

~ Indicates the item is Unresolved, Licensee identified Proprietary

~ Licensee, identified

~ Reviewer identified Equipment is qualified

~ Aging is less than life of plant with licensee indicating periodic replacement 3 ~ Equipment requires modification (resolution, shielding, etc.)

4 ~ Qualification of equipment unresolved a)

Testing schedule but not complete b)

Reviewer needs additional information c)

Qual. Record search still in process 5 ~ Equipment not qualified 6 ~ Item identified to EQB for resolution IUIVIEMER

~

~

ATE~Nb

I

(

EAUCLL'iC ain 3'y-g8 P x ~pard Al rhl:tNENy 1

FOR lE5 19-Oil egg tlQR Q

Ot b'ES

~

Page Hei Equips I~

Do Generic Rane Accidi Profile

'/usia Profile Inside Outside RaIBtia)iqn gu(li Qual.

Hathod CIILao Spray Replace elocate Accur.

Suba Licensee Action Outstanding lteas ldentifie4 by Category ot ltees htoV 147'ph ihOV P7E htDV hfpV AQV g-y ggp4 kf 0 V b'av-3.

Mt Flea AAUV 10)p oV NAY-3 PC -3 3-A R-3 "

ol Pc-Co e:

g Wor S

-ur ll UL P

L R

1 2

S~rc w

~ Indicates chs icea is belov the flood level

~ indicates Che iten is Satisfactory

~ indicates chs itea is Nut Applicable

~ indicates che iten is Unresolved, Licensee identified

~ Proprietary

~ Lic<<nuue idencific4

~ Ruvieuer id<<ntifled

~ Equipa<<nt lu qualified

~ Aging Lv 1<<us chan life of plant ulth licensee indicating perio4ic replaceaent 3 ~ Equipaent requires aodificacion (resolucioa, ahieldiag, etc.

4 ~ Qualification of equipnent unresolve4 a)

Testing schedule buc noc coeplete b)

Ruviever needs additional inforaatioa c)

Qual.

Record search still in process 5 ~ Equipment not qualified 6 ~ ltea identified to Eqg for resolution REV1EME sag

FAULLitt V~ a Pdih ( 8 4 P SYSTEH SW Pf0 A1TACNNEÃf l FOR 1ER 79-Olg TER

CES, Page Hoi Equip.

1.

Da Cenerfc Hase Accid.

Profile Qual.

Proflie inside Outside Ra/la)fqn qual, Qual Hetbod CllCQs Spray Replace elocate Accur.

Subs.

Licensee Actioa OllCatanding.

Oateeory Icesa oF Identified by ltesa g 0 7 o7 45-3" s 3 n<

EO@a y" gt Cu e:

B Wor S

-orH UL P

L R

1 2

~ 1ndfcates the iten fa belou the flood level

~ indicates che fees fa Satisfactory

~ lwdicaces che iten ia Noc Applicable

~ 1ndicutus the fees is Unresolved, Licensee identified

~ Proprietary

~ Licensee fdentfffcd

~ kuvfcucr id<<ntffied

~ Equfpscnc iu qualified

~ Aging is less than life of plant ufth licensee fndicatfng periodic replacescnc 3 ~ Equfpnent requires aodfficatfon (rasolutfoa, abfelding, atco 4 ~ Qualification of equipsenc unresolved a)

Jesting schedule buc noc cosplete b)

Revievcr needs additfonal inforwacfoa c)

Qual. Record search still in process 5 ~ Equfpmeuc not qualified 6 ~ iten idencfffed to EQB for reaolutfon I

REV1EUER 4 DAta LED

~

~

FRULLiTT SYSTEIf C7 h'IThCRRENT l FOR 1ER )9-01S TEIL um~ ov C

CES, Psgs Ro, Kquipo
l. Do

]

Generic hccid.

Rane Profile Qual.

Proflie Rags)iqn )u~l.

Inside Outside

Qual, IIethod Chca.

Spray hccure Suba.

Replace elo cate Liceaaee kctioa Outstanding leans Idcatifisd by Category oy lteaa SV-Q-

$V-g SV 5)' cV-3 gg/o C'V-3

/

CV"3" Cu e:

R Wor S

-urN UL P

L R

1 2

~ indicates che icea is belov the flood level

~ indicates che ices is Satisfactory

~ 1wdicac< R<<vicuer id<<atified

~ Equips<<nc is qualified

~ hglng is less then life of plant vith licensee indicac.ing periodic replacesent uvavma cP

~

~m J~~

3 ~ Kquipseac requires aodification (resolution, shielding, etc.

4 ~ Qualificacion of equipsent unresolved a)

Testing schedule but not cosplete b)

Reviever needs addicional inforsatioa c)

Qus)..

Record search still in process 5 ~ Equipsent not qualified 6 ~ ltea identified to EQR for resolution ri,,( (/>>, '..g

(

k'

~k SYSTEM CP ATTACtlWNT 1 FOR 1KB 79-015 TKR PJCE~

01~

CESAR Page Hei Equips I'o I

Cenerfc Hase Acctd.

Prof 5le Qual.

Profile inside Outside Raga)iyn Qu~l, Qual+

Hechod Chtua.

Spray Replace elocate

hccur, Suba, Licensee Action uCstandfng Cateaory irene oF Identified by YceM ea p

C'.

g5'<3-F7 3-PC /I B

Mor S

-ur8 UL p

L R

1 2

~ lndicacea che ttea fa balou the flood level

~ indicates cha feels fs Sucisfaccory

~ ludlcuceu chs teen fs Noc hppltcl bio

~ ludtcuces che tees ts Unresolved, Licensee fdencfffed

~ Proprietary

~ Licens<<e identified

~ Ruvteuur td<<nttfied KqutpIsent iu qualified

~ bring is less chan life of plant utch licensee indicating periodic replaceeenc r

RNIENR

~

IStE~~

/

I 3 ~ Equfpaant requires aodiffcacfon (resolution, shielding,

~Cc.

4 ~ Qualiffcacion of equipaenC unresolved s)

Testing schedule buc not coaplece b)

Revieuer ne<<da additional fnforuacion c)

Qual.

Record search ecfll in process 5 ~ Equtpmenc not qualified 6 I lcea identified co KQB for resolucfon I

AT f d glar I 'I'y Pi g'rf I

I

I I

FACLLilr SlSelf h'llhl Ht1UfC l FOR 1EB )9-0)B TKk

+ex I oi~

CESo Page Ho+

Equip.

Io Do I

Generic hccid Nano Profile Qualo Profile inside Outside Raga)iyn )u)l, Qual.

Hethod Ch~e Spray Replace elocata

Subn, Licenses Action Outstanding Catory ltaas of Idantifia4 by 1 tees PT Pl= 3-pr Zb 7

Pl" PT-3'-

PT Pl VCr tf'u e.

B Wor S

-orH UL P

L R

1 2

>> indicates ths iten is belov the floo4 level

>> ludicatee the iteu is Satisfactory

>> ludicutee the SteLI ie Rut hppllcable ludicutee the itea is Unresolved, Licensee identified

>> Proprietary

>> Licensee identifie4

>> kevieuer id<<ntified

>> Equip>>cut ie qualified

>> Aging is lees thun life of plant vith licensee indicating periodic replacesent 3>> Equipaent requires aodificatfon (resolution, shielding, etc.

4>> Qualification of equipuent unresolve4 a)

Testing schedule but not coeplete b)

Reviever needs additional inforsation c)

Qual. Record search still in procbss 5>> Equipeeut not qualified 6>> iten identified to EqB for resolution ItKVIBIER' OlTE ~~+

FAI'fL Pui O-g8" f>

S v5e~

A'lTAO f

FOR 1KB

-01$

TER NCE X Ot~

CES o Page How Equfpt lo Do I

Cenerfc hccfd.

Same Proflie qu41 ~

Profile

!nside Outafde Ra/la) f~n CP~li l)usl o Hethod Chem.

Spray Replace Relocate hccur Subm.

Licensee Action Outs'tending Oateaory ltese of identified by Items SV P ft>

)>'

s) OS'V

~3 sv P6o V-3" LI S

/

r b

Wor S ot H Dl P

L Rl 2

~ indicates the ftem is belov the flood level

~ indicates the item fa Satisfactory

~ indicates the item fs Hot Applicable

~ Kndfcetes the item fs Unresolved, Licensee identified

~ Proprfet4ry

~ Licensee identified

~ Rovfever identified

~ Equipment fs qualified

~ Aging fs lees than life of plant vfth licensee fndfcating periodic teplacemeut 3 ~ Equipment requires modification (resolutfont shfeldfngg atc.

~ 4 ~ f)uelfficetfon of equipment unresolved a)

Testing schedule but not complete b)

Revfeuer needs additional information c) qual.

Record search still fn process S ~ Equipment not qualified 6 I item identified to Eqb fot teeolutfon I 'C r>

r REVIKQER ~

~'ATE 0

j i

II

PhUI SYSTEH oin~ 'e P~

in 7 /an<

ATT r I FOR IEB 19-Olb TER PACE~

OP~

CES.

Page Ho+

Equfp.

I~

Do v Generic hccid.

Hase Ptofile 5V Quail Profile Inside Outside Rsgla[f~n gull.

Qual.

Hethod Chea.

Spray Replace elocate

Accur, Subn.

Licensee Actioa Outstaadiag Cstesory Itesa oF ldcntffied by Itcas l~r PAV-g-s> I ~ v t/gy e

5 Wor S

-utH UL P

L R

I 2

~ lndicatea the ften ia below the flood level

< Indicates the iten is Satisfactory

~ Indicates the iten is Hot hpplfcable

~ Indicates the iten is Unresolved, Licensee identified a Proprietary

~ Licensee identified a Ravfeuet identified

~ Equfpaent is qualified Aging is less than life of plant ufth licensee indicating periodic teplaceaent

/

I RZVIEUER 3 a Equfpaent requires nodiffcation (resolution, shielding, atc.

4 ~ Qualification of equipaent unresolved a)

Testing schedule but not coaplete b)

Revlever needs additional fnfotastfon c) goal.

Recotd search still in process 5 ~ Equipaent not qualified 6 a Iten identified to EQB for tesolution gp/.fJ E~

~ass

Phui SISml F

Wa Hi~ C r c'a~

ATTA r I fOR IEB )9-OIS TKR naa~or

/

CESAR Page Moo Equip.

Io Do I

hbV l u3 Generic Nane Accidi Profii Qual.

Profile Inside Outside Ragafi~n gu~i ~

Qual.

)method CheDl ~

Spray Accur.

Subn.

Replace elocate Licensee Action Outstanding Cateeory Itees of Identified by Itees hl)V~3-iwoC std Y 4> V I pZ e

B Wor S

-orN UL P

L Rl 2

~ Indicates the iten is below the flood level

~ Indicates the iten ie Satisfactory

~ Indicates the iten is Hot Applicable

~ Indicates the iten ie Unresolved, Licensee identified

~ Proprietary

~ Licensee identified

~ Reviewer identified

~ Kquipacnt iu qualified

~ Aging is less chan life of plant with licensee'ndicating periodic replacenent 3 ~ Kquipnent requires aodification (resolution, shielding, <<tc.

4 ~ Qualification of equipnent unresolved a)

Testing schedule but not coaplete b)

Reviewer needs additional infornation c)

Qual.

Record search still in process 5 ~ Equipaent not qualified 6 ~ Iten identified to KQB for resolution REViBIERc~C'+

OA'm ~~~ >

A 4'

PhgfLfl.

NSTKH Ps; 3,'g> -gS O hTrhgtN FDR 1Kb lb" lb

'FKR toox~oi ?.

CKS ~

Page Hoo Kquip.

lo Do I

L7 Cenerfc Hans Accido Proffle

Qual, Raga)i)n )u~l.

p if1 n a na A

Inside Out sfde Qual.

Chm.

Hathod Spray hccuro Subno Licensee hctfon Replace elocate Outstanding Cateeory lteaa o'

fdentified by lte@a Lr-g-

!T Av. l7= 3t5 ir-a-l7= 3-SV dd fY-3.-

0 S V /Z r b

Wor S

-or H UL P

L Rl 2

~ indicates the iten fs belou the flood level

~ indicates the iten is Satfsfactory

~ indicates the iten ie Hot hpplicable

~ indicates the iten ie Unresolved, Licensee identified

~ Proprietary

< Licensee identified

~ Rovieuer identified

~ Equlpacnt is qualified

~ hglng is leu>> than life of plant uith licensee indicating periodic replaceaent 3 ~ Kqufpaent requires nodificatfon (resolutfony shielding, atc.

4 ~ Qualfffcation o! equipaent unresolved a)

Testing schedule but not coeplete b)

Rcvieuer needs additional inforaatfon c)

Qual. Record search still in process 5 ~ Equipment not qualified 6 ~ ltca identified to KQB for resolution c.i.('a 4 i:,:; -.,

omvmso~

oooo io

I

PAI:ibl SVSml A'ITAL FOR IE5 79-01$

PACE~ Ot 2 CES e Page IIoo Equips lo Do

]

Pgf~ ).

Caaertc IIaaa hccidi Proffla

qual, Proffle Inside Outside Regia)fyn gull.

Qusli Hethod ChLD o Spray Replace elocate

Accur, Subn, Licensee Actioa Outstaading Catesory ltees of identified by Iteas pp5 igo e'

Wor S

-ur II UL P

L Rl 2

~ Indicates the itea ia belou the flood level

~ lndfcatea the iten ia Satisfactory

~ Indicates ths iten fs IIot Applicable

~ Indicates the iten is Unresolved, Licensee identfffed

~ Proprietary

~ Licensee identified

~ Ravieuer identified

~ Equfpaunt iu quaLified

~ Aging is less thsn life of plant ufth licensee fndicsting Periodic rePlaceaent 3 ~ Equfpaent requires aodfffcation (resolution, shielding, atc.

4 ~ qualification of equfpaent unresolved a)

Testing schedule but not cosplete b)

RevfcMer needs additional fnforastioa c) qual.

Record search still fn process 5 ~ Equipnent not qualified 6 ~ iten identified to Eqg tor resolution i.,'t...

I 4 saviour~ ~><~P'4'

t

Phgl 3

~'o P~D STSTEN Ca(i s~> ~ F>

Md~'~ "t*"

A1TA FOR 1EN 79-0)S TER a(a~or ~

CESo Page Noe Equip.

I~

D0 j

Generic Nano Accidi Profile Qual+

Profile inside Outside Regia)iqn )u~l, Qual.

Hcthod Chm.

Spray Accur.

Subn.

Replace elocate Licensee Action Outstanding Cateeory it<<as of identified by 1 tees Nsv-9 ~

(2 p go V-3.

IVI2

~o+

+')3 SY J 5)( 3~

J>

/,2 sV-3-j S'-l7 o e:

R Wor S

-orN UL P

L Rl 2

~ Indicatca the iten is belov the flood level

~ indicates the iten is Satisfactory

~ indicates the iten ia Not Applicable

~ indicates the itel is Unresolved, Licensee identified

~ Propri<<tery

< Licensee identified

~ Ravieuer identified

~ Equipeent iu qualified

~ Aging ie lees than life of plant with licensee indicating periodic replaccnent 3 ~ Equipnent requires aodification (resolution, shielding, etc.

4 ~ Qualification of cquipnent unresolved a)

Testing schedule but not cosplete b)

Revieuer needs additional infonaation c)

Qual. Record search still in process 5 ~ Equipnent not qualified 6 ~ Iten identified to EQI for resolution 7c gesf,)gg(t gj (r r

~ e, I llgle v e<<E(e~rnne

~d

> HV

( (

~ ~

1 I

FACIL SYSTEH

, Qp Psd

~)]f),f~Hi~

ATTAI l

FOR IKB

-Olg TER eeoc

/

ee~

CES>>

Page Hoo Kquip.

I>>

Do I

T'r 3 Gener'ic hccid.

Hans Profile Qual ~

Profile Rage)iqn qual ~

inside Outside Qual.

Method Chua.

Spray hccur.

Subno Licensee Action Replace elocate Outstandillg 1 cess Identified by Category or Ice%a v/

o Ve 18 I

-3 Z+

78 U-3 "

+vs v 9-4.

e:

&3-3~a 78 7&Z-7 g

Mor S

-orH UL P

L RI 2

~ Indicatea the iten is belou the flood level

~ Indicates che iteea ia Satisfactory

~ Iudicatcs tha iten ia Hoc hpplicable

~ Indicates che iten ia Unresolved, Licenses identified

~ Proprietary

~ Licensee identified

~ Revieuer identified

~ Equipacnc iu qualified

~ hglng is Iees than life of plane ulth licensee indicating periodic replaceaent 3 ~ Kquipnent requires aodification (resolution, shielding, etc.

4 ~ Qualification of equipsent unresolved s)

Testing schedule but noc cosplete b)

Reviever needs additional inforuation c).Qual.

Record search still in process i ~ Equipwent not qualified 6 ~ Icea identified to KQg tor resolution eeveeeee~

eeoc ~<>

/e~d

~ ~

I

Fhgt

~

Pl 3

o ~O SYSTEH 8 Jl A17 V>

>.le >(n~

ATTACHMENT 1

FOR IEB 79-01$

TER p~a~op~

CES ~

Page No+

Equipi I~

Do I

E Generic Accid.

Rane Profile

'Qual+

Profile inside Outside Raga)i~n Jug Qual.

Method Chum.

Spray Accuto

Subn, Licensee Action Replace elocate Outstanding Iteas identified by Category Tteas

&3-7P $

~+7 9-6' Co el B

~or S

-orN UL P

L R

1 2

~ indicates the iten is below the flood level

~ indicates the iten is Satisfactory

~ indicates the itea is Not Applicable

~ !ndicates the iten is Unresolved, Licensee identified

~ Ptopriutaty

< Licensee identified

~ Rovieuer identified

~ Equipacnt is qualified

~ Aging is ious than life of plant uith licensee indicating petiodic replacenent 3 ~ Equipnent requires Nodification (resolution, shielding, atc.

4 ~ Qualification of equipaent unresolved s)

Testing schedule but not coaplete b)

Revieuet needs additional infotaation c)

Qual.

Record search still in process 5 ~ Equipment not qualified 6 ~ iten identified to KQB for tesolution RZV<avER <~ ~i'an ~>>>><i'a

I I

All SYSTEH gin 1" >

gl f

/

A'VfhtqlNKHT l FOR 1KB 79-OLS TKR CES ~

Page lion Equipi lo D

Ceneric hccid Hams Proflie Qual.

Profile inside Outside Raga)iyn Qu~l.

Quail Hethod Clma.

Spray Acean

Subn, Licensee Action Replace elocate Outstanding 1 tees identified by Category ot 1tees RD-g-f-sP R D Fs-g 0-hatt FS

~ Q

-SP F5-3 fs-q-Co e:

B Wor S

-orN UL P

L Rl 2

<5-8.

/

~ Indicates the iten is belou the flood level

~ Indicates the iten is Satisfactory

~ indicates the iten is Not Applicable

~ indicates the iten is Unresolved, Licensee identified

~ Proprietary

~ Licensee identified

~ Rovieuer identified

~ Kquipaent is qualified

~ Aging is less than life of plant uith licensee indicating periodic replaceaont 3 ~ Equipaent requires nodification (resolution, shielding, stc.

4 ~ Qualification of equipment unresolved a)

Testing schedule but not coeplete b)

Reviewer needs additional inforuation c)

Qual.

Record search still in process 5 ~ Equipuent not qualified 6 ~ ltoa identified to EQB for resolution c

RKPTEMKR ~

UATE

~'. >:',~"c'",

/'

FhllLLTi 0/h STSTF2i C *i'nn 7 l~ P.'in HZ~

ATTACHMENT 1 FOR 1EB 19"018 TER tees~ ar~

CES, Page Boo
Equip, io Do

]

Ceneric Accid.

Name Profile Qualo Profile inside Outside Regia)i~n Qu~],,

Qual, Hethod Chum.

Spray Accur.

Subm, Licensee Action Replace elocate Outstanding items op l4entifie4 by Items SV S)/-g-F SV -v'7 p9'n Jo P7=9-Ps g-S'o e:

B Wor S

-or tl UL P

L Rl 2

~ indicates the item ia below the flood level

~ lndicatca the item is Satisfactory

~ indicates the item ia Hot Applicable

~ indicates the item is Unresolved, Licensee identified

~ Proprietary

~ Licensee identifie4

~ Reviewer identified

~ Equipment is qualified

~ Aging is less than life of plant Mith licensee indicating periodic replacement 3 ~ Equipment requires modification (resolution, shielding, atc.

A ~ Qualification of equipment unresolve4 a)

Testing schedule but not complete b)

Revieuer needs additional information c)

Qual. Record search still in process 5 ~ Equipment not qualified 6 ~ item.ideotified to EQB for resolution

)

BEViEUER ii

'ATE

Pal;1LL'1 r STSTKH 7 y bI ATThL'I%Off' FOR lEB 19-01g TKR

>>AGE~ >>>>~

CES ~

Page Ho>>

Equip.

1>> D.

g Generic hccfd.

Mane Profile Qwl>>

Profile inside Oucside Ra(fa)f~n qual>>

Qual >>

ClII>>a>>

Hethod Spray Accur>>

Replace elec>>Ca Suba.

Licensee Action Oucscsndfng Cat<<sory it<<as of Idencified by PS-g-0

- ol

-/IP7 fPrg i/l V o ec g

Mor S

- ur H UL 1'

R 1

2

~ indicates the fcea is below the 1'lood level

~ lnd1cates the iten is Satisfactory

~ ludfcac<> Nut hpplfcahle

~ Indicsce>>

chs 1 tea 1>> Unresolved>>

Lfcenoe<< fd<<nciffed

~ Proprietary

~ Lic<<n>>ea fdentified

~ kuvfeuer identiff<<d

~ Equipsent fe qualified

~ hgfng 1>> le>>s than life of plant ufth iicen>>ee indicating periodic r<<place:w:nt 3 ~ Equipnent requires nodfffcatfon ( eaolucion, shield1ng, etc.

4 ~ Quell 1 1cation of equfpsenc unresolved a)

Tempting schedule but not co>>piete b)

Revfsuer needs additional. infornacion c)

Qual. kecord search still in process 5 ~ Equfpm<<nt not qualified 6 r lc<> lndfcates chs iten fs belou the flood level

>> Indicates cha ftei is Sacfsfsctory

>> lndicateu cha iced fe Rot hpplfceble

>> lndfcacee che ic<<a fs Unresolved, Licensee l4entified Proprietary

>> Licensee ldentifi<<d

>> Revfever ideuclf led

>> Equips<<nc is qualified

>> agfng fu lees chan lff'e of plant ufth licensee ind fcecfng peri04ic replscenenc 2>> Fqufpoent requires aodff fcatfon (reaolutfoa~ shielding ~ etc.

4>> Qualification of equfpnent unresolved s)

Teeciug schedule buc noc conpleco b)

Revieuer needs addlcfonal inforaatioa c)

Qual.

Record search acill in process 5 >> Equipnenc nuc qbalfffed 6 ~ lees idcntific4 to KRB for resolution v

RKyfKRKR

/

PhTE

/

Ã4CfI fyt SYSTEH P

r 7 5

iiu~d f/ 8 ~VMS a

s l-'+ ~~'8 <~s ATTAChhENT l fOR 1KB 79-Ofg TER tom

/

or~

CES ~

Page Boo Equi pi I'.

Genarf c Mama Accfdi Proffle Qual+

Profile Raga[iyn quP.

Inside Outa fde Qual o Hcchod Chm.

Spray Accurs Sub>>.

Replace locate Licensee Action Outstanding lease ldcnciffed by Category of I e>>s ov 5 5

)b trav)

Co e:

B Mor S

-orN UL P

L R

I 2

~ indicates cha ftea ia belov cha flood level

~ indicates the fte>> fs Satisfactory

~ jwdicatee the ite>> fs Hut Applicable

~ indicates the fte>> is Unresolved, Licensee identified

~ Proprietary

~ Lic<<>>see identified

~ Revfever identified

~ Equipment iu qualified Aging is less chan lffe of plant vfth licensee indicating periodic replacement 3 ~ Equip>>ant requires nodiffcacfon (reaolutfon, shielding, ecc.

4 ~ Quelfffcatfon of equipment unresolved u)

Tearing schedule buc not complete b)

Revfevur needs addicfonal infor>>ation c)

Qual.

Record search acill in process 5 ~ Equipment not qualified 6 ~ It<<a identified to KQB for resolution RKyiKMKR W PAlE ~~

C

PACfLffr

~urA'ysmf sec //

e Scl )QD lllbhrid, Jg 8'wc Wpw A'lYAcNMNEl yuR leg 19-Ojg TER

+ca~ or I

CES, Page Ho Equip.

lo Do Ceneric Accid Rase Proffla sw/+

Qualo Profile Raga]iqn fiuti fnsfde Outside Qual.

Nechod Chen.

Spray Accuro Suba.

Lfcansea Action Replace elocace Outs tend fog

?casa Identified by Category t

nW'/a '

S asnQi~

s/

> e:

R rorS

-ur ff UL p

L Rl 2

~ ludicatea the ft<<a ie belov the flood level

~ lndfcut<<s tha ft<<>> fs Sutfsfactory

~ ludfcsc<<s the fc<<>> is Hoc Applicable

~ Indicates the ic<<n fs Unresolved, Licenses fdencffied

~ Propri<<tery

~ Licensee identified

+ kuvfuuer idvntfff<<d

< Equip>><<nc is qualfffed

~ Agfng fs l<<us thun life of plant ufth licensee fnd fearing periodic replacement 3 ~ Equfp>>ent requires nodfffcatfon (resolution, shfeldfnga stci Quslfficacfon of <<qufpnenc unresolved a)

Tescfng schedule but. not co>>plate b)

Reyfuuur ne<<ds additional inforawtfon c)

Qual. Record eeaLch still in process 5 ~ equip>>cut not qualified

& ~ Iten identified co EQS for resolution ungsma ~i-aud

> "g~!J

l

PAI'ikt'I'I I

SESlER E/

h'IThlALHKNF I FOR 1KB 79-0tl TER uoa~ o~~

ol CES.

Page IIoo

Equip, lo D

I Cenerfc Mana Accfdo Proftie Qual.

Proffle Inside Outside Raga)fqn )u~l.

Ual o Hethod Chase Spray Replace elocate iccur.

Suba.

Licensee Action Outstanding Catesory Iteaa oF identified bp 1 tean x -3 3P 3 PR 73p~)

&)'4 O( II0$03 d-))

Swg FP oo

)p )3 f3PP<

gJ A p~onI'IO~, I -)

73

)

EP8

'/6 Co e.

B Wor S

-orN UL P

L R

1 2

~ lndicatea the iten fe below the flood level

~ ludicatca ties ftea fo Satisfactory

~ Indicates the ftua ia Not hppltcuble lndicateu the ftca ta llnresolvcd, licensee identified

~ Proprietary

~ Licensee identified

~ Ruvtewcr tdcnttffcd

~ Equtpacnt iu qualified a hglng tu leva then lite of plant wtth licensee indicating periodic rcplaccaunt 3 ~ Equtpaent requires aodfftcatfon (resolution> shteldfng, etc.

~ IIualtficatton of equtpnent unresolved a) lusting schedule but not coaplete b)

Reviewer nccda additional tnfotaarion c)

IIual. Record scorch sttll tn process 5 ~ Equipccnt not qualit fad 6 ~ ltca identified to kI)B for resolution QEV1ERER Dhlg

/

'1

teaCcl 1 1 r SYSTEtf PM s 7.

/, 4.4 M~ a $/ as 5 hl 1ALttNtta1 1

FOR IEB 29-015 TER eeee~ oe 2.

CES.

P<<gs

tto, Equip.
l. D, Censric Accid.

ttaaee Profile t)usl.

Profilu inside Outside karl<<) la~n go~1, gaa<<l.

H<<thud Chose.

Spr<<y hccur ~

Subn, Licensee Action Replace Relocate Outstsndinl it<<as identified by Category ot iten<<

2-9/

yl 8 P8 p-Zi 7jzgs SPA D]rA>>

a-3~

vzS'~s sr 8 u-33 T z EP8 J -3~

Wzxa3 EP8 CIJ e' Wor S

-orN UL P

L k

1 2

~ 1udlcstss the ltsaa ls bulov the flood lovel

~ indicates the it<<a<< ls S<<tisf<<ctory

~ lwdlcatss ties iteea is tt<<c hppllc<<ble

~ ludlcstus the iteaa ls Unresolva:d, Licenses identified

~ Proprietary

~ Lice:nsuo Jdentifla:d kuvluvsr ldsntlflcd

~'qutpeeuaat ls qualified

~ Aking ls loss ch<<n 11(s of plant vlth licenses lead lc<<Clntl Psr ludlc ruPlaceaa aat 3 ~ Equipsent requires caodiftcacion (resolutiona shieldinga etc.

4 Qu<<ltftcation of aqulpaent unresolved

<<)

Tssc laag schedule bur. n<<t coaeplete b)

Revla ver aaeods <<ddiciunal inforaeuation c) ttual. Record susrrh still in process 5 ~ Equll scut not qu<<lifted 6 << lccm identified to Fi)tt for resolution REV)EME~/'<

DATE i'>~~+',Ra

I

tclc1LIIz 7 I

R}pr}

~ ~d)

EF) ~

  • >/

~

c AA.

A'I'I'AC:I}NENr I FOR IEU )9-OIS TER FACE

/

CF 2 OLCn'>'ES.

Pal@a No.

Equips I ~ D.

Cab'odd Generic Accld.

Hs<<<e Profile gusl.

Profile Inside Outside Ra IfIo) Iyn go~ 1 A I)usl.

Ifethod Ch<<n.

Spray Replace elocate Accur.

Sobs.

Licensee Action Outstanding Cateeory ftess oF identified by.

ltess r

z>hJ I

pVC NS b/d ah/

do bh 41 hh

'}3-/d}

C/

cab)

~9 - u.

Cu <<l a'o

)}><

c,st<

8 Wor S

-ur II UI.

p L

R I

2 indicates th<<

fte<E< is befou the 1'lood level

~ lodfcuc<<s the ice<a is Satisfactory

~ Iloffcatl:s the Itee Is Nuc Apl<lie<<bi<<

iud I<<acus the Ic<<<<E is U<lfe~fved, Licl'nsee identlfied

~ Pruprf <<l.ury

~ Lfc<<lls<<e ldunttff<<d Ruvf<<ver ld<<ntlf I<'d bqufp< \\:oc i<A quu11f I ed AI.I>>U Is less el<un Iffe of plant uith licensee fo I I< at Ill}C P<<rfud lc r<<pl<AC<<<<<ent 3

Equip<<<ant requires <<<edification (resolutfonl shfcldingc stc.

4 IIuslffication of equi pe<<or unresolved s)

T<<scf<}g schedule but not complete b)

R<<vleu<<r n<<<<ds additional io}ur<Eat ion c) goal.

Record search still In proc<<ss S ~ Equip<<<eot oot quslltl<<d 6 o Ice<}< Identiflcd to KJU for resolution REVIEMER~ M

/

O

f<<CfLffr f'ain 7.

SISXEff haiti S 1!s<<

~ff > ~>> >

AI'FACNNENL FOR IE!f 29-01$

TEK a<ca Z

ol~

CES.

Page Noi Equip.

l< D.

dab u g

oafenerfc Accfd.

H<<sae Prof 1 le Qual.

'rof 1 le ~N 0<n.'tnt'nside Outside Qaa<<l ~

Hschod Ch ca<a.

Spray Accur.

Subas.

Replace elocete Licensee Accion Outstanding Cat<<eery Itess oF Idenciffed by.

Ice<a<<<

)).)g c~h/ -"

J3-o 8-2/

c~s/>>

/3-PX

<~ah L))'>b/>>

C<l< e '

Mor S

-orH Ul.

P L

Kl 2

~ l>>dfc<<ce>>

che it<<as ls below che flood level indicate>> the fee<<< fs Sacf>>f>>ccory

~ l>><!fence>> the fceas 1>> Noc Applfc<<ble

~ lndfcuces the fceaaa ls U>>re>>olved, Lfcen>>ee ldentif1ed

~ Proprfa:cary i Lira:>>>>eu lda:ntlfled

~ lhlvfeuer ld<.nt1f la;d Equi pa<<>>lac 1>> a!uallffed AK!>>U fs la>>s than life of pl<<nt ufth l fcen>>ea.

ja)J fracfng p<<rindle replace<<<'IIC 3

EqufPTL>>nt requires sodff ication (resolution, Shiefdfnga etc.

<a Qu>>lf 1'fration of equlpnent unresolved

<<)

Te>>tfaag schedule buc not complete b)

B<<viewer n<<eds

<<ddfcfalnal faaforaa<atlon r)

Qu al. Record>>esrrh a<cfII fn process 5 ~ Equi pm<<>>t >>oc qu>>l11 fed 6 ~ Ice<<a fd<<ntfffed to El/!f for resolutfon a<a<all<a+~A '<T< ~+<

e

r<agfl 1 fc SYSTEH A11ALNNtkl 1

PUR IEg 79-Olg TER PAGE~

GP 2 CES ~

Pug>>

No.

Equip, I. D.

I Generic Accid.

N>>a<le Profile qual.

Profile R>>IIf;a)fyn gull.

[nsfde Outside Qaa>>l, Hechod Chem.

Spray Accur.

Subn.

Replace elocate Licenses Action Outstanding lcesa ldentiflad by, Category Dy Icela>>

7 8w e

~r r ~x

/2 C<) <1 a<

g or S

-orN VLr L

R 1

2

<< lndfcuce>>

che ice>>a is below the flood level

<< lndic>>ce>>

che ice<<a is Szcfef>>ccory

<< la<die>>cela elle feel<a fe Nuc Applic<<ble

<< Iaadfcuce>>

che ft<<n is Unre<<olv<<d, Licensee ldentif led

<<Paopria:c>>ry

<<Lfca:n>>a:u ldentifivd

<<R<<vfvwvr identlf1<<d

<< t<~ufp<aaaat faa quuf ffied

<<Aging fu le<>n life of Pl>>nc wlch 1fcenaaee 1 ad fc>>tlllg per10dfc ra'pl<lee>><alit 3

Equip<<lent requires aodif ication (reaolutfona shielding, etc.

4 Qu>>lffication of equipment unreeolved a)

Te>>tfng schedule but nut co<a<pl>>to b)

Rvviewer needs additional fnfora<uation c)

Qaaul.

Record ae>>rch still in process 5 ~ Equfpa<<ent not qualified 6 ~

fees< identified to E1)5 for resolution

/

REy1E11ER W~

OATE

FA Pc.<

SVSII 7 ZJ nI n sE J A'ITA nNEN'l' FOR IEB 79-OIB TER PACE~ CP~

GEST Page RoA Equip.

l. D.
7. 8'xi3 7.

Zp'enerfc hccfd.

Bane Profile Qual.

Proffl RsItfa)fyn )u~l, Inside Outside Qual.

Hethod ChecE.

Spray Accur.

Suba.

Replace elocate Licensee Action Outstanding Iteas Identified by Category OF Items AQ 7,'x

/-a 7 e>

7; 8'x P ZX 1, 8'Y 33 v) 7 ~r lV. PD 3s 7,

8p'S'."EX

'g-w 7.

Zp'o e:

B Wor S

-orN UL P

L R

I 2

>> lndfcatea tha item fs being the flood level

>> Indicates the fteEE fs Satisfactory

>> Indicates the ft<<m fs Not Applfceble Indicates the ft<<a is Unresolved, Licensee 1dentffied

>> Proprietary

>> LicE:nsce identified

>> Ruvieuet identified

>> Equfpm<<nt fs qusifficd

>> Aging fs less then life of plant fifth lfcensee fad fcating periodic replacement 3>> Equfpaeat tcqufrea modification (resolutfoa, shielding, etc.

4 Qualification of equipment unresolved s)

TestiEEg schedule but not complete b)

Reviever needs add1tional information c)

Qual. Record search still in process 5 >> Equipment not qualified 6 >> Ita:m identified to EQB for resolution P

REVIEWER ~P

~~

DATE A

/

~

~

1I

~ 1

ATTACHMENT 2 FUNCTIONS/SYSTEMS LIST (W)

PWR Needed For Mitigation Of Consequences Of IOCA Or MSLB 1.

Reactor Protection 2.

Safeguards Actuation 3.

Containment Isolation 4.

Main and Auxiliary Steam Isolation 5.

Main and Auxiliary Feedwater Isolation 6.

Feedwater Control 7.

Containment Spray 8.

Containment Air Purification/Cleanup 9.

Containment Ventilation/Cooling 10.

Containment Combustible Gas Control ll.

High Pressure Injection 12.

Iow Pressure Injection 13.

Accumulators 14.

Residual Heat Removal 15.

Chemical and Volume Control 16.

Pressurizer Spray 17.

Power Operated Relief Valves 18.

Steam Dump 19.

Containment Radiation/Monitoring 20.

Containment Radiation/Sampling 21.

Component Cooling Water 22.

Service Water 23.

Emergency Power 24.

Containment Sump 25.

Control Room Habitability 26.

Safety Equipment Area Ventilation 27.

Auxiliary Feedwater 28.

Reactor Coolant

SFCTION C 4 LIST OF UALIFICATION DOCK'iE'tiT REFERENCES (Located in Turkey Point Document Control)

NO.

DESCRIPTION 1 ~

POST LOCA PRESSURE AND TEMPERATURE TBANSIENTS INSIDE CONTAL&KNT-ENGINEERXNG ARQYSXS (5177-M08-124-1

& 5177-M08-124-2) 2.

POST LOCA RADIATION DOSE XNSIDE CONTAI&iENT - MATHEMATICALANALYSIS 3.

FPL LETTER TO USNRC L"75-210 DATED 4"30-75 3.1.

FPL CALCULATION OF T.P.

RECXRC.

SUMP LIQUID PH ADJUSTMENT 3.2 CALCULATION OF POST LOCA CONTAZNMKlT SUMP MVEL 4.

POST LOCA RADIATION DOSE OUTSIDE CONTAPMNT - ~fA~MATICALARM'iSIS 5 ~

FISCHER & PORTER REPORT if DP-2224" 1 RPT

'P 002 6

FISCHER & PORTER REPORT rr DP 2224 1

RPT t 004 7.

FXSCh~R & PORTER TEST REPORT 2204-51-B-006 8.

FISCHZR & PORTER LETTER 3-6-75 WITH AMERON LAB TEST!F 1550a DATED 3-23-72 9.

WESTINGHOUSE LEiTER NS-CE-1586, 10-28-77 10.

JOY ENGINEERING TEST REPORT 1969, V.P. 5610-M-39-41-1 12.

WESTINGHOUSE WCAP"7410-L VOL. I OF II FIM REPORT F-C2639 BY FRANKLQi INSTITUTE RESEARCH LAB (hOV 1969)

WESTINGHOUSE WCAP-7410-L VOL. I OF XI, FINAL REPORT F-C2667 BY FRANKLIN INSTITUTE RESEARCH LAB (NOVEMBER 1969) 13.

WESTINGHOUSE WCAP-9157 SECTION 2-7 AND APPENDICES 14 'ESTINGHOUSE WCAP-7410-L VOL. I OF II SECTION 5 15 ~

WESTINGHOUSE WCAP 7410-L VOL. I OF II APPENDIX D FINAL REPORT F&2485>>01 16.

WESTINGHOUSE WCAP-7410-L VOL I OF II APPENDIX C FINAL REPORT F-C2232-01 17.

FSAR TABLE 6.7-1 18.

FPL LETTER L-75-247 TO NRC, MAY 21, 1975 19.

LIMITORQUE TEST REPORT 0 600198

C

WESTINGHOUSE WCAP-7410-L VOL. II OF II TOPICAL REPORT, ENVIRORKNTAL TESTING ENGIiiERZNG ANALYSIS OF DOUSING VALVES 22.

23.

24.

25.

26.

ANALYSIS OF OPERATING TIME POR DEVICES COVERED IN IE BULLETIN 79-01B MASTER LIST RAYCHEM LETTER 4"14-80 ON HEAT SHRINKABLE TUBING "RNF-100" OKONITE LETTER (MARCH 22, 1971)

TO BECHZEL AND IEEE TRANSACTIONS PAPER, VOL. PAS 88, NO. 5 MAY 1969 BECHZEL LETTER (APRIL 7, 1980)

TO OKONITE AND OKONITE REPLY (APRIL 10, 1980)

ENGINEERING ANALYSIS OF GROUSE-HINDS PENETRATIONS 27.

WESTINGHOUSE SPECIFICATION SHEETS FOR INSTRUMENTS 28.

29.

QUALIFICATION TEST OF LIMITORQUE VALVE ACTUATOR IN A ST~61 ENVZROib~iZiNT FIRL F-C 3271 A STATUS REPORT ON G.E.

WIRE AND CABLE DEPARDEiiT CO~PREHENSIVE TESTZ'.iG PROGRAM WITH COVER LETZER FROM G.E.

DATED MAY 30,

1949, AND MATh MA

~ ICAL ANALYSIS 30.

31.

32 ~

ENGZNEERLXG AiiLYSZS OP THERMOCOL'PLE EXTENSION WIRE CONTIiiEiiZALWLK & CABLE TEST REPORT AiiD MA~TIC ANALYSIS CHARCOAL FILTER TZPERATURE ELBEibZS - ENVIRON'lTAL QUALIFICATZON-ENGIiiERING Ai%LLYSIS 33.

CONTAINMENT-VEC AIR FLOW SWITCHES - ENVIRONMENTAL QUALIFICATION ENGINEERING ARQ.YSIS 34 ~

ITZ BARTON QUALITY RELEASE POR LEVEL TRANSMITZERS 35 ~

ENGINEERING ANALYSIS FOR REPLACEMENT SOLENOID VALVES (INSIDE CONTAIhKNZ) 36.

FISCHER & PORTER DIFFERENTIAL PRESSURE TRANSMITTER - TEMPERATURE EXTRAPOLATION.,

37.

HEAT SHRINKABLE INSULATING SLEEVES " ENGINEERING ANALYSIS BASED ON FZRL REPORT F"C4033"3 37.1 PC/M 79 35

& 36 SIGN OFF INSPECTION SHEETS 38 'NGINEERING ANALYSIS OP MACKWORTH G.

REES LOCAL CONTROL STATIONS 39.

SCOTCH TYPE 23 ELECTRICAL TAPE - PRODUCT DATA & 3M LETTER OP 4-14-80 40.1 FPL LETTERS TO USAEC ON PIPE BREAK ANALYSIS 2-26-73 AND 6-21-73 40 '

41.

USAEC LETTER TO FPL 4-2-73 STATIC 0 RING PRESSURE SWITCHES - ENGINEERINC ANALYSIS ON QUALIFICATION a

l

~ 5 l

)a c

h 42.

ENGINEERING ANALYSIS ON QUALIFICATION OF MOTOROIA PRESSURE TRANSMITTERS 43.

QUALIFICATION TYPE TEST REPORT NO. B0003 LXMITORQUE VALVE ACTUATORS OUTSIDE PRXMARY CONTAIÃKNT 44.

QUALXFICATION TEST REPORT FOR ROSEMOUiNT PRESSURE TRANSiMITTER RMT REPORT NO. 3788 REV. A 45.

ENGINEERING ANALYSXS OF RCS TO RHR INLET ISOLATION VALVES 46.

ENVIRONMENTAL QUALIFICATION/ANALYSISOF UNITED ELECTRXC PRESSURE AND LEVEL COÃZROLLERS 47 ~

48, E1iVIRORfDiTAL QUALIFICATION OF CLASS IE MOTORS FOR NUCLEAR OUT-OF-CONTAIÃ'KNT USE WESTINGHOUSE nCAP 8754 (PAGES 4 1

Sc 5-1)

ENGINEERING ANALYSIS - QUALIFICATION OF SOLENOID VALVE IN AUXXLLXRY BUILDING AND STEA~f LINE BREAK AREAS 49.

ENGLNE RING A,tQYSXS CHARCOAL FILTER DOUSING VALVES 50.

QUALIFXCATXONANALYSIS FOR tt't fCO LIMIT SWITCHES 51.

XSO~EDXX TEST REPORT FOR INSTREKbT CABLE FOR PT-406 A.'R PT-407 RCS PRESSURE TBANSMITZERS 52.

QUALIFICATION OF REPLACPiENT NAMCO CONTROLS LIMIT SNITCH MODEL EA-180-11302 53 ~

ENGI'.JEERING ANALYSIS FOR AGING OF DEVICES COVEP D IN IEB-7901B MASTER LIST 54.

GE~t ELECTRIC LETTER 10 BECHTEL DA'ZED MAY 16, 1980 55.

ENGI~tKERING ANALYSXS OF ITT BARTON PRESSURE CONTROLLERS 6 DIFFERENTIAL PRESSURE SMXTCHES 56.

CHEMPUMP LETTER TO BECHTEL DATED JUNE 10, 1980 I

57 ~

FISHER COÃZROLS LETZER TO FPL DATED MAY 2, 1980 AND TYPE 546 BULLETIN 58.

ENGQKQRING ANALYSIS-RKXATION DETEC'ZORS RD-11, RD-12 59.

= ENGINEERING ANALYSIS OF DAYZON MOTORS 60.

ENGINEERING ANALYSIS AND PRODUCT SPECIFICATIONS FOR FOXBORO INSTEb~ii S

8 I II

~

ti Page 1 of 3 OUTSTANDING ITEMS As Identified By licensee CES ITEN age No.

(See Code CbCl~

P

)

Replace Modify agoing Analysis DISPOSITION Other Disposition

Schedule, Notes

/-3 7

- sob l~/ Cb-~

)

I Ae/ a/~

~ '-/7 Chc~ Vr/

lSV.3-3/o A J.&$ u, 0

4'V 9/0 I

2

-3]oS SV

-3 QDo J+ Sar.

Qdo SY Y o g,t. SM dV 3-V 5

4 41C

i'p

~ 1

Page g, of g F.'ttachment 4

OUTSTANDING ITEMS As Identified By I,icensee C E S

Page No.

ITEM (See Code)

DISPOSITION agoing Analysis Replace Modify Other Disposition

Schedule, Notes sS/g 8g:

T iFT-3 (k 2 /ac

~c 3

IZS ~

- /~>b I

LX'w

-/4' oL/--

s.V SV CV Cu'-

s 7" >X gi 8y

/

VZ/a cp I

>~/

' ') 0

~

Attachment 4

Page 3 of 3 Docket No.:

50-250 NOTES:

l.

Item to be replaced at first opportunity.

l.a Procurement action has been completed and installation will be done during the refueling outage after the satisfactory qualification test of the conduit seal material.

2.

Item could be submerged under water if water level in containment during IOCA reached maximum level.

This willbe relocated at earliest opportunity.

CODE:

It. Sw.. Limit Switch SV

~

~

~

~ ~

~

~

~

~

~

~

~

~

S

~

~

~

~ ~

~

T Solenoid Valve Switch (LS << Ievel SW, PS - Pressure SW, FS - Flow SW)

Transmitter MOV..... Motor Operated Valve Mtl

~

~ ~

~

~

~

~

~ ~ ~

~ ~

C

~

~ ~ ~ ~

~

TE Motor Controller Temperature Element T. Bx... Terminal or Junction Box RD...... Radiation Detector TB...... Terminal Blocks

sic r. W t